background image

User Guide | Danfoss troubleshooting guide for supermarket electronics

© Danfoss | Climate Solutions | 2022.02

BC337731384771en-000301 | 9

Host Comm/ Host Count Error

1.  Verify the comm and see if the controllers can see each other

a.  If the router is down, the controllers cannot dial out alarms or see each other

i.  Power cycle the router and the controllers (Unit #0 as last)

2.  Verify host comm type (RS 485 or Ethernet)

a.  If Ethernet, go to configure internet (comm 

 internet)

i.  Make sure to have same master IP addresses for every controller and distinctive slave IP 

addresses for each slave controllers

ii.  Verify DNS and DHCP
iii.  If DHCP is set to no, verify default gateway and network mask. Every controller will share the 

same default gateway and network mask

b.  Verify # of AK-SC255’s on network.

i.  i.e. (of x); x should match the total number of AK-SC 255s in host network

3.  Reset #0 (master) to force scan for slave units.

8. AKC 55

AKC 55 IO Relay Chattering

1.  Older RO8 modules ‘chatter’ with AKC 55 v1.061 or higher (incl. 255)
2.  Comm timing needs to be changed from 20s to 4s (backdoor change)

AKC 55 Loses Program on Power Cycle

1.  Battery needs to be replaced (no alarms generate for this). Would need to solder new battery in 

place of existing.

No Communication with AK2 Modules

1.  AKC 55 must be version 1.013 or higher to communicate with AK2 style module
2.  To enter an AK2 style board-point, use the zero key to enter a decimal point.

‘Invalid License’

1.  Try right-click on desktop icon, go to Properties 

 Compatibility tab. Enable check box for ‘Run this 

Program as an administrator’

2.  Uninstall software, reinstall AKA65 software outside of Program Files or Program Files x86 folder.
3.  Obtain generic copy of aka65.ini file, place in C:/Windows folder (replace existing).

‘Unable to locate compatible Win55’ Error

1.  Each version of 255 software that exists requires a separate file on PC to view.

a.  Verify location win55 should exist under Options button in AKA65. Under Directories tab, ‘Win55’ 

path is where file should be placed matching version of controller you are connecting to.

b.  If no file exists matching version of controller, file must be downloaded from 255 support 

website and placed in folder.

Unable to Fully Connect to Site Remotely

1.  If seeing ‘Connection Accepted’ but connection then times out, select Edit button to review setup 

for site.

a.  Drop-down at bottom of setup screen should be set to ‘Ethernet’ for 255, ‘Netmodem’ for AKC55

 

Unable to Direct Connect to AK-SC 255 Locally

1.  Ensure controller address is ‘0’

a.  If not set to 0, will need to connect to 255 that is address 0 (if host network exists)
b.  Otherwise, controller address will need to be changed to 0 and 255 reset

2.  If using Danfoss direct connect cable, ensure you are connecting to port on side of controller, 

above latch

3.  If using crossover cat5 cable:

a.  Ensure connection goes to Ethernet port inside of 255
b.  Ensure PC settings and 255 IP settings allow for both devices to see one another. Process 

documented here: 

  https://www.danfoss.com/enus/search/?query=AX279033702249&filter=documentationLangua

ge%3Aen_en%2CdocumentationArchived%3Afalse

9. AKC 164

10. AKA 65

Sensor Failure Status

1.  If all sensors reading ok, typically an issue with KVQ valve (replace) 
2.  Pins 35, 36 inside KVQ actuator should be ~20k Ω @75F
3.  NTC Temp: 120F = KVQ fully open, 220F = NTC fully closed
4.  Valve opens to 100% in this failure mode

Содержание AK-SM 800A

Страница 1: ...User Guide Danfoss troubleshooting guide for supermarket electronics www danfoss com...

Страница 2: ...C 550A to AK SM 800 7 Dual Temp Setup 7 4 AK CC 750 7 Replacing AK CC 750 7 5 AK XM Modules 7 AKS Temp Sensor not Reading on IO Module 7 AK XM 103A module not coming online 7 Relay will not respond to...

Страница 3: ...should be 24 V AC DC 2 Verify Channel Lonworks enabled on Network Nodes screen a If not enable and rescan afterwards 3 Verify term resistor switch position at AK SM 800 is correct a If 1 loop from pl...

Страница 4: ...4 Replace AK SM 800 IO Offline 1 Verify Power to modules Complete rescan a Power supply to comm modules should be 24 V AC DC 2 Verify Channel Lonworks enabled on Network Nodes screen a If not enable...

Страница 5: ...ue address 3 Verify connection from AK SM 800 to switch and switch to network a Could be the issue with the cable b Power cycle network switch router or cell modem 4 Reset AK SM 800 a Make sure to res...

Страница 6: ...dc c Measure voltage across terminals 31 32 Should be in range of 0 5 4 5Vdc d Verify transducer type Label of transducer should say AKS32R HFC or AKS 2050 CO2 S3 Error E25 1 If no return air s3 senso...

Страница 7: ...e or loose connection between module and probe b If reading closed likely a short in cable between module and probe c If reading expected resistance compare to temp ohm chart for PT1000 move sensor to...

Страница 8: ...ion IO Offline 1 Verify Power to modules Complete rescan 2 Verify Channel Lonworks enabled on Network Nodes screen a If not update and rescan afterwards 3 Verify EOL resistor in place at end of loop a...

Страница 9: ...oftware reinstall AKA65 software outside of Program Files or Program Files x86 folder 3 Obtain generic copy of aka65 ini file place in C Windows folder replace existing Unable to locate compatible Win...

Страница 10: ...Danfoss Climate Solutions 2022 02 BC337731384771en 000301 10...

Отзывы: