Akva Vita TDP-F - district heating flat station for direct HE and DHW

Instructions

DH-SMT/PL

VI.KR.Z1.02  ©

  Danfoss 09/2006

6

4. DHW temperature control

The  DHW  temperature  is  controlled  by  a 

proportional valve – the PM controller. The DHW 

temperature control is realized by turning the 

lever towards the red (hot) or blue (cold) mark. The 

temperature should be set to 45-48 °C at normal 

use (7-8 l/min). 

The temperature should never 

exceed 55 °C

 to avoid lime scale precipitation in 

the heat exchanger.

If it is not possible to set the temperature according 

to the above recommendations, it is recommended 

to change the standard controller setting.

PM controller

The  PM  controller  can  operate  in  three  basic  

settings:

- High

- Standard – default

- Low

Approximate setting of PM controller is dependent on 

district heating supply temperature and ∆p:

Supply 

temperature:

 Disposable  differential 

pressure ∆p (bar):

0.2 - 0.5

0.5 -1.0

> 1.0

60 - 70 °C

low

low

standard

70 - 80 °C

low

standard standard

80 - 90 °C

low

high

high

Setting changes:

- dismount lever by using the attached Allen  

wrench,

- remove plastic cap,

- mount lever again and turn it: 

- 1 rotation 

clockwise – high

,

- 1 rotation 

counter – clockwise – low

,

- mount cap and lever again.

Содержание Akva Vita TDP-F

Страница 1: ...s DH SMT PL VI KR Z1 02 Danfoss 09 2006 1 Akva Vita TDP F Table of contents Akva Vita TDP F 1 Table of contents 1 Safety notes 2 Delivery 2 Transport and storage 2 Mounting 3 Pipes connections 4 Elect...

Страница 2: ...he at station has not been damaged during transport Noise level 55 dB Corrosion protection All pipes and components are made of stainless steel and brass The maximum chloride compounds of the ow mediu...

Страница 3: ...pillary tube with union nut from pos 3 to pos 2 Screw the conical screw from pos 2 4 mm on to the mu at pos 3 Connect circulation installation system with connection pipe for circulation Remember pump...

Страница 4: ...s the primary supply for the tted substations enabling the Danfoss Redan substations to be used in numerous schemes with di erent energy sources depending on the local operating conditions In order to...

Страница 5: ...be equipped with an electronic programmable room thermostat and a zone valve with actuator In this case temperature is controlled by the room thermostat and radiator thermostats Please note that the r...

Страница 6: ...If it is not possible to set the temperature according to the above recommendations it is recommended to change the standard controller setting PM controller The PM controller can operate in three ba...

Страница 7: ...1 20 C 2 30 C 3 40 C 4 45 C I 50 C max temp 5 Filters Filtersshouldfrequentlybecleanedfromsediments by authorized personnel according to producer s instructions and depending on the at station s oper...

Страница 8: ...logged Defective non return valve in thermostatic battery DHW tap temperature lower than DHW from at station Defective non return valve in hot water circulation circulation return pipe is getting cold...

Страница 9: ...t in the zone valve housing Air pockets in the system Clean gate strainer Clean the lter after consulting the district heating plant Check the operation of the di erential pressure controller clean th...

Страница 10: ...33 35 DK 8240 Risskov Denmark Phone 45 87 43 89 43 Fax 45 87 43 89 44 redan danfoss com www redan danfoss dk Akva Vita TDP F district heating at station for direct HE and DHW Instructions DH SMT PL VI...

Отзывы: