12 

User 

Guide RS8KH202 © Danfoss 2019-03 

AK-PC 

572

Compressor status

Compressor status

Comp. 1 status

Read the operating status for compressor 1 here. The following information may appear:
Alarm - Alarm situation
Main Sw. off - Compressor is stopped
Manual ctrl. - Compressor is cut out on safety input (DI safety input)
High Sd temp. - Stopped due  to high Sd temperature
Ready - Compressor is ready to start
OFF timer - Compressor is waiting for Min OFF timer to expire
Min. ON timer - Compressor is waiting for Min ON timer to expire
Running - Compressor is running
Disabled - Compressor has been taken out of operation (compressor service)

Comp. 2....

The same function for the remaining compressors

Compressor capacity

Compressor capacity

Comp. 1 cap.

Read the connected capacity of the compressor (0-100%) here

Comp. 2......

The same function for the remaining compressors

Compressor runhours

Compressor run hours

Reset runtime/cycles

Reset all of the hour counters and start counters for the subsequent compressors here.

Comp.1 Runtime L

Read the total operating time of the compressor (in hours) here 

Comp.2.....

The same function for the remaining compressors

Compressor cycles

Compressor cycles

Comp.1 Cycle total

Read the number of times the compressor has been started here

Komp.2.....

The same function for the remaining compressors

Compressor service

Compressor service

Comp.1 out of service The compressor can be taken out of operation, so that the controller regulates without this 

compressor.
No = Normal regulation
Yes = Regulating is carried out without this compressor, and no alarms are generated by it.

Yes /No
Fac: No

Comp.2.....

The same function for the remaining compressors

Suction  LT

Suction group LT . 

Please see descriptions under suction group

 MT. 

 (In suction group LT it is not possible to use: Bitzer CRII, Po optimisation and night-time reduc-
tion).

Gas cooler

 Control status

Regulation status

Control status

Here you can read the status of the condenser circuit, e.g.:
• Main Sw. off - Main switch = OFF

• Normal - Controller working as expected
• Emergency – Emergency Controls

• Manual ctrl - Capacity control is set in manual control mode

Pgc

The current value of the regulation sensor can be read here

Sgc

The current value of the regulation sensor can be read here

Pgc Reference

The total regulation reference can be read here

Sgc Reference

The total regulation reference can be read here

Vhp OD

Here you can see the opening degree of the Vhp valve

Fan running capacity

Here the connected capacity can be read as a % of total capacity

Fan requested 
capacity

Here the preferred connected capacity can be read as a % of total capacity

Sc3 air on cond.

The measured outdoor temperature with sensor Sc3 can be read here 

Heat recovery status

Here the status of the heat recovery function can be read

HP safety switch

The status of the HP safety switch can be read here

Day / night status

Here you can see whether the controller is in Day or Night mode

 Control settings

Control settings

Vhp control mode

Regulation type
The regulation is normally set to “Auto”, but it can be changed to “Manual”. 

MAN / AUTO
Fac: AUTO

Vhp manual capacity

When setting to “Manual”, capacity can then be forced set in %.

Min: 0 %
Max: 100%

Содержание ADAP-KOOL AK-PC 572

Страница 1: ...Capacity controller for CO2 mini pack AK PC 572 User Guide ADAP KOOL Refrigeration Control System...

Страница 2: ...t available This could for example be used as an alarm input If the compressor used is not a Bitzer CRII a solid state output can be used for oil management If heat recovery is not used the AUX3 funct...

Страница 3: ...point Based on the configured reference the controller will permit an offset of up to 8K depending on the other control parameters For example Night time increase Fixed 5 K on the MT circuit only Po o...

Страница 4: ...in the transcritical area Reference It is controlled using variable references An outdoor temperature sensor Sc3 must be installed The sensor must be positioned so that it registers the correct out d...

Страница 5: ...overy has been reached and the DI signal disappears the reference will drop once again though it will do so over the course of a few minutes to prevent abrupt changes in the reference A potential rela...

Страница 6: ...UX2 DI It can then be used as an alarm input AUX2 DO The potential relay output can be freely used for liquid injection DE SH or hot gas dumping AUX3 DI This function shares an input with the heat rec...

Страница 7: ...et capacity in night operation e g 25 but with a minimum of one step In the event of a Pgc error the fan capacity that corresponds to how much compressor capacity is connected will cut in Compressor r...

Страница 8: ...will depend on how the set up is made They will illustrate what is regulated Click on the Right Arrow to view e g the following images When an alarm is sent from the con troller you must advance to t...

Страница 9: ...ined on the pages that follow Start screen upon delivery Set up overview There are 2 ways in which the controller can be set up Select the one that is easiest for you either Wizard or a review of all...

Страница 10: ...read as a of total capacity No of running comp The number of compressors in operation can be read here MC PoMT offset The size of a reference displacement on PoMT required from the system unit suction...

Страница 11: ...under Compressor mode Min 1 m3h Max 20 m3h Fac 1 m3h Comp 2 size Set the nominal compressor capacity for compressor 2 Min 1 m3h Max 20 m3h Fac 1 m3h Comp 3 size Set the nominal compressor capacity fo...

Страница 12: ...lation Yes Regulating is carried out without this compressor and no alarms are generated by it Yes No Fac No Comp 2 The same function for the remaining compressors Suction LT Suction group LT Please s...

Страница 13: ...e should be started with a signal on a DI input here No No function DI only A DI input is reserved When a signal is registered the heat recovery function refer ence will become active DI and DO Choose...

Страница 14: ...you can override the hot gas valve Only if hot gas dump is defined in the AUX section Auto Man on Man off Oil Control Limitation It is only possible to use oil management if the solid state outputs DO...

Страница 15: ...be used for an optional function You can choose between the functions Fan error or Alarm D demand DI AUX2 If level signals are not desired for oil management the DI on the high pressure module input w...

Страница 16: ...clock Date and time Used by weekly plan and alarm function Year month date Hours minutes Network Network Modbus Address Set the address of the controller here if it is connected to a system device vi...

Страница 17: ...e MT circuit Once a signal is received the circuit will cut out 6 Signal from the high pressure switch in the LT circuit Once a signal is received the circuit will cut out 7 Signal from compressor 1 i...

Страница 18: ...tch to Auto when the override is to be completed Auto Man 0 100 Expansion modules Manual control of a connection in the HP module and receiver module During normal regulation the function of the outpu...

Страница 19: ...imit for SdMT discharge temperature has been exceeded 10K below safety limit High disch temp SdMT Critical Comp 1MT High disch temp Safety limit for discharge gas temperature has been exceeded Compres...

Страница 20: ...rsion must be 1 13 or newer Once the display s software version has been checked check the display s settings as follows 1 Hold the Enter key and the X key down for 5 seconds until the Bios menu appea...

Страница 21: ...e HP module 97 for the receiver module The addresses will only be used internally between the three modules If anything has gone wrong the two valve modules will have acti vated the function EXD reset...

Страница 22: ...cation and display must be kept separate from high voltage 230 V electric cables Use separate cable trays Keep a distance between high voltage and signal cables of at least 10 cm Cables longer than 3...

Страница 23: ...10 volts from terminals Com AO1 N AO3 and N AO4 PAY ATTENTION TO THE POLARITY of N AO3 and AO4 are galvanically isolated AO1 is not AI Analog inputs Pressure transmitters 4 pcs AI1 AI4 Temperature sen...

Страница 24: ...rnal display If an external display is connected it must be connected to the controller using a wire with a plug See order Communication will take place via Canbus The Canbus termination must be moved...

Страница 25: ...rting As a result the evaporators will not be filled with fluid that can be led to a compressor when the regulation process restarts This function can be achieved through data communication Alternativ...

Страница 26: ...mm2 multi core Approvals EU Low Voltage Directive and EMC demands re CE marking complied with LVD tested acc EN 60730 1 and EN 60730 2 9 EMC tested acc EN61000 6 2 and 3 UL approval Data Pressure tra...

Страница 27: ...G0320 EXD 316 Valve driver Operation from AK PC 572 24 V 084B8042 MMIGRS2 Display unit With buttons and display 080G0294 Wire for display unit L 1 5 m 1 pcs 080G0075 L 3 m 1 pcs 080G0076 List of liter...

Страница 28: ...forbeholder sig ret til uden forudg ende varsel at foretage ndringer i sine produkter herunder i produkter som allerede er i ordre s fremt dette kan ske uden at ndre allerede aftalte specifikationer...

Отзывы: