Example: Wizard
Condenser
Set the condenser control as well as control
sensor and reference settings� The pressure
range of the pressure transmitter can be
set�
Pc sensor max� range:
34.0 bar
Pc sensor min� range:
-1.0 bar
Reference mode:
Floating
Setpoint:
30 °C
Min� reference:
15 °C
Max� reference:
45 °C
Capacity ctrl� mode:
Speed
No� of fans:
1
VSD Start via DO:
Yes
Monitor fan safety:
Common
Extra
Select whether to use an alarm relay and
Modbus network address�
Alarm output:
No relay
Modbus address:
100
Summary
Get an overview of the inputs and outputs
generated by the wizard�
Next step
Select which main menu to go to� Press
DOWN to go to the selected menu�
It is recommended to check the IO (input /
output) configuration before starting the
controller�
Apply wizard settings
Press ENTER to apply the wizard settings
to the controller including automatic
assignment requested inputs and outputs�
Press DOWN to go to the selected menu and finish the