Part NO: 212-0024-8S   

                   12                                        September 24th, 

 

Timed Modes of Operation 

 

Battery Voltage:  

 

A) 

Between 14.0 to 18V 

the output of the “PDU Timer”  will be 

ON unconditionally

B) If the battery voltage drops 

below 14.0V 

and the 

ignition is OFF

, the “PDU Timer”  will 

commence a predetermined countdown delay at the end of which the unit will shut-off and 

go into “STANDBY” mode. This delay is set by the 4 DIP switches on the “PDU Timer” , 

THE FACTORY DEFAULT IS TYPICALLY SET TO 2 hours (DIP switch 3 =OFF all 

others on). Check and set this accordingly.

 

C) If the battery voltage recovers and is raised above 14.0V (i.e.. the battery is being charged) 

the countdown process will cease and the “PDU Timer” will go into “ON” mode 

 

Ignition: 

A) If the ignition switch is OFF and the unit is in countdown mode, cycling the ignition switch 

ON/OFF will reset the countdown. Always at the end of the countdown the “PDU Timer”  

will be in “STANDBY” mode. 

B) The ignition switch “ON” will always reset the countdown and prevent it from timing down 

(override countdown mode and keep the “PDU Timer”  ON). 

 

Override: 

The override circuit can be triggered by the PB (push button) momentary on switch on the 

“PDU Timer” . Triggering the override will send the unit into “ON” mode for “2” minutes re-

gardless of the operating mode, or battery voltage (providing battery is not completely dead 

and the ignition is off). 

 

Standby: 

Once the “PDU Timer”  is in STANDBY mode, the only way for the system to come out of 

STANDBY is; 

A) Override Switch is pressed 

B) Battery is charging and the battery voltage is over 14V. 

C) Ignition switch is switched ON. 

 

LED Indicator: 

The LED indicator shows the mode or status by the following indications; 

A) 

STANDBY 

– LED blinking at the rate of  

10% ON 90% OFF

B) 

ON

 -  LED 

ON solid

 

C) 

COUNTDOWN

 - LED blinking at the rate of 

90% ON 10% OFF

 

 

 

LED Fuse Indicators 

Each fuse has an LED indicator, the LED will be lit if the fuse is good and there is a DC volt-

age present on the appropriate terminal. To save power and prevent unnecessary drain of the 

battery these LED indicators will only be lit if the ignition input is present at the 

PDU

. The on-

ly exception are the LED indicators on the Timed outputs, these will indicate “ON” if the timer 

is active and the fuse is good. 

Содержание PDU-8S

Страница 1: ... Table of Contents Applicable Models 2 Introduction 2 General Warnings 3 Unpacking Pre Installation Check 3 Installation Mounting 4 Wiring and Setup Instructions 4 Output Fuse Combinations 6 Timed Modes Of Operation 12 Maintenance 13 Parts List 13 Troubleshooting 14 Product Specifications 15 Warranty 16 ...

Страница 2: ... requirements These output features have the following characteristics 1 Constant Battery Outputs There are 8 output connections each with individual fuses that are on at all time providing the PDU is connected to the battery 2 Ignition Controlled Outputs The 8 output power connections also individually fused provide 12V output while the vehicle ignition is ON Power will be immediately turned OFF ...

Страница 3: ...utput performance of vehicle sys tems 6 Placement of control switches must be so as to provide convenient reach for the opera tor without loosing eye contact with the road 7 Emergency warning devices require high electrical voltages and or currents Properly connect and ground all circuits Shorting or improper grounding of this device may caused personal injuring vehicle damage or both 8 All operat...

Страница 4: ...celeration or turns 2 Be sure to mount unit through the steel of the vehicle Avoid mounting through plastic or other non structural materials 3 POINT OF INSTALLATION MUST NOT INTERFERE WITH DEPLOYMENT OF VEHICLE AIR BAGS 4 D R Electronics recommends this and any of our other products be installed by quali fied professionals Warning Mounting the PDU unit The PDU 8S may be mounted anywhere inside th...

Страница 5: ...ions The maximum fuse sizes and some possible combinations are shown in a table on the following page Figure 2 The fuses are indicated as 20A maximum the x is no fuse or no connection and the N A means that the limit of that area has been reached with the indicated max imum fuse values and that spot is not available Many combinations can be de rived based on the PDU specifications and the equipmen...

Страница 6: ...20A 20A 2 x x 20A 20A 20A 3 x x x 20A 20A 4 x x x x 20A 5 x x x x N A 6 x x x x N A 7 x x x x N A 8 x x x x N A 12V BATTERY 1 20A 20A 20A 20A 15A 2 20A 20A 20A 20A 15A 3 20A 20A 20A 20A 15A 4 20A 20A x 15A 15A 5 N A N A x 10A 15A 6 N A N A x N A 15A 7 N A N A x N A N A 8 N A N A x N A N A AND IGNITION 1 20A 20A 20A 20A 20A 2 20A 20A 20A 20A 20A 3 20A 20A 20A x 15A 4 20A 20A x x 15A 5 N A x x x 15A...

Страница 7: ...a fusible link or circuit breaker rated at 80A to the PDU 8S 2 Cut the wire to length and strip 1 2 length of insulation from the end of the wire insert the bare wire into a suitable ring terminal these are not provided the ring hole must clear a 1 4 bolt crimp or solder 3 Connect as shown in Figure 3 Connecting ground input to the PDU 1 Run a 6 AWG wire lead to the chassis of the vehicle if neces...

Страница 8: ...d be fused and located as close as possible to the POSITIVE battery terminal We recommend a 1A fuse inside an inline weather resistant fuse holder be used Connecting high Current AMP power outputs from the PDU The PDU supplies two high current 12V OUT outputs which may be used to power high current devices such as a lightbar or siren and light control system this output uses the same style of powe...

Страница 9: ...l to the PDU To activate the ignition control and timed outputs feature the PDU must receive a control sig nal from the vehicle 1 The installer must locate the ignition output from the vehicles wiring harness and run an 18 AWG wire from this point to the ignition input IGN IN on the PDU Care must be taken to connect the correct ignition control wire from the vehicle wiring har ness some of the new...

Страница 10: ...tions to and from the PDU are completed the output fuses can be installed according to the required rating of the connected equipment The PDU accepts a standard Automotive Blade ATO ATC Type fuses each fuse location has an LED indicator to show that the fuse is in place and working The LED indicator will glow RED if the fuse is GOOD otherwise it will be off Setting The Time Delay on Timed Outputs ...

Страница 11: ... will select the time increments to the output off time delay Table 1 Time Delay Switch Settings Factory Default 2 Hours TIME SW 1 SW 2 SW 3 SW 4 2 MIN ON ON ON ON 10 MIN OFF ON ON ON 30 MIN ON OFF ON ON 1 HR OFF OFF ON ON 2 HR ON ON OFF ON 3 HR OFF ON OFF ON 4 HR ON OFF OFF ON 5 HR OFF OFF OFF ON 6 HR ON ON ON OFF 7 HR OFF ON ON OFF 8 HR ON OFF ON OFF 9 HR OFF OFF ON OFF 10 HR ON ON OFF OFF 11 HR...

Страница 12: ... countdown mode and keep the PDU Timer ON Override The override circuit can be triggered by the PB push button momentary on switch on the PDU Timer Triggering the override will send the unit into ON mode for 2 minutes re gardless of the operating mode or battery voltage providing battery is not completely dead and the ignition is off Standby Once the PDU Timer is in STANDBY mode the only way for t...

Страница 13: ...Part NO 212 0024 8S 13 September 24th Maintenance The PDU 8S does not require user maintenance except for the individual fuse replacement ...

Страница 14: ...DU ignition ter minal Incorrect connection to vehicle wiring harness Faulty Unit Verify ignition input connection Consult the factory specifications and wiring diagrams for the vehicle Verify that the ignition wire re ceives 12V when vehicle ignition is set to ON and vehicle is run ning Return unit for repair Timed outputs not on while ignition is ON Timing cycle incorrect Timing cycle does not en...

Страница 15: ...er the total current not to exceed 60A 8 Continuous Power the total current not to exceed 60A 8 Timed Power the total current not to exceed 60A 8 Ground return path for the Output terminal blocks the total return current not exceed 60A 7 NOTE All combined output power using any combination of outputs not to exceed 60A Timed Outputs With Voltage Protection Specification Operating Voltage monitored ...

Страница 16: ...es for removal or installation Lamps flash tubes batteries or other items considered consumables are not covered under warranty This warranty is in lieu of all other express warranties D R Electronics makes no warranties ex pressed or implied other than the express warranties contained herein WARRANTY PRODUCT RETURN POLICY In order to provide you with faster service product returns for repair or r...

Отзывы: