AFP 2 / VFG 22 (221) DN15-250

ENGLISH

Safety Notes

Prior to assembly and commissioning 
to avoid injury of persons and damages 
of the devices, it is absolutely necessary 

to carefully read and observe these instructions.

Necessary assembly, start-up, and maintenance 
work must be performed only by qualified, 
trained and authorized personnel.

Prior to assembly and maintenance work on the 
controller, the system must be:

- depressurized,
-  cooled down,
-  emptied and
- cleaned.

Please comply with the instructions of the 
system manufacturer or system operator.

Disposal instructions

 This product should be dismantled 
and its components sorted, if possible, 
in various groups before recycling or 

disposal.
Always follow the local disposal regulations.

Definition of Application

The controller is used for diffe rential pressure 
control of water and water glycol mixtures for 
heating, district heating and cooling systems.

The technical data on the label plates determine 
the use.

Scope of Delivery 

*)  Impulse tube AF, accessory

Assembly

Admissible Installation Positions 

  media temperatures up to 150 °C: 

Can be installed in any positi on.

  media temperatures > 150 °C. 

Installation permitted only in horizontal 
pipelines with the actuator oriented 
downwards.

Installation Location and Installation 
Scheme 

Return mounting 

Flow mounting 

Valve Installation 

1.  Install strainer 

 before the controller.

2.  Rinse system prior to installing the valve.
3.  Observe flow direction 

 on valve body.

 Flanges 

 in the pipeline must be in 

parallel position and sealing surfaces 
must be clean and without any 
damage.

4.  Install valve.
5.  Tighten screws crosswise in 3 steps up to the 

max. torque.

Actuator Installation 

 The actuator stem must be screwed 
into the valve stem.

1.  Remove the spindle protection cup
2.  Align the actuator stem with the valve stem, 

connect both stems and turn gently the whole 
pressure actuator clockwise with both hands, 
until the stems are fully connected (valve stem 
fully screwed into the actuator stem). 

3.  Release the uninon nut by pulling out the 

blocking spring.

4.  Tight the union nut
5.  Release the pressure actuator by turning it 

counter clockwise for approximately half a 
turn.

6.  Observe the position of impulse tubes 

connection to the valve and align the 
actuator accordingly.

7.  Hold the actuator in the position and tight 

the union nut to the valve with 100- 120 Nm 
torque.

Impulse Tube mounting 

•  Which impulse tubes to use?
 

The impulse tube set AF (2×) 

❻①

 can be 

used: Order No.: 

003G1391

 

or use the following pipes: 

Stainless steel

Ø 10×0.8 

DIN 17458,

DIN 2391

Steel

Ø 10×1

DIN 2391

Copper

Ø 10×1

DIN 1754

•  Connection of impulse tubes 

❻②

 in the 

system 
Installation in return flow 

 

Installation in supply flow 

Connection to the valve 

1.  Remove plug 

 at the valve.

2.  Screw in threaded joint G 1/4 

 with copper 

seal, Torque 40 Nm.

- or -

Connection to the Pipeline 

❽①

No connection downwards/upwards 

, could

bring dirt/air into an impulse tube.
1.  Cut pipe in rectangular sections 

 and 

deburr.

2.  For copper pipe: 

insert sockets 

 on both sides.

3.  Verify the correct position of the cutting 

ring 

.

4.  Press impulse tube 

 into the threaded joint 

up to its stop.

5.  Tighten union nut 

 Torque 40 Nm.

 When installing seal pots 

❽⑧

, please 

observe the Installati on Instructions 
for the seal pots.

Insulation 

For media temperatures up to 120 °C the 
pressure actua tor may be insulated 

.

Dismounting 

 

Danger

Danger of injury by hot water

Prior to dismounting depres surize system or 
use shut off valves on the impulse tubes!

Carry out dismounting in re verse order to 
mounting.

Leak and Pressure Test 

 To prevent damages  on the 
diaphragm pressure must be 
constantly and simultaneously 
increased at the + and − connection 

① 

until the max testing pressure is 
reached.

In case of higher test pressu res, remove impulse 
tubes at the pipelines 

.

Observe nominal pressure 

 of the valve.

Max. test pres sure must not exceed the plant 
testing pressure and must always be lower than  
1.5 × PN

Non-compliance may cause damages at the 
actuator or valve.

Filling the System, Start-up 

 The return flow pressure 

 must not 

exceed the supply flow pressure 

.

Non-compliance may cause damages at the 
controller 

.

1.  Open shut-off devices 

 that are possibly 

available at the impulse tubes.

2.  Slowly open valves in the system.
3.  Slowly open shut-off devices 

 in the supply 

flow.

4.  Slowly open shut-off devices 

 in the return 

flow.

Putting out of Operation

1.  Slowly close shut-off devices 

 in the supply 

flow.

2.  Slowly close shut-off devices 

 in the return 

flow.

Differential Pressure Setting 

Set-point range see rating plate 

1.  Start-up of system, see section 

.

2.  Set flow rate on a motorized valve 

 over 

which the differential pressure is controlled, 
to about 50 % 

3. Adjustment

•  Observe pressure indica tors 

.

•  Turning to the right 

 increases the  set-

point (stressing the spring)

•  Turning to the left 

 redu ces the  

set-point (un-stressing the spring)

4.  The set-point adjuster 

 may be sealed.

5.  Release the not yet used pointer 

, move it 

to the set position and fix it with the screw

Dimensions 

Flanges: connection dimensi ons acc. to  DIN 2501, seal form C

Содержание AFP 2/VFG 22 (221)

Страница 1: ...GLISH Differential Pressure Controller AFP 2 VFG 22 221 www danfoss com Page 7 AFP 2 VFG 22 221 DN15 250 Operating Guide This document is included in the scope of delivery The latest document version is available on virtus danfoss com ...

Страница 2: ...NCE FREE AF 2 DN 15 50 Tmax 150 C Bellows VFG2 VFG21 AFP 2 AFP 2 1 V1 V2 630 cm2 AF 2 Bellows VFG2 DN 15 50 Tmax 200 C Piston VFG22 VFG221 DN 65 250 Tmax 150 C AF 2 AFP 2 AFP 2 1 V1 V2 630 cm2 AF 2 DN 65 250 Tmax 200 C Bellows VFG 22 Available from Q4 2018 adapter 003G1780 adapter 003G1780 3 mm SW13 19 36 46 ...

Страница 3: ... Danfoss 2018 01 3 VI LI H1 02 AFP 2 VFG 22 221 DN15 250 SW46 Max 100 120 Nm Turn till end Pull out Hold Fix Release for turn ...

Страница 4: ...4 Danfoss 2018 01 VI LI H1 02 AFP 2 VFG 22 221 DN15 250 G 1 4 AF T 120 C T 120 C T 150 C SW 19 40 Nm SW 13 SW 19 40 Nm ...

Страница 5: ...221 DN15 250 EN GJL 250 GG 25 VFG VFGS PN 16 VFG PN 25 EN GJS 400 GGG 40 3 VFG PN 40 EN GP 240 GH GS C 25 Δp 1 3 bar Type AFP 2 Code Nr 003G5650 p 1 3 bar Tmax 150 C Area cm2 80 SW46 Max 100 120 Nm Turn till end Hold Fix Release for turn Pull out ...

Страница 6: ...213 239 239 241 241 H 267 267 304 304 323 323 Size ØA HA Weight cm2 mm kg 80 175 485 10 160 228 505 13 5 320 295 505 20 5 630 300 630 36 Total installation height of the controller VFG 22 1 valve AFP 2 pressure actuator is sum of HV and HA DN L B H HV Weight PN 16 PN 25 PN 40 mm kg 65 290 220 345 285 24 25 26 80 310 220 345 285 29 30 32 100 350 260 405 345 47 48 50 125 400 260 425 365 60 62 60 150...

Страница 7: ...s to use The impulse tube set AF 2 can be used Order No 003G1391 or use the following pipes Stainless steel Ø 10 0 8 DIN 17458 DIN 2391 Steel Ø 10 1 DIN 2391 Copper Ø 10 1 DIN 1754 Connection of impulse tubes in the system Installation in return flow Installation in supply flow Connection to the valve 1 Remove plug at the valve 2 Screw in threaded joint G 1 4 with copper seal Torque 40 Nm or Conne...

Страница 8: ...s the right to alter its products without notice This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary eady agreed All trademarks in this material are property of the respective companies Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved AFP VFG 2 21 DN 15 250 ...

Отзывы: