The grey
side of the
ECL Card
Ex
tended ser
vic
e
32m
Service parameter(s) 199
199 Master / slave address
Circuit
Setting range
Factory setting
I
0 ... 9, 15
15
The setting is relevant when more controllers are working in the
same ECL Comfort system (connected via the system device bus
(ECL Comfort BUS)).
0:
The slave receives information about the
system time.
1 ... 9: The slave receives information about the
system time.
The slave sends information about the
desired flow temperature (at S2) to the
master.
15:
The controller is master. The master sends
information about the system time.
The master receives the desired flow
temperature information from the slaves
with addresses 1 ... 9.
The bus is active and connected ECAs
(max. 2) are powered.
The ECL Comfort controllers can be connected via the bus to
perform a larger system.
Each slave must be configured with its own address (1 ... 9).
However, more slaves can have the address 0 if they only have
to receive information about compensation temperature and
system time.
The settings 10 ... 14 are not to be used.