Assembling the Lower Duct Enclosure
The front cover gasket (10) and front cover plate (9) are not installed during the lower duct assembly. They are installed once the
duct is attached to the mounting backplate.
1.
Install the left and right side gaskets (6) against the back side of the duct enclosure (11).
2.
Place the grill (7) on top of the gaskets. Secure the grill to the enclosure using 4 M5 nuts. Torque to 5.1 Nm (45 in-lb).
3.
Install the gasket (8) on top of the grill.
4.
On the base of the enclosure, install the gasket (12) and then the base cover plate (13) on the enclosure. Secure with 10
M5 nuts and torque to 5.1 Nm (45 in-lb).
5.
On the top of the enclosure, install the gasket (3) and then the top plate (13) on the enclosure. Secure the top plate to
the enclosure with 4 M5 nuts. Torque to 5.1 Nm (45 in-lb).
6.
Install the gasket (1) on the top plate. Leave the paper backing on the adhesive until ready to install on the drive module.
7.
Turn the duct enclosure over so the base of the enclosure is facing up. Install the top side gaskets (4) on the sides of the
top plate (2).
8.
Place a top side cover (5) on each gasket (4). Secure each cover with 5 M5 nuts and torque to 5.1 Nm (45 in-lb).
Illustration 1.4 Assembling the Lower Duct Enclosure
1
Gasket between drive module and top plate
8
Gasket between grill and cabinet
2
Top plate
9
Front cover plate
3
Gasket between duct enclosure and top plate
10
Gasket between duct enclosure and front cover plate
4
Gasket, top side
11
Duct enclosure
5
Top side, cover
12
Gasket between duct enclosure and base cover plate
6
Gasket, side of grill
13
Base cover plate
7
Grill
–
–
Installation Instructions
In-back/Out-back Cooling Kit for VLT®
Parallel Drive Modules
VLT® Series FC 102, FC 202, and FC 302
4
Danfoss A/S © 04/2016 All rights reserved.
MI92J102