background image

Assembling the Lower Duct Enclosure

The front cover gasket (10) and front cover plate (9) are not installed during the lower duct assembly. They are installed once the
duct is attached to the mounting backplate.

1.

Install the left and right side gaskets (6) against the back side of the duct enclosure (11).

2.

Place the grill (7) on top of the gaskets. Secure the grill to the enclosure using 4 M5 nuts. Torque to 5.1 Nm (45 in-lb).

3.

Install the gasket (8) on top of the grill.

4.

On the base of the enclosure, install the gasket (12) and then the base cover plate (13) on the enclosure. Secure with 10
M5 nuts and torque to 5.1 Nm (45 in-lb).

5.

On the top of the enclosure, install the gasket (3) and then the top plate (13) on the enclosure. Secure the top plate to
the enclosure with 4 M5 nuts. Torque to 5.1 Nm (45 in-lb).

6.

Install the gasket (1) on the top plate. Leave the paper backing on the adhesive until ready to install on the drive module.

7.

Turn the duct enclosure over so the base of the enclosure is facing up. Install the top side gaskets (4) on the sides of the
top plate (2).

8.

Place a top side cover (5) on each gasket (4). Secure each cover with 5 M5 nuts and torque to 5.1 Nm (45 in-lb).

Illustration 1.4 Assembling the Lower Duct Enclosure

1

Gasket between drive module and top plate

8

Gasket between grill and cabinet

2

Top plate

9

Front cover plate

3

Gasket between duct enclosure and top plate

10

Gasket between duct enclosure and front cover plate

4

Gasket, top side

11

Duct enclosure

5

Top side, cover

12

Gasket between duct enclosure and base cover plate

6

Gasket, side of grill

13

Base cover plate

7

Grill

Installation Instructions

In-back/Out-back Cooling Kit for VLT®
Parallel Drive Modules
VLT® Series FC 102, FC 202, and FC 302

4

Danfoss A/S © 04/2016 All rights reserved.

MI92J102

Содержание 176F6493

Страница 1: ...on 176F6493 In back Out back Cooling Kit for the VLT Parallel Drive Modules 2 drive system Table 1 1 Part Number for the VLT Parallel Drive Modules In back Out back Cooling Kit Items Supplied Top plate assembly Top cover 1 Gasket top cover 1 Gasket cut out 1 Screws M5x12 11 Enclosure mounting assembly Base mounting plate 38 mm 1 5 in 2 Gasket base mounting plate 2 Gasket frequency converter exhaus...

Страница 2: ...g battery back ups UPS and DC link connections to other frequency converters Wait 20 minutes for the capacitors to discharge fully before performing any service or repair work Measure the voltage level to verify full discharge Installation NOTICE If both a bus bar kit and a back channel cooling kit are being installed in the cabinet install the back channel cooling kit first NOTICE APPROVALS AND C...

Страница 3: ...ll the 12 screw holes around the exhaust top vent openings and insert the 12 M5 X 12 pem studs 3 Drill the 12 screw holes around the intake bottom vent openings and insert the 12 M5 X 12 pem studs Illustration 1 3 Vent Dimensions for Mounting Plate Installation Instructions In back Out back Cooling Kit for VLT Parallel Drive Modules VLT Series FC 102 FC 202 and FC 302 MI92J102 Danfoss A S 04 2016 ...

Страница 4: ...1 Nm 45 in lb 6 Install the gasket 1 on the top plate Leave the paper backing on the adhesive until ready to install on the drive module 7 Turn the duct enclosure over so the base of the enclosure is facing up Install the top side gaskets 4 on the sides of the top plate 2 8 Place a top side cover 5 on each gasket 4 Secure each cover with 5 M5 nuts and torque to 5 1 Nm 45 in lb Illustration 1 4 Ass...

Страница 5: ...screws are secure since the base of the drive module rests on these screws 4 Slightly lean the top of the drive module forward and set the cutouts in the base of the module onto the lower 2 M10 screws in the mounting backplate 5 Slowly push the top of the drive module back against the mounting backplate until the top 2 holes on the module line up with the 2 mounting holes in the mounting backplate...

Страница 6: ...slot 3 Gasket between drive module exhaust and mounting backplate Illustration 1 5 Installing the Drive Modules to the Mounting Back Plate Installation Instructions In back Out back Cooling Kit for VLT Parallel Drive Modules VLT Series FC 102 FC 202 and FC 302 6 Danfoss A S 04 2016 All rights reserved MI92J102 ...

Страница 7: ...m 45 in lb 5 On the front side of the lower duct install the front cover gasket 10 and then the front cover plate 9 Refer to Illustration 1 4 Secure with 8 M5 nuts and torque to 5 1 Nm 45 in lb 6 Install the lower duct assembly for the next drive module 1 Drive module 5 Base mounting plate 38 mm 1 5 in 2 Gasket slot 6 M10 screw 3 Cutout in drive module base that rests on the M10 screw 7 M5x16 scre...

Страница 8: ...n lb 5 Place a gasket 3 onto each exhaust duct spacer 6 Place a gasket 7 onto each intake duct spacer 7 Prepare the back panel cover Refer to Illustration 1 8 7a Cut out the 2 intake and 2 exhaust vent openings in the back panel The openings must match to the intake and exhaust duct spacer openings 7b Drill the 16 screw holes around the vent openings 8 Secure the back panel cover to the frame 9 Se...

Страница 9: ...pacer intake 3 Gasket between the exhaust duct spacer and the back panel 7 Gasket between the intake duct spacer and the back panel 4 Mounting plate Illustration 1 7 Installing the Duct Spacers Installation Instructions In back Out back Cooling Kit for VLT Parallel Drive Modules VLT Series FC 102 FC 202 and FC 302 MI92J102 Danfoss A S 04 2016 All rights reserved 9 ...

Страница 10: ...ce This also applies to products already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respective companies Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved Danfoss A S Ulsnaes 1 DK 6300 Graasten vlt drives danfoss com MI92J102 M...

Отзывы: