Safety Instructions

Refer to 

VLT

®

 DriveMotor FCP 106 and FCM 106 Operating

Instructions

 for detailed information about safety precautions

for installation.

WARNING

DISCHARGE TIME

The frequency converter contains DC-link capacitors, which
can remain charged even when the frequency converter is
not powered. High voltage can be present even when the
warning LED indicator lights are off. Failure to wait the
specified time after power has been removed before
performing service or repair work can result in death or
serious injury.

1.

Stop the motor.

2.

Disconnect AC mains, permanent magnet type
motors, and remote DC-link supplies, including
battery back-ups, UPS, and DC-link connections to
other frequency converters.

3.

Wait for the capacitors to discharge fully, before
performing any service or repair work. The duration
of waiting time is specified in 

Table 1.1

.

Voltage

[V]

Power Range

1)

[kW]

Minimum waiting

time

(min)

3x400

0.55–7.5

4

Table 1.1 Discharge Time

1) Power ratings relate to NO, see VLT

®

 DriveMotor FCP 106 and FCM 106

Operating Instructions.

Connection to FCP 106 or FCM 106

1.

Connect the LOP as shown in 

Table 1.2

 and

Illustration 1.3

.

2.

After completing connections, cut off or isolate
excess wire.

3.

Connect terminal 27 V to +24 V or set

parameter 5-12 Terminal 27 Digital Input

 to 

[0] No

operation

.

Terminal

Dual-speed

operation

Dual-mode

operation

Dual-direction

operation

18

Purple

Gray

19

27

Brown

29

Green

12

Red

50

Yellow

55

Blue

Table 1.2 Electrical Connections

Illustration 1.3 LOP Connections to FCP 106 or FCM 106

Installation Instructions

LOP Connection and Set-up
VLT

®

 DriveMotor FCP/FCM 106

2

Danfoss A/S © 09/2015 All rights reserved.

MI03L202

Содержание 175N0128 IP 65

Страница 1: ...7 included in 175N0128 see Illustration 1 2 LOP cable Illustration 1 1 Local Operation Panel LOP 175N0128 IP 65 Illustration 1 2 Fixture for LOP 175N2717 included in 175N0128 Installation Instructions LOP Connection and Set up VLT DriveMotor FCP FCM 106 Danfoss A S 09 2015 All rights reserved MI03L202 ...

Страница 2: ... capacitors to discharge fully before performing any service or repair work The duration of waiting time is specified in Table 1 1 Voltage V Power Range1 kW Minimum waiting time min 3x400 0 55 7 5 4 Table 1 1 Discharge Time 1 Power ratings relate to NO see VLT DriveMotor FCP 106 and FCM 106 Operating Instructions Connection to FCP 106 or FCM 106 1 Connect the LOP as shown in Table 1 2 and Illustra...

Страница 3: ...tion connect purple or orange wire Select the modes of operation in set ups 1 and 2 Set parameter 0 10 Active Set up to 9 Multi Set up Set parameter 5 13 Terminal 29 Digital Input to 23 Set up select bit 0 Run with set up 1 Run with set up 2 Stop and reset2 if trip Function 3 Dual direction operation connect gray wire Set parameter 4 10 Motor Speed Direction to 2 Both directions Set parameter 5 13...

Страница 4: ...ducts already on order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed All trademarks in this material are property of the respective companies Danfoss and the Danfoss logotype are trademarks of Danfoss A S All rights reserved Danfoss A S Ulsnaes 1 DK 6300 Graasten vlt drives danfoss com MI03L202 MI03L202 130R0393 09 2015 ...

Отзывы: