Non-Programmable 088L5133
English
Press the
Down
button to return to the original temperature set-
ting. If the test fails, check the heating cable and thermostat.
If during normal operation the GFCI trips without the
TEST
button
being pressed, there could be a ground fault! To check whether it
is a ground fault or nuisance tripping, press
Standby/Reset
. If this
causes the red light to go off and stay off, it was nuisance tripping
and the system is operating correctly. If this does not occur, there
is a ground fault! Contact your electrical installer.
Settings
The thermostat has an intuitive menu, allowing it to be easily set.
Press
OK
to access the following options:
FLOOR TEMP Displays actual floor
temperature.
SCALE HIGH
Allows you to set the highest temperature to
which the thermostat can be adjusted.
Press
OK
and change the temperature with
the
UP
or
DOWN
button. Confirm with
OK
.
SCALE LOW
Allows you to set the lowest temperature to
which the thermostat can be adjusted.
Press
OK
and change the temperature with
the
UP
or
DOWN
button. Confirm with
OK
.
C ° / F °
Allows °C (Celsius) or °F (Fahrenheit) to be
selected as the temperature unit.
Press
OK
and change the temperature unit
with the
UP
or
DOWN
button. Confirm with
OK
.
OFFSET
TEMP
Allows the difference in temperature between
the thermostat and a room thermometer to
be set.
Press
OK
. Press the
UP
or
DOWN
button
to set the offset temperature (in steps of
0.2°F/0.1°C). Confirm with
OK
APPLICATION Allows you to select FLOOR SENSOR or
REGULATOR.
FLOOR SENSOR: A floor sensor is used.
Only floor temperature is controlled. (Factory
default)
REGULATOR: The thermostat functions as a
simple regulator and no sensors are used.
Press
OK
. Press the
UP
or
DOWN
button
to select FLOOR SENSOR or
REGULATOR. Confirm with
OK
EXIT
Exits the menu.
Press
OK
to return to the initial display.
Standby
The thermostat has a standby function, which turns off the thermo-
stat and display.
Press and hold the Standby button for 2 seconds. The display
shows
OFF
and then turns off.
To turn the thermostat on again, simply press the Standby button.
Error messages
E0 = Internal failure. Replace thermostat.
E1 = Air sensor defective or short-circuited. Replace thermostat.
E2 = Floor sensor defective or short-circuited. Check floor sensor.