Manual RS8FB102 © Danfoss 03-2008 

AK-PI 

100

Installation

Preparing the TCP/IP connection

The AK-PI 100 must be linked to the AK-SC 255 physically and also 

with a software setting. You can do this as follows:

1. Connection

Cables are run from the units to a router or to a switch.

2. Setting

a) Router

- Dynamic: If DHCP is enabled, no settings need to be 

changed in the router

- Static: Check that the static address range does not conflict 

with the DHCP range

b) Switch

No direct settings are necessary, but addresses are always 

static for AK-SC 255 and AK-PI 100

c) AK-SC 255

- Choose static if the AK-SC 255 and AK-PI 100 are connected 

by a switch or if the system can be accessed from outside. 

Then configure the IP address (request an IP address from 

the IT officer of the department).

- Select dynamic if the system is self-contained and both units 

are connected to a router. 

d) In the AK-PI 100, set IP addressing to either static or dynamic.

- Choose static if the AK-SC 255 and AK-PI 100 are linked by a 

switch. Then configure the IP address (request an IP address 

from the IT officer of the department).

- Select dynamic if the system is self-contained and both units 

are connected to a router. 

3. If a router or switch is connected, turn it on.

AK-PI 100 configuration

1. Set the address on the front to 0 (0 is the factory setting)

2. Switch on

3. Attach the service tool (the service tool can only be used if the 

address is set to 0)

4. Set AK-PI 100

a. Press the service key button

b. Unlock the configuration

c. Select System setup

d. Enter a name for the controller (the name cannot be seen 

outside the PI unit yet)

e. Select the protocol you want to use (MDM or WTP)

f. Select whether you want to use the “Address offset” function

g. Switch to IP setup if you are using a static IP address. 

Configure the address

h. Lock the configuration

5. Disconnect the service tool

6. Set the address on the front (for example to 12). 

 

The address range is between 11 and 199.

Содержание AK-PI 100

Страница 1: ...Woodley Protokol interface AK PI 100 User Guide ADAP KOOL Refrigeration control systems...

Страница 2: ...orward connection the two units can be linked by a switch In this case the IP addresses are set to static addresses You can choose any addresses but only if nothing else is connected It is easiest to...

Страница 3: ...200 screen Each PI unit is configured with a different address You can choose 11 12 or above e g 21 Addresses 1 to 10 are reserved for sub nets Connection When you configure the system controller the...

Страница 4: ...d In the AK PI 100 set IP addressing to either static or dynamic Choose static if the AK SC 255 and AK PI 100 are linked by a switch Then configure the IP address request an IP address from the IT of...

Страница 5: ...ith Communications I O Network Rescan channels Select the Channel PI 100 200 field Activate the Rescan Network function Click the PI 100 200 button to switch to the next screen Select the addresses to...

Страница 6: ...rols Specify the description file Select No for Pack controller Select the number of controllers in this example 10 Click the Setup button to switch to the next screen Click Edit on the first controll...

Страница 7: ...ss to the following The configuration lock is used with the following settings Communication setting MDM or WTP Address offset setting addresses are configured for all units on the communication line...

Страница 8: ...VA Supply 080Z0053 RS 232 cable between AK PI 100 and Woodley MDM 4 way TPI card 080Z0263 Type Function Application Language Code no AK PI 100 Protokol interface Intermediary link between System cont...

Отзывы: