controller RS8HE202 © Danfoss 2017-07
AK-PC 781A
Configuration of inputs
and outputs
1. Go to Configuration menu
2. Select I/O configuration
3. Configuration of Digital outputs
Press the +-button to go on to the
next page
4. Setup On/off inputs
Configuration - continued
3 - Outputs
The possible functions are
the following:
Comp. 1
Unloader 1-1
Unloader 1-2
Unloader 1-3
Do for Compressor. 2-8
Oil valve comp. 1-8
Lp comp. oil pulse
Oil valve 1-4 (8)
Oil valve separat. 1-8
MT Comp. release
LT Comp. request
Injection heat exchanger
Injection suction line
Injection ON
Fan 1
Fan 2 - 8
HP Control
Valve gas cooler V3gc
Heat recovery
Valve tap water V3tw
Pump tap water tw
Valve heat recov. V3hr
Pump heat recov. hr
Additional heat
Alarm
I'm alive relay
Thermostat 1 - 5
Pressostat 1 - 5
Volt input 1 - 5
PI 1-3
4 - Digital inputs
The possible functions are
the following:
Ext. Main switch
Ext. compr. stop
Ext. power loss
Night setback
Load shed 1
Load shed 2
LT Comp. Release
MT Comp. Request
All compressors:
Common safety
Comp. 1
Oil pressure safety
Over current safety
Motor protect. safety
Disch. temp. safety
Disch. press. safety
General safety
VSD comp. Fault
Do for Comp. 2-8
Fan 1 safety
Do for fan 2-8
VSD cond safety
Reset comp. lockout
LP comp.oil counter
Oil receiver low
Oil receiver high
Oil level comp.1-8
Oil separator low 1-8
Oil separator high 1-8
Heat recovery
tw enable
hr enable
Flow switch tw
Flow switch hr
DI 1 Alarm input
DI 2-10 ...
PI-1 Di ref
External DI PI-1
The following displays will depend on the earlier definitions. The dis-
plays will show which connections the earlier settings will require. The
tables are the same as shown earlier.
• Digital outputs
• Digital inputs
• Analog outputs
• Analog inputs
We set up the controller’s digital input functions by keying in which
module and point on this module each one of these has been connected
to.
We furthermore select for each output whether the function is to be ac-
tive when the output is in pos. Closed or Open.
Open has been selected here for all the safety circuits. This means that
the controller will receive signal under normal operation and register it
as a fault if the signal is interrupted.
Load
Output
Module
Point
Active at
Solenoid valve, oil, Comp. 1
DO1
1
12
ON
Solenoid valve, oil, Comp. 2
DO2
1
13
ON
Solenoid valve, oil, Comp. 3
DO3
1
14
ON
Solenoid valve, oil, Comp. 4
DO4
1
15
ON
Solenoid valve, oil separator
DO5
1
16
ON
Circulation pump tw
D06
1
17
ON
Circulation pump hr
DO7
1
18
ON
Room fan
DO8
1
19
ON
Compressor 1
DO1
2
9
ON
Compressor 2
DO2
2
10
ON
Compressor 3
DO3
2
11
ON
Compressor 4
DO4
2
12
ON
Start /stop of VLT for fans
DO5
2
13
ON
3-way valve, tap water, V3tw
DO6
2
14
ON
3-way valve, Heat circuit, V3hr
DO7
2
15
ON
3-way valve, gas cooler, V3gc
DO8
2
16
ON
We set up the controller’s digital outputs by keying in which module
and point on this module each one of these has been connected to.
We furthermore select for each output whether the load is to be active
when the output is in pos. ON or OFF.
Attention! Relay outputs must not be inverted at unloader valves. The
controller inverts the function itself.
There will be no voltage at the bypass valves when the compressor is not
in operation. Power is connected immediately before the compressor is
started.
Function
Input
Module
Point
Active at
External compressor stop
AI4
1
4
Closed
Level switch, oil, comp.1
AI8
1
8
Closed
Level switch, oil, comp.2
AI9
1
9
Closed
Level switch, oil, comp.3
AI10
1
10
Closed
Level switch, oil, comp.4
AI11
1
11
Closed
Level switch, oil, receiver High
AI1
2
1
Closed
Level switch, oil, receiver Low
AI2
2
2
Closed
Level switch, oil, Separator
AI3
2
3
Closed
Level switch, CO2 receiver
AI4
2
4
Open
Reset of compressor stop
AI5
2
5
Pulse signal
Compressor 1 Gen. Safety
DI1
4
1
Open
Compressor 2 Gen. Safety
DI2
4
2
Open
Compressor 3 Gen. Safety
DI3
4
3
Open
Compressor 4 Gen. Safety
DI4
4
4
Open
Start/stop of heat recovery hr
DI5
4
5
Closed
All compressors common safety
DI6
4
6
Open
Flow switch FStw
DI7
4
7
Open
Flow switch FShr
DI8
4
8
Open
Start/stop of heat recovery tw
AI2
5
3
Closed
Содержание AK-PC 781A
Страница 39: ...AK PC 781A Capacity controller RS8HE202 Danfoss 2017 07 39 Example continued ...
Страница 42: ...42 Capacity controller RS8HE202 Danfoss 2017 07 AK PC 781A ...
Страница 90: ...90 Capacity controller RS8HE202 Danfoss 2017 07 AK PC 781A ...
Страница 133: ...AK PC 781A Capacity controller RS8HE202 Danfoss 2017 07 133 ...