English

Changing Refrigerant setting

The setting may be carried out before the level 

transmitter is mounted in the plant.
1.  Before electrically connecting the liquid level  

 

sensor press the calibration pushbotton and  

 

keep it pressed while connecting 24V a.c./ 24 V 

 

d.c. to the sensor and then releasing the    

 

pushbotton.

 

 

NOTE!

 

 

The setting of the sensor for the actual  

 

 

refrigerant may be carried out before  

 

 

the liquid level sensor is installed.

 

 

The default setting is R717

2.  After releasing the calibration pushbotton  

 

observe the present refrigerant setting and  

 

measure the 4-20 mA output signal on  

 

 

terminals 2(+) and 3(-).

 

1 flash of Green LED - output signal is

 

~ 5 mA = R717 (factory setting)

 

2 flashes of Green LED - output signal is 

 

~ 6 mA = R22  

 

3 flashes of Green LED - output signal is

 

~ 7 mA = R404A 

 

4 flashes of Green LED - output signal is

 

~ 8 mA = R134a

 

5 flashes of Green LED - output signal is 

 

~ 9 mA = R744 

3.  Activate the calibration pushbutton to select 

 

required refrigerant. Each activation will cause 

 

AKS 41U to step to next refrigerant according to 

 

below sequence:

 

~ 5 mA = R717 (factory setting)

 

~ 6 mA = R22  

 

~ 7 mA = R404A 

 

~ 8 mA = R134a 

 

~ 9 mA = R744

4.  When the current corresponds to the required 

 

refrigerant, wait 10 seconds until the green LED 

 

is constant ON (not flashing). This indicates that  

 

the required refrigerant has been selected.

5.  To leave the setting mode isolate the voltage  

 

supply to the level transmitter.

 

Go through step 1, 2 and 5 if you wish to check 

 

the setting.

Signal damping

Signal damping is factory-set at 15 seconds. This 

setting can be altered by activating the calibration 

pushbutton, while the level probe is in normal 

operation. The setting range is 1 to 120 seconds. 

Procedure:

1.   Connect the supply voltage.

2.   Push the calibration pushbutton once for each 

 

second by which you want to increase the 

 

damping. Anytime a calibration is started it will 

 

begin with 1 second signal damping. 

 

 

Example:

 

1. push 

  1 sec.

 

2. pushes 

  2 sec.

 

etc.

 

120. pushes 

  120 sec.

 

121. pushes 

  120 sec.

Réglage de l'AKS 41

Les réglages peuvent être effectués avant 

l’installation du transmetteur de niveau.
1.  Avant de mettre sous tension la sonde de 

 

niveau liquide, appuyer sur le bouton-poussoir 

 

de calibrage et le tenir enfoncé tout en 

 

connectant l’alimentation 24 V c.a. / 24 V c.d. à 

 

la sonde ; relâcher ensuite le bouton-poussoir. 

 

 

Attention !

 

 

Respecter impérativement cette    

 

 

séquence. Si vous mettez le  

 

 

 

transmetteur sous tension avant    

 

 

d’appuyer sur le bouton-poussoir de  

 

calibrage, l’amortissement du signal sera 

 

modifié.  Le réglage par défaut est celui du R717.

2.  Relâcher le bouton-poussoir de calibrage, puis 

 

noter le réglage actuel du fluide frigorigène et 

 

mesurer l’intensité du signal de sortie 4 - 20 mA 

 

aux bornes 2(+) et 3(-).

 

1 clignotement de la DEL verte - l'intensité  

 

du signal de sortie est  ~ 5 mA = R 717  

 

 

(réglage en usine)

 

2 clignotements de la DEL verte -  l'intensité  

 

du signal de sortie est  ~ 6 mA = R 22

 

3 clignotements de la DEL verte -  l'intensité  

 

du signal de sortie est ~ 7 mA = R 404a

 

4 clignotements de la DEL verte - l'intensité  

 

du signal de sortie est ~ 8 mA = R 134a

 

 5 clignotements de la DEL verte - l'intensitét  

 

du signal de sortie est ~ 9 mA = R744 

3.  Activer le bouton-poussoir de calibrage pour 

 

sélectionner le fluide frigorigène choisi. Chaque 

 

pression permet à l’AKS de passer au fluide  

 

frigorigène suivant selon la séquence suivante :

 

~ 5 mA = R 717 (réglage en usine)

 

~ 6 mA = R 22

 

~ 7 mA = R 404a

 

~ 8 mA = R 134a

 

~ 9 mA = R744

4.  Lorsque l’intensité du courant correspond au  

 

fluide frigorigène choisi, attendre 10 secondes 

 

jusqu’à ce que la DEL verte soit allumée en 

 

permanence (ne clignote plus), ce qui signifie 

 

que le fluide frigorigène choisi a été sélectionné.

