4

Installation Guide 

ASV‑PV (DN 15‑50)

SMT/SI 

VI.A6.D2.7O 

Heating Solutions

ENGLISH

Automatic balancing valves ASV-PV is used 

together with shut-off and measuring valve 

ASV-M to control the differential pressure 

in risers where the radiator valves have 

presetting facilities. ASV-PV is also used 

together with adjustment valve ASV-I to 

control the differential pressure and flow 

in risers where the radiator valves have no 

presetting facilities (P/Q control), fig. 

.

ASV-PV maintains constant differential 

pressure across the riser.
Max. working pressure  ...........................16 bar
Differential pressure across valve:

DN 15 - 40  ...........................................10-150 kPa

DN 50  .................................................. 10-250 kPa 

Max. flow temperature............................120 °C

Valve size

Internal 

thread

External 

thread

DN 15

Rp ½

G ¾ A

DN 20

Rp ¾

G 1 A

DN 25

Rp 1

G 1¼ A

DN 32

Rp 1¼

G 1½ A

DN 40

Rp 1½

G 1¾ A

DN 50

-

G 2½

Impulse line: G 1⁄16

Installation 

ASV-PV must be installed in the return 

pipe. The flow must be in the direction of 

the arrow on the valve body fig. 

.

It is recommended that an FV filter be 

installed in the system supply pipe. The 

impulse tube must be fitted on the flow 

pipe, e.g. via an ASV-I or an ASV-M valve.

The tube must be flushed through before 

being fitted on the + connection of the 

ASV-PV automatic balancing valves fig. 

.

ASV-PV must in addition be installed as 

determined by installation conditions. 

When the system has been in use for 

some time, the connections with external 

threads should be tightened once again to 

minimize the risk for leakage.

Shut-off

Turning the ASV-PV knob fully clockwise 

will shut-off the riser fig. 

 

.

Pressure testing

Max. test pressure  ....................................25 bar

Notes:

When pressure testing you must secure that 

both sides of the membrane have the same 

static pressure. That means the impulse 

tube must be connected and any needle 

valves must be open. If ASV‑PV is installed 

in combination with ASV‑M both valves can 

be open or closed (both valves must be in 

the same position!). If ASV‑PV is installed in 

combination with ASV‑I both valves must 

be open. During this operation (closing or 

opening the valves) please make sure that 

there is never lower pressure on upper side of 

the membrane.
If ASV‑ PV is installed in combination with 

ASV‑I do not drain main pipes while leaving 

risers under pressure / filled with water. Doing 

so ASV‑PV membrane would have lower 

pressure on upper side which might damage 

the membrane.

If this instructions are ignored, the 

membrane of the automatic balancing valve 

might be damaged.

Setting/adjustment 

The ASV-PV valves are sold in four different 

∆p setting ranges. The valves are factory–

set to a defined value as described on 

Factory presseting table on fig. 

. Use 

the following procedure to set the desired 

differential presure: the setting on ASV-PV 

can be changed by turning the setting 

spindle fig. 

❷②

Turning the spindle clockwise increases 

the setting; turning it counter clockwise 

reduces the setting.

If the setting is not known, turn the spindle 

fully clockwise. With this the setting on 

ASV-PV is at maximum value within setting 

range. Now turn the spindle a number of 

times (n) as described in fig. 

 until the 

required differential pressure setting is 

obtained. 

Note: 

Do not turn the spindle more than 20 turns as 

it will become disengaged.

The connection (closed, fig. 

 - open, 

fig. 

) can be used for water tapping 

and filling.

Starting

You can fill the system with the drain-

connection on ASV-PV. The system shall 

be ventilated at the highest point. During 

system start – opening the shut-off on 

ASV-PV and partner valve - please secure 

that there is the same static pressure on 

both sides or higher pressure on upper 

side of the membrane (+ connection, 

Fig.

). If filling is done by opening ASV-PV 

and partner valve, please make sure there 

is a pressure on the upper side of the 

membrane by opening partner valve first 

before ASV-PV is opened.

Notes! 

a)  ASV‑PV used with ASV‑M (Fig. 

):  

if this procedure is not followed, the 

membrane of ASV‑PV might be damaged.

b)  ASV‑PV used with ASV/I (Fig. 

):  

If this procedure is not followed, ASV‑PV 

may become locked in closed position 

even if the valve is fully opened.

c)  Both ASV‑PV and ASV‑M/I should be 

always fully opened if used together with 

dedicated shut‑off valves (Fig. 

).

Fault location

Check the following if the riser valve does 

not function correctly:
1.  Is the flow direction through the valve 

correct?

2.  Is the impulse tube fitted correctly and 

are any needle valves open?

3.  Is the valve shut-off open?

Insulation (DN 15 - 40)

The styropor packaging in which the valve 

is supplied can be used as an insulation 

jacket for temperatures up to 80 °C.

Содержание ASV-PV DN 15

Страница 1: ...50 ENGLISH ASV PV DN 15 50 www danfoss com Page 4 DEUTSCH ASV PV DN 15 50 www danfoss de Seite 5 POLSKI ASV PV DN 15 50 www danfoss pl Strona 6 ASV PV DN 15 50 www danfoss ru 7 SVENSKA ASV PV DN 15 50...

Страница 2: ...2 Installation Guide ASV PV DN 15 50 SMT SI VI A6 D2 7O Heating Solutions DN 15 2 5 20 3 25 4 32 5 40 5 50 5...

Страница 3: ...3 41 66 18 7 22 39 64 19 6 21 37 62 20 5 20 35 60 Factory presetting p setting range kPa kPa 5 25 10 20 40 30 20 60 30 35 75 60 Factory presetting p setting range bar bar 0 05 0 25 0 1 0 20 0 40 0 3 0...

Страница 4: ...t drain main pipes while leaving risers under pressure filled with water Doing so ASV PV membrane would have lower pressure on upper side which might damage the membrane If this instructions are ignor...

Страница 5: ...ehalten wird kann die Membran des automatischen Strangdifferenzdruckreglers besch digt werden Einstellung Die ASV PV Ventile sind in vier unterschiedlichen p Einstellbereichen erh ltlich Die Ventile w...

Страница 6: ...wy szezalecenianieb d przestrzegane membrana automatycznego zaworu r wnowa cego mo e ulec uszkodzeniu Nastawianie regulacja Zawory ASV PV s dost pne w czterech r nych wersjach w zale no ci od zakresu...

Страница 7: ...5 Rp G A 20 Rp G 1 A 25 Rp 1 G 1 A 32 Rp 1 G 1 A 40 Rp 1 G 1 A 50 G 2 G 1 16 ASV PV FV ASV I ASV M ASV PV ASV PV ASV PV 25 ASV PV ASV M ASV PV ASV I ASV PV ASV I ASV PV ASV PV p ASV PV ASV PV n Factor...

Страница 8: ...under tryck eller fyllda med vatten Om man g r det r det l gre tryck p vre sidan av membranet i ASV PV vilket kan skada membranet Om denna anvisning inte f ljs kan membranen i den automatiska balanse...

Отзывы: