Function
Description
Values
Code
Short name
Min OFF time
Minimum time the compressor has to be stopped
c02
c02 Min.Off time
Delay between
comp.
Time delay for couplings of two compressors. The
step delay is the time that has to elapse from the first
compressor cuts in and until the next compressor can
cut in.
c05
c05 Step delay
Step control mode
Selection of step control mode for compressors. At se-
quential mode compressor 1 will always be the first to
start and the last to stop. In cyclic mode the run time
between the compressor will be equalized.
1=Sequential, 2=Cyclic
c08
c08 Step mode
Comp. 2 ctrl. Th.
band 2
Select whether compressor 2 is to be in operation in
thermostat band 2
0=OFF, 1=ON
c85
c85 Cmp2 In Th2
Fan control
Table 31: Fan control
Function
Description
Values
Code
Short name
Control state A
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 2=Min ON timer,
3=Min OFF timer, 4=Drip off, 10=Main switch OFF,
11=Thermostat cut-out, 12=Frost protection S4,
14=Defrost, 15=Fan delay, 16=Forced closing,
17=Door open, 18=Melt period, 19=Modulating
temp. control, 20=Emergency control, 23=Adaptive
superheat control, 24=Start injection, 25=Manual
control, 26=No refrigerant selected, 29=Case clean-
ing, 30=Forced cooling, 31=Door open, 32=Power-up
delay, 33=Air heating, 45=Shut down controller,
48=Adaptive liquid control
u00
u00 Ctrl. state
Fan
Actual status of output function
0=OFF, 1=ON
u59
u59 Fan relay
Fan ECO
Actual status of output function
0=OFF, 1=ON
U37
U37 Fan Eco
Fan pulsing mode
Pulse operation of fan 0: No pulse operation 1: Pulse
operation when the thermostat is cut out2: Pulse op-
eration when the thermostat is cut out, but only dur-
ing night operation
0=No pulsing, 1=Pulsing cutout, 2=Pulsing cutout
night
F05
F05 FanPulseMode
Fan period time
Periodtime for pulsing of fan
F06
F06 Fan cycle
Fan ON cycle
ON time for fan. The ON period is set as a percentage
of the period time
F07
F07 Fan ON %
Fan stop high S5
temp.
Fan stop temperature The function stops the fans in
an error situation, so that they will not provide power
to the appliance. If the defrost sensor registers a high-
er temperature than the one set here, the fans will be
stopped. There will be re-start at 2 K below the set-
ting. The function is not active during a defrost or
start-up after a defrost.
F04
F04 FanStop temp
Fan at forced closing You can set whether fans should be operational or
stopped if the function "Forced closing" is activated
here. 0: Fans are OFF1: Fans are ON2: Fans are OFF and
defrost is not permitted3: Fans are ON and defrost is
not permitted
0=OFF, 1=ON, 2=OFF and suppress defrost, 3=ON and
suppress defrost
o90
o90 Fan ForcedCl
Fan stop at blinds
closing
When blinds are closing the fans are stopped in the
defined time delay in order to ensure that the blinds
are closed correctly
P65
P65 BlindFanStop
Railheat control
Table 32: Railheat control
Function
Description
Values
Code
Short name
Control state A
Readout of the actual control state of the controller
0=Normal ctrl., 1=Hold after defrost, 2=Min ON timer,
3=Min OFF timer, 4=Drip off, 10=Main switch OFF,
11=Thermostat cut-out, 12=Frost protection S4,
14=Defrost, 15=Fan delay, 16=Forced closing,
17=Door open, 18=Melt period, 19=Modulating
temp. control, 20=Emergency control, 23=Adaptive
superheat control, 24=Start injection, 25=Manual
control, 26=No refrigerant selected, 29=Case clean-
ing, 30=Forced cooling, 31=Door open, 32=Power-up
delay, 33=Air heating, 45=Shut down controller,
48=Adaptive liquid control
u00
u00 Ctrl. state
Dewpoint
Actual dewpoint received from system manager via
network
x18
--- Dew point
Rail heat
Actual status of output function
0=OFF, 1=ON
u61
u61 Railh. relay
Railheat power
Readout of the actual rail power in %
u85
u85 Rail DutyC %
Rail heat PWM
Actual status of output function
U59
U59 Railheat PWM