4
|
Compressor assembly
Setup on an even surface or frame with sufficient load-
bearing capacity.
Single compressor preferably on vibration damper.
Duplex and parallel circuits always rigid.
Provide adequate clearance for maintenance work.
Ensure adequate compressor ventilation.
Do not use in a corrosive, dusty, damp atmosphere or a
combustible environment.
Fig. 10
Fig. 11
Fig. 12
ATTENTION! Superheating can damage the valve.
Remove the pipe supports from the valve for soldering.
Only solder using inert gas to inhibit oxidation products (scale).
4.3 Pipe connections
INFO!
New compressors are factory-filled with inert gas.
Leave this service charge in the compressor for as long as possible
and prevent the ingress of air.
Check the compressor for transport damage before starting any
work.
4.2 Setting up
?
4.1 Storage and transport
Use transport eyelet.
Do not lift manually!
Use lifting gear!
Storage at (-30°C) - (+70°C), maximum permissible relative humidity
10% - 95%, no condensation
Do not store in a corrosive, dusty, vaporous atmosphere or in a com-
bustible environment.
Fig. 9
Fig. 8
ATTENTION!
Attachments (e.g. pipe holders, additional units, fastening parts,
etc.) directly to the compressor are not permissible!