• Connect the device to the power supply
(see the section "Electrical installation/
connection").
• Press 3 times.
• Press
• Press or to select between SINGLE,
COAXIAL D14 and COAXIAL D22. Choose
COAXIAL D14 and press to confirm.
• Press (NO) to confirm
• Press to change the PROBE LENGTH.
Press to change the position of the
cursor.
Press to decrease the value or to
increase the value.
Press to confirm.
• Press to change of SCALE 4 mA.
Press to change the cursor position.
Press to decrease the value or to
increase the value.
Press to confirm.
• Press to change of SCALE 20 mA.
Press to change the cursor position.
Press to decrease the value or to
increase the value.
Press to confirm.
• Wait for QUICK SETUP to complete.
Count down from 8 sec.
• Press to confirm.
• Press or to select between
STORE NO or STORE YES.
Press to confirm.
Default screen appears:
Quick Setup completed
For all other refrigerants:
AKS 4100
QUICK SETUP?
YES NO
AKS 4100
PROBETYPE
SINGLECABLE
AKS 4100
LIQUID CO
2
?
YES NO
AKS 4100
PROBE LENGTH
05000 mm
AKS 4100
SCALE 4mA
04946 mm
AKS 4100
SCALE 20mA
00070 mm
AKS 4100
QUICK SETUP
COMPLETED IN 8
AKS 4100
1.0.0
QUICK SETUP
AKS 4100
1.0.0
STORE NO
AKS 4100
DISTANCE
5000 mm