5.  Pour quitter le mode réglage, mettre hors   

 

tension le transmetteur de niveau. Pour    

 

contrôler les réglages, suivre les étapes 1, 2 et 5.

Amortissement de signal

L’amortissement de signal est réglé en usine à 15 

secondes. Ce réglage peut être modifié en activant 

le bouton-poussoir de calibrage pendant que la 

sonde de niveau est en mode d’exploitation 

normale. La plage de réglage s’étend de 1 à 120 

secondes.

Procédure :

1.  Mettre sous tension.

2.  Appuyer sur le bouton-poussoir de calibrage 

 

autant de fois que vous souhaitez augmenter la 

 

durée d’amortissement. Tout nouveau calibrage 

 

commencera toujours par une durée  

 

 

d’amortissement de signal de 1 seconde.

 

Exemple :

 

1 x  pression  

  1 seconde

 

2 x pressions   

  2 secondes

 

etc.

 

120 x pressions 

  120 secondes

 

121 x pressions 

  120 secondes

10 secondes après la dernière pression, la valeur est 

enregistrée dans la mémoire et la DEL verte se 

remet à clignoter. 

Au bout de 10 secondes, une nouvelle pression 

fait passer l’amortissement de signal à 1 seconde 

(si le réglage de l’amortissement est trop élevé, 

redémarrer la procédure à partir de l’étape 1).

Réglage des points de calibrage minimum et 

maximum :

Calibrage du minimum :

1.  Amener le niveau du liquide frigorigène au 

 

niveau minimal souhaité.

2.   Appuyer sur le bouton-poussoir de calibrage et  

 

le tenir enfoncé pendant 5 secondes environ,  

 

jusqu’à ce que la DEL verte s’arrête de clignoter.

3.   Appuyer une fois sur le bouton-poussoir  

 

de calibrage dans un délai de 10 secondes (si  

 

le bouton-poussoir de calibrage n’est pas activé  

 

dans ce délai, l’appareil quitte automatiquement  

 

le mode étalonnage et revient au mode  

 

d’exploitation normale). 

La DEL verte s’allume pendant quelques secondes, 

puis se met à clignoter.

La sortie est désormais de 4 mA et l’AKS 41 ou 41U 

est en mode d’exploitation normale.

Français

10 seconds after the last push, the value will be 

saved in the memory and the green LED will start 

flashing again.

After 10 seconds, a further push will change the 

signal damping to 1-second. (If the damping

setting is set too high, restart the procedure from

step 1).

Adjusting the min. /max. calibration points:

Min. calibration:

1.  Bring the refrigerant liquid level to desired  

 

minimum level.

2.   Press the calibration pushbutton and keep it  

 

activated in approx. 5 seconds, until green LED 

 

stopps flashing.

3.   Activate, within the next 10 seconds, the 

 

calibration pushbutton once (If calibration  

 

pushbutton is not activated within 10 seconds, it 

 

will automatically leave calibration mode and 

 

return to normal operation)

Green LED is ON in a few seconds, and then flashing.

Output is now 4 mA and AKS 41 / 41U is in normal 

operation

Max. calibration:

1.   Bring the refrigerant liquid level to desired  

 

maximum level.

2.   Press the calibration pushbutton and keep it  

 

activated in approx. 5 seconds, until green LED 

 

stopps flashing.

3.   Activate, within the next 10 seconds, the    

 

calibration pushbutton twice (If calibration  

 

pushbutton is not activated within 10 seconds, it 

 

will automatically leave calibration mode and 

 

return to normal operation)

Green LED is ON in a few seconds, and then flashing.

Output is now 20 mA and AKS 41 / 41U is in normal 

operation

Min. calibration when minimum refrigerant 

level must be different from 4 mA:

1.   Bring the refrigerant liquid level to desired  

 

minimum level.

2.  Press the calibration pushbutton and keep it  

 

activated in approx. 5 seconds, until green LED 

 

stopps flashing.

3.  Activate, within the next 10 seconds, the 

 

calibration pushbutton once and keep it    

 

activated. (If calibration pushbutton is not 

 

activated within 10 seconds, it will automatically 

 

leave calibration mode and return to normal 

 

operation)

4.   Observe the output mA signal increasing fast  

 

starting at 4 mA.

5.  Release the calibration pushbutton when the 

 

output signal is approx. 0.5 mA from the desired 

 

point.

6.  All the next activations will increase the output 

 

signal by approx. 0.05 mA

7.  Approx. 10 seconds after the latest activation the 

 

LED starts flashing

8.  Output now corresponds to the value measured 

 

at the latest activation.

Max. calibration when maximum refrigerant 

level must be different from 20 mA:

1.  Bring the refrigerant liquid level to desired  

 

maximum level.

2.  Press the calibration pushbutton and keep it  

 

activated in approx. 5 seconds, until green LED 

 

stopps flashing.

3.  Activate, within the next 10 seconds, the 

 

calibration pushbutton twice and keep it    

 

activated. (If calibration pushbutton is not 

 

activated within 10 seconds, it will automatically 

 

leave calibration mode and return to normal 

 

operation)

4.  Observe the output mA signal decreasing fast 

 

starting at 20 mA.

5.  Release the calibration pushbutton when the 

 

output signal is approx. 0.5 mA from the desired 

 

point.

6.  All the next activations will decrease the output  

 

signal by approx. 0.05 mA

7.  Approx. 10 seconds after the latest activation the 

 

LED starts flashing

8.  Output now corresponds to the value measured 

 

at the latest activation.

Reset to factory setting

AKS 41 can always be reset to factory setting 

regardless of any revised calibration values

1.   Press the calibtation pushbutton and keep it 

 

activated in min. 20 sec, until green LED starts  

 

flashing

2.   Release calibtation pushbutton

3.   When LED starts flashing, reset to factory setting 

 

is completed.

For furter calibration information please see 

technical leaflet RD8AA.

Содержание AKS 41U

Страница 1: ... puede montarse en 4 direcciones Instruction Type AKS 41U ver 4 0 084R9761 084R9761 AKS 41U 76 F t 212 F 60 C t 100 C Type Insertion length AKS 41U 6 6 152 mm AKS 41U 8 8 203 mm AKS 41U 12 12 305 mm AKS 41U 15 3 15 3 389 mm AKS 41U 19 2 19 2 488 mm AKS 41U 23 1 23 1 587 mm AKS 41U 30 30 762 mm AKS 41U 35 35 889 mm AKS 41U 45 45 1143 mm AKS 41U 55 55 1397 mm AKS 41U 65 65 1651 mm AKS 41U 85 85 2159...

Страница 2: ...the level transmitter is required Please contract Danfoss Si vous utilisez un fluide frigorigène qui ne figure pas sur la liste une modification du calibrage du transmetteur de niveau est nécessaire Veuillez contacter Danfoss Si se utilizan otros refrigerantes no relacio nados aquí se requiere una nueva calibración del transmisor de nivel Consultar a Danfoss Factory setting The rod comes factory cali...

Страница 3: ...haitez augmenter la durée d amortissement Tout nouveau calibrage commencera toujours par une durée d amortissement de signal de 1 seconde Exemple 1 x pression 1 seconde 2 x pressions 2 secondes etc 120 x pressions 120 secondes 121 x pressions 120 secondes 10 secondes après la dernière pression la valeur est enregistrée dans la mémoire et la DEL verte se remet à clignoter Au bout de 10 secondes une...

Страница 4: ...permanezca encendido sin parpadear Esto indica que el refrigerante requerido ha sido seleccionado 5 Para salir de la sección de ajustes cortar el suministro de corriente al transductor de nivel Si se desea comprobar el ajuste seguir los puntos 1 2 y 5 Amortiguación de señal El ajuste de fábrica de la amortiguación de señal es de 15 segundos Se puede modificar este ajuste mediante la activación del ...

Страница 5: ...DIR RI5KB55M Danfoss A S RC CMS MWA 01 2005 5 ...

Страница 6: ...6 RI5KB55M Danfoss A S RC CMS MWA 01 2005 DIR ...

Страница 7: ...DIR RI5KB55M Danfoss A S RC CMS MWA 01 2005 7 ...

Страница 8: ...unity Danfoss Industrial Refrigeration A S Stormosevej 10 DK 8361 Hasselager Declaration We hereby declare that below mentioned equipment is in conformity with below mention directives standars or other normative documents provided it is used according to our instructions Description of Equipment Electronic Level Transmitter Type AKS 41U References of other Technical Standards and Specifications us...

Отзывы: