User Guide
BasicPlus
2
Room Thermostats
Danfoss Floor Heating Hydronics
VUCUA212
03/2015
The digits indicate the set value as follows:
No.
Parameter settings
Settings range
Default
WT-D/DR WT-P/PR
P01 Working mode
01: Manual
02: Advanced Programmable Timer
NA
02
P02 Temperature control mode
01: Only room temp.;
02: Room and floor temp.;
03: Only floor temp.
01
01
P03 High room temp. limit
5-35° C (only for 01 and 02 in P02)
30° C
30° C
P04 Low room temp. limit
5-35° C (only for 01 and 02 in P02)
5° C
5° C
P05 Floor temp. limitation mode
01: High temp. limitation;
02: Low temp. limitation (only for 02 in P02)
01
01
P06 Floor temp. limitation setpoint
20-45° C (only for 02 in P02)
35° C
35° C
P07 High floor temp. limit
20-45° C (only for 03 in P02)
35° C
35° C
P08 Low floor temp. limit
20-45° C (only for 03 in P02)
20° C
20° C
P09 Frost protection
01: Enable; 02: Disable
01
01
P10 Frost protection setpoint
5-17° C
5° C
5° C
P11 Timer display option
01: 24 h; 02: 12 h
NA
01
P12 Room temp. display option at
shutdown
01: No display current temp.;
02: Display current temp.
01
01
P03 to P08 appear on relevant temperature control mode.
10
Error Messages
E1
Room sensor failure
E2
Floor sensor failure
EE
EEPROM failure
Lo
Temperature lower than 0° C
Hi
Temperature higher than 50° C
All relay output will be turned off in all cases.