User Guide
|
Optyma™ control AK-RC 113 three phase
© Danfoss | DCS (vt) | 2020.03
BC317523579312en-000101 | 11
5.8 List of Level 1 variables
(user level)
To access the second programming level press the UP (
) and DOWN (
) keys and the LIGHT key
simultaneously for a few seconds.
When the first programming variable appears the system automatically goes to stand-by.
1. Select the variable to be modified by pressing the UP (
) and DOWN (
) keys.
When the parameter has been selected it is possible to:
2. View the setting by pressing the SET key.
3. Modify the setting by holding the SET key down and pressing the (
) or (
) key.
4. When configuration settings have been completed you can exit the menu by pressing the (
) and
(
) keys simultaneously and keeping them pressed until the room temperature reappears.
5. Changes are saved automatically when you exit the configuration menu.
6. Press the STAND-BY key to enable electronic control.
5.9 Level 2 programming
(installer level)
5.10 List of Level 2 variables
(installer level)
Variables Meaning
Value
Default
F3
Fan status with compressor off
0 = Fans run continuously
1 = Fans only run when
compressor is working
2 = Fans disabled
1
F4
Fan pause during defrosting
0 = Fans run during defrost
1 = Fans do not run during
defrost
1
F6
Evaporator fans activation for air recirculation.
The fans are activated for a time defined by F7 if they
have not started operating for the time F6. If the time
of activation coincides with the defrost phase,
the defrost end is still awaited.
0 – 240 min
0 = (function not activated)
0 min
F7
Duration of activation of the evaporator fans for air
recirculation
Fans working time for F6
0 – 240 sec
10 sec
dE
Evaporator probe presence
If the evaporator sensor is disabled, defrosts are
carried out cyclically with period d0: defrosting ends
when an external device trips and closes the remote
defrost contact or when time d3 expires.
0 = evaporator sensor present
1 = no evaporator sensor
0
Variables Meaning
Value
Default
r0
Temperature difference
compared to main SETPOINT
0.2 – 10 °C
2 °C
d0
Defrost interval
(hours)
If
d0
= 0 cyclical defrosts Off
0 – 24 hours
4 hours
d2
End-of-defrost setpoint
Defrost is not executed if the temperature read by the defrost
sensor is greater than
d2
.
(If the sensor is faulty defrost is stopped on time set by the d3
parameter)
-35 – 45 °C
15 °C
d3
Max defrost duration
(minutes)
1 – 240 min
25 min
d7
Drip duration
(minutes)
At the end of defrost the compressor and fans remain at standstill
for time
d7
, the defrost LED on the front panel flashes.
0 – 10 min
0 min
F5
Fan pause
after defrost (minutes)
Allows fans to be kept at standstill for a time
F5
after dripping. This
time begins at the end of dripping. If no dripping has been set the
fan pause starts directly at the end of defrost.
0 – 10 min
0 min
A1
Minimum temperature alarm
Allows user to define a minimum temperature for the room being
refrigerated. Below value
A1
an alarm trips: the alarm LED flashes,
displayed temperature flashes and the buzzer sounds to indicate
the problem.
-45 – (A2-1) °C
-45 °C
A2
Maximum temperature alarm
Allows user to define a maximum temperature for the room being
refrigerated. Above value
A2
an alarm trips: the alarm LED flashes,
displayed temperature flashes and the buzzer sounds to indicate
the problem.
(A1+1) – 99 °C
99 °C
tEu
Evaporator sensor temperature display
(displays nothing if
dE =1
)
evaporator
temperature
read only