AD
AP
-K
OOL®
Operating status
(Measurement)
The controller goes through some regulating situations where it is just waiting for the
next sequence of the regulation. To make these “why is nothing happening” situa-
tions visible, you can see an operating status on the display. Push the info button for
3 seconds to see status. If there is a status code, it will be shown on the display. The
individual status codes have the following meanings:
Ctrl. state:
(Shown in all menu displays)
Normal regulation
S0
0
Waiting for end of the coordinated defrost
S1
1
When the compressor is operating, it must run for at least x minutes
S2
2
When the compressor is stopped, it must remain stopped for at least x minutes
S3
3
The evaporator drips off and waits for the time to run out
S4
4
Refrigeration stopped by main switch. Either with r12 or a DI-input
S10
10
Refrigeration stopped by thermostat
S11
11
The refrigeration is stopped due to too low S4 temperature
S12
12
Defrost sequence. Defrost in progress
S14
14
Defrost sequence. Fan delay — water attaches to the evaporator
S15
15
Refrigeration stopped due to open ON input or stopped regulation
S16
16
Door is open. DI input is open
S17
17
Melt function in progress. Refrigeration is interrupted
S18
18
Modulating thermostat control
S19
19
Emergency cooling *)
S20
20
Adaptive control of superheat
S23
23
Start-up phase 1. Signal reliability from sensors is controlled
S24
24
Manual control of outputs
S25
25
No refrigerant selected
S26
26
Appliance cleaning
S29
29
Forced cooling
S30
30
Delay on outputs during start-up
S32
32
Heat function is active
S33
33
Case shutdown
S45
45
Operation with adaptive liquid control
S48
48
Other displays:
Defrost in progress / first cooling after the defrost where the temperature is still
above the thermostat band.
-d-
Password required. Set password
PS
Regulation is stopped via main switch or case cleaning
OFF
The main switch is set to service/manual operation
SEr
*) Emergency cooling will take effect when there is lack of signal from a defined S3 or S4 sensor or signal from the pressure transmitter is outside signal
range. The regulation will continue with a registered average cut-in frequency. There are two registered values – one for day operation and one for
night operation.