New compressors are factory-filled with inert gas. Leave this
service charge in the compressor for as long as possible and prevent
the ingress of air.
Immediately after refrigeration technological connection of
the compressor close the shut-off devices in suction-, dis-
charge-, oil return line etc. and evacuate the compressor.
Check the compressor for transport damage before starting any
work.
4.2 Setting up
Setup on an even surface or frame with sufficient load-bearing
capacity.
Single compressor preferably on vibration damper.
Compound connection basically rigid.
Provide adequate clearance for maintenance work.
Ensure adequate compressor ventilation.
Do not use in a corrosive, dusty, damp atmosphere or a com-
bustible environment.
?
4.1 Storage and transportation
Use transport eyelet.
Do not lift manually!
Use lifting gear!
Storage at (-30 °C) - (+70 °C), maximum permissible relative humidity
10 % - 95 %, no condensation.
Do not store in a corrosive, dusty, vaporous atmosphere or in a com-
bustible environment.
ATTENTION
Attachments (e.g. pipe holders, additional units, fastening parts,
etc.) directly to the compressor are not permissible!
4
|
Compressor assembly