Instructions RI8SR1ML © Danfoss 01/2019  

  AK-PC 572

External display

Dimensions

Bitzer CRII

The pulse signal can also be used to control one of the CRII with 2 unloaders (4 cylinders version).
Compressor capacity can be controlled from 10 to 100% depending on the pulsation of the unloaders.
The unloaders are connected to DO5 and DO6.
Connect compressor relay to DO-MT1.

Unloader 2 follows unloader 1
but is offset a ½ period.

Unloader 1

Unloader 2

Important

Read the following before you connect the controller and the two 
valve modules to the supply voltage.

Both valve modules are factory set with the same address. 
In order to give each module the correct address, you must follow 
this procedure:

1. On the two valve modules, remove the terminals with power 

supply.
(The power supply is connected later, but in the correct order).

2. Connect the controller to the power supply
3. Check that the main switch is OFF
4. 

HP

 

module

: Mount the terminal with power supply

5. Wait 5 seconds
6. 

Receiver module

: Mount the terminal with power supply.

Wait 5 seconds

All modules now have power supply and the two modules each 
have their own address: 
96 for the HP module 
97 for the receiver module.
The addresses will only be used internally between the three 
modules.

If anything has gone wrong, the two valve modules will have acti-
vated the function "EXD reset node ID" and the procedure must be 
repeated.

Resetting incorrect addresses in the valve modules:
1. Connect all three modules to the power supply
2. Find the following setting on the controller module

"System"> "Network" > "EXD reset node id's"

3. Set the value to 20
4. Cut out the supply voltage to the valve modules
5. Repeat the earlier procedure.

If you wish to check the addresses of the two valve modules, you 
should carry out the following:
1. Connect all modules to the power supply.
2. Immediately press on both the "X" and "Enter" buttons while the 

controller is starting up.

3. Find the display  "CAN SETTINGS" > "ACTIVE NODES"

The two 1-digits represent the addresses 96 and 97 respec-
tively.
If you remove the connection to a valve module, the display of 
the address will also disappear.

Содержание 080G0294

Страница 1: ...80G0320 24 V a c d c 17 VA EXD 316 084B8042 24 V a c d c 10 VA 1 5 m 080G0075 3 0 m 080G0076 MMIGRS2 080G0294 RI8SR1ML 2019 01 IP 20 20 60 C 0 140 F RH max 90 non condensing AK PC 572 17 VA EXD 316 HP...

Страница 2: ...cm Cables longer than 3 m at the DI input should be avoided Connections DO DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 1 8 I Max 10 A 3 5 10 A 3 5 6 A 4 6 A 4 0 5 A min 50 mA Ioff 1 5 mA 0 5 A min 50 mA Ioff 1 5...

Страница 3: ...10 volts from terminals Com AO1 N AO3 and N AO4 PAY ATTENTION TO THE POLARITY of N AO3 and AO4 are galvanically isolated AO1 is not AI Analog inputs Pressure transmitters 4 pcs AI1 AI4 Temperature se...

Страница 4: ...5 Wait 5 seconds 6 Receiver module Mount the terminal with power supply Wait 5 seconds All modules now have power supply and the two modules each have their own address 96 for the HP module 97 for th...

Страница 5: ...cm Cabos de extens o superior a 3 m na entrada DI devem ser evitados Conex es DO DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 1 8 I Max 10 A 3 5 10 A 3 5 6 A 4 6 A 4 0 5 A min 50 mA Ioff 1 5 mA 0 5 A min 50 mA Iof...

Страница 6: ...dor com isolamento duplo O lado se cund rio n o deve ser aterrado Obtenha 0 10 volts dos terminais Com AO1 N AO3 eN AO4 PRESTE ATEN O POLARIDADE de N AO3 e AO4 s o isolados galvanicamente AO1 n o AI E...

Страница 7: ...te de alimenta o 5 Aguarde 5 segundos 6 M dulo receptor Monte o terminal com a fonte de alimen ta o Aguarde 5 segundos Agora todos os m dulos t m uma fonte de alimenta o e cada um dos dois m dulos tem...

Страница 8: ...halten Bei DI Eing ngen Kabel l nger als 3 m vermeiden Anschluss DO DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 1 8 I Max 10 A 3 5 10 A 3 5 6 A 4 6 A 4 0 5 A min 50 mA Ioff 1 5 mA 0 5 A min 50 mA Ioff 1 5 mA 6 A...

Страница 9: ...Versorgungsspannung an Vermeiden Sie einen Erdschlussstrom Verwenden Sie doppelt isolierte Transformatoren Die se kund re Seite darf nicht geerdet werden 0 10 Volt erhalten Sie von den Klemmen Com AO...

Страница 10: ...mit der Ver sorgungsspannung an 5 Warten Sie 5 Sekunden 6 Empf ngermodul Schlie en Sie die Klemme mit der Ver sorgungsspannung an Warten Sie 5 Sekunden Alle Module werden jetzt mit Spannung versorgt u...

Страница 11: ...aute tension et de signal C bles sup rieurs 3 m l entr e DI doivent tre vit s Raccordements DO DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 1 8 I Max 10 A 3 5 10 A 3 5 6 A 4 6 A 4 0 5 A min 50 mA Ioff 1 5 mA 0 5 A...

Страница 12: ...ation Le c t secon daire ne doit pas tre mis la terre Obtenir 0 10 V des bornes Com AO1 N AO3 et N AO4 VEILLER LA POLARIT DE N AO3 et AO4 sont isol s galvaniquement pas AO1 AI Entr es analogiques 4 tr...

Страница 13: ...al est bien teint 4 HP module Monter la borne avec alimentation lectrique 5 Attendre 5 secondes 6 Module r cepteur Monter la borne avec l alimentation Attendre 5 secondes Tous les modules sont mainten...

Страница 14: ...se al Cables de m s de 3 m en la entrada DI deben evitarse Conexiones DO DO1 DO2 DO3 DO4 DO5 DO6 DO7 DO8 1 8 I Max 10 A 3 5 10 A 3 5 6 A 4 6 A 4 0 5 A min 50 mA Ioff 1 5 mA 0 5 A min 50 mA Ioff 1 5 mA...

Страница 15: ...independiente Evite la corriente de fallo a tierra Utilice un transformador con aislamiento doble El lado secun dario no debe conectarse a tierra Obtenga 0 10 V de los terminales Com AO1 N AO3 y N AO4...

Страница 16: ...limentaci n 3 Compruebe que el interruptor principal est en la posici n de desconexi n 4 M dulo HP monte el terminal con alimentaci n el ctrica 5 Espere cinco segundos 6 M dulo receptor monte el termi...

Отзывы: