System Settings
Whilst logged on at a Supervisor level it is recommended to check
the ‘Local Options’ screen. Within this screen it is possible to
define how your AK-SM 800AL behaves when receiving an
alarm(s).
The following (user changeable) options are available;
Front LED
[Enabled / Disabled] – New / Acknowledged alarms will
show RED, no alarms will show Green
Buzzer
[Enabled / Disabled] – Buzzer will activate if new alarm
occurs. Also, when reminder alert is triggered
Internal relay option
[Enabled / Disabled] – Relay 2 will enable
when new or reminder alert triggered
Allow multiple-alarm acknowledge
[Enabled / Disabled] – Allow
bulk acknowledge actions if enabled
Enable alarm logger reminder alerts
[Enabled / Disabled]
– A reminder alert will be triggered if there are any new or
acknowledged alarms in the AK-SM 800AL. The time between
alerts is configurable and the AK-SM 800AL will check to see
if there are any active (new / acknowledged) alarms, every x
minutes.
Number of minutes between alerts
[1-60] – user configurable
Press to clear alarm log on this unit
– as described
Press to clear the database
– as described
Press to reset this unit
– as described
Note
:
With the logger reminder alert set to ‘Enabled’ and a time set
between alerts, the AK-SM 800AL will trigger the front LED (green
and return red), local alarm relay (if enabled), and the unit buzzer
(if enabled). This feature is intended to alert the store staff that
outstanding active alarms (also host network errors) are still
present in the system and minimizes the risk of food loss due to
in-action of alarm condition.