background image

Instructions  RI8RE3ML   ©  Danfoss  10/2016 

   AK-CC 210A

Setting:

1 Open parameter r12 and stop the regulation

2 Select electric connection based on the drawings on page 2

3 Open parameter o61 and set the electric connection number in it

4 Now select one of the preset settings from the table on the right-

hand side

5 Open parameter o62 and set the number for the array of preset-

tings

6 Open parameter r12 and start the regulation

7 Go through the survey of factory settings. Make any necessary 

changes in the respective parameters.

8 For network. Set the address in o03 and then transmit it to the 

gateway/system unit with setting o04.

Array 1-3:   The settings in the grey fields will be changed

English

Parameters

Variant of AK-CC

Min.-

value

Max.-
value

Factory 

setting

Actual 

setting

Function

 Codes

1

2

3

4

5

Normal operation

Temperature (set point)

---

-50.0°C

50.0°C

2.0°C

Thermostat

Differential

***

r01

0.0 K

20.0K

2.0 K

Max. limitation of setpoint setting

***

r02

-49.0°C

50°C

50.0°C

Min. limitation of setpoint setting

***

r03

-50.0°C

49.0°C

-50.0°C

Adjustment of temperature indication

r04

-20.0 K

20.0 K

0.0 K

Temperature unit (°C/°F)

r05

°C

°F

°C

Correction of the signal from S4

r09

-10.0 K

+10.0 K

0.0 K

Correction of the signal from S3

r10

-10.0 K

+10.0 K

0.0 K

Manual service, stop regulation, start regulation (-1, 0, 1)

r12

-1

1

0

Displacement of reference during night operation

r13

-20.0 K

20.0 K

0.0 K

Definition and weighting, if applicable, of thermostat sensors - S4% (100%=S4,  0%=S3)

r15

0%

100%

100%

Activation of reference displacement  r40

r39

OFF

ON

OFF

Value of reference displacement (activate via r39 or DI)

r40

-50.0 K

50.0 K

0.0 K

Alarm

Delay for temperature alarm

A03

0 min

240 min

30 min

Delay for door alarm

***

A04

0 min

240 min

60 min

Delay for temperature alarm after defrost

A12

0 min

240 min

90 min

High alarm limit

***

A13

-50.0°C

50.0°C

8.0°C

Low alarm limit

***

A14

-50.0°C

50.0°C

-30.0°C

Alarm delay DI1

A27

0 min

240 min

30 min

Alarm delay DI2

A28

0 min

240 min

30 min

Signal for alarm thermostat. S4% (100%=S4, 0%=S3)

A36

0%

100%

100%

Compressor

Min. ON-time

c01

0 min

30 min

0 min

Min. OFF-time

c02

0 min

30 min

0 min

Time delay for cutin of comp.2

c05

0 sec

900 sec

5 sec

Compressor relay 1 must cutin and out inversely
(NC-function)

c30

0

OFF

1

ON

0

OFF

Time delay for cutin of compressor 2 during defrost

c92

0 s

30 s

5 s

Defrost

Defrost method (none/EL/GAS)

d01

no

GAS

GAS

Defrost stop temperature

d02

0.0°C

25.0°C

6.0°C

Interval between defrost starts

d03

0 hours 240 hours 8 hours

Max. defrost duration

d04

0 min

360 min

45 min

Displacement of time on cutin of defrost at start-up

d05

0 min

240 min

0 min

Drip off time

d06

0 min

60 min

0 min

Delay for fan start after defrost

d07

0 min

60 min

0 min

Fan start temperature

d08

-50.0°C

0.0°C

-5.0°C

Fan cutin during defrost
0: Stopped
1: Running
2: Running during  pump down and defrost

d09

0

2

1

Defrost sensor (0=time, 1=S5, 2=S4)

d10

0

2

0

Pump down delay

d16

0 min

60 min

0 min

Max. aggregate refrigeration time between two defrosts

d18

0 hours 48 hours 0 hours

Defrost on demand - S5 temperature’s permitted variation during frost build-up. On 
central plant choose 20 K (=off)

d19

0.0 K

20.0 k

20.0 K

Max. duration of -d- in display

d40

5 min

240 min

30 min

Fan

Fan stop at cutout compressor

F01

no

yes

no

Delay of fan stop

F02

0 min

30 min

0 min

Fan stop temperature (S5)

F04

-50.0°C

50.0°C

50.0°C

Auxiliary table for settings
(quick-setup)

Defrost 

stop on 

time

Defrost stop 

on S5

Preset settings

 (o62)

1

2

3

Temperature (SP)

4°C

2°C

-24°C

Max. temp. setting (r02)

6°C

4°C

-22°C

Min. temp. setting (r03)

2°C

0°C

-26°C

Alarm limit high (A13)

10°C

8°C

-15°C

Alarm limit low (A14)

-5°C

-5°C

-30°C

Interval between defrost (d03)

6 h

6h

12h

Defrost sensor: 0=time,1=S5, 2=S4 (d10)

0

1

1

DI1 configuration (o02)

10

10

10

Содержание 084B8530

Страница 1: ... 6 A 10 A Resistive 5FLA 30LRA DO2 Defrost 8 6 A 10 A Resistive 5FLA 30LRA DO3 Refrigeration 2 6 3 A 6 A Resistive 3FLA 18LRA 131 VA Pilot duty DO4 Alarm light rail heat fan or comp fan 4 1 A Min 100 mA 4 A Resistive 131 VA Pilot duty DO1 and DO2 are 16 A relays DO3 and DO4 are 8 A relays Max load must be kept Gold plating ensures make function with small contact loads UL approval based on 30000 c...

Страница 2: ...2 Instructions RI8RE3ML Danfoss 10 2016 AK CC 210A 1 2 3 4 5 o61 Electrical connections Conexão elétrica DI1 DI2 AU Guld Gold Or Oro l max 15 m ...

Страница 3: ...ermostatfølere S4 100 S4 0 S3 r15 0 100 100 Aktivering af referenceforskydning r40 r39 OFF ON OFF Værdi for referenceforskydning aktiveres via r39 eller DI r40 50 0 K 50 0 K 0 0 K Alarm Forsinkelse på temperaturalarm A03 0 min 240 min 30 min Forsinkelse på døralarm A04 0 min 240 min 60 min Forsinkelse på temperaturalarm efter afrimning A12 0 min 240 min 90 min Høj alarmgrænse A13 50 0 C 50 0 C 8 0...

Страница 4: ...ngen S4 100 S4 0 S3 o17 0 100 100 Indgangssignal på DI2 Funktion 0 ikke anvendt 1 status på DI2 2 dørfunktion med alarm ved åben 3 døralarm ved åben 4 afrimningsstart pulssignal 5 ekstern hovedafbryder 6 natdrift 7 skift reference r40 aktiveres 8 alarmfunktion ved sluttet 9 alarmfunktion ved åben 10 møbelrengøring pulssignal o37 0 10 0 Konfiguration af lysfunktionen relæ 4 1 ON under dagdrift 2 ON...

Страница 5: ...eter 2 Tryk på øverste eller nederste knap og find hen til den parameter du vil indstille 3 Tryk på den midterste knap indtil vær dien for parameteren vises 4 Tryk på øverste eller nederste knap og find den nye værdi 5 Tryk igen på den midterste knap for at fastlåse værdien Udkoble alarmrelæ se alarmkode Kort tryk på den øverste knap Indstille temperaturen 1 Tryk på den midterste knap til tempera ...

Страница 6: ...efrost A12 0 min 240 min 90 min High alarm limit A13 50 0 C 50 0 C 8 0 C Low alarm limit A14 50 0 C 50 0 C 30 0 C Alarm delay DI1 A27 0 min 240 min 30 min Alarm delay DI2 A28 0 min 240 min 30 min Signal for alarm thermostat S4 100 S4 0 S3 A36 0 100 100 Compressor Min ON time c01 0 min 30 min 0 min Min OFF time c02 0 min 30 min 0 min Time delay for cutin of comp 2 c05 0 sec 900 sec 5 sec Compressor...

Страница 7: ... 100 Input signal on DI2 Function 0 not used 1 status on DI2 2 door function with alarm when open 3 door alarm when open 4 defrost start pulse signal 5 ext main switch 6 night operation 7 change reference activate r40 8 alarm function when closed 9 alarm function when open 10 case cleaning pulse signal o37 0 10 0 Configuration of light function relay 4 1 ON during day operation 2 ON OFF via data c...

Страница 8: ...arameter r01 is shown 2 Push the upper or the lower button and find that parameter you want to change 3 Push the middle button until the parameter value is shown 4 Push the upper or the lower button and select the new value 5 Push the middle button again to enter the value Cutout alarm relay receipt alarm see alarm code Push short the upper button Set temperature 1 Push the middle button until the...

Страница 9: ...e alarme DI1 A27 0 min 240 min 30 min Atraso de alarme DI2 A28 0 min 240 min 30 min Sinal do termostato do alarme S4 100 S4 0 S3 A36 0 100 100 Compressor Tempo mínimo LIGADO c01 0 min 30 min 0 min Tempo mínimo DESLIGADO c02 0 min 30 min 0 min Tempo de atraso de ativação do comp 2 c05 0 sec 900 sec 5 sec O relé do compressor 1 deve ativar e desativar inversamente função NC c30 0 OFF 1 ON 0 OFF Temp...

Страница 10: ...ando fe chado 9 função de alarme quando aberto 10 limpeza do expositor pressão de pulso o37 0 10 0 Configuração da função de luz relé 4 1 LIGADO durante a operação diurna 2 LIGADO DESLIGADO via comunicação de dados 3 segue a função de DI quando DI estiver selecionado para função de porta ou alarme da porta o38 1 3 1 Ativação do relé de luz somente se o38 2 o39 OFF ON OFF Tempo de aquecimento do tr...

Страница 11: ... Há parada baseada no tempo d Degelo em andamento Primeiro resfria mento após degelo PS Senha requerida Configurar senha Os botões Programar menu 1 Pressione o botão superior até ser mos trado um parâmetro r01 2 Pressione o botão superior ou inferior e localize o parâmetro que deseja alterar 3 Pressione o botão intermediário até o valor de parâmetro ser mostrado 4 Pressione o botão superior ou inf...

Страница 12: ...12 Instructions RI8RE3ML Danfoss 10 2016 AK CC 210A ...

Отзывы: