Important Safety Information

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

Decommissioning

Before carrying out this procedure, it is essential 

that the technician is completely familiar with the 

equipment in all its detail. It is recommended good 

practice that all refrigerants are recovered safely. 

Prior to the task being carried out, an oil and 

refrigerant sample shall be taken in case analysis is 

required prior to re-use of reclaimed refrigerant. It 

is essential that electrical power is available before 

the task is commenced.

A.  Become familiar with the equipment and its 

operation.

B.  Isolate system electrically.

C.  Before attempting the procedure ensure that:

•  Mechanical handling equipment is available 

if required for handling refrigerant cylinders.

•  All personal protective equipment is 

available and being used correctly.

•  The recovery process is supervised at all 

times by a competent person.

•  Recovery equipment and cylinders conform 

to the appropriate standards.

D.  Pump down refrigerant system, if possible.

E.  If a vacuum is not possible, make a manifold so 

that refrigerant can be removed from various 

parts of the system.

F.  Make sure that cylinder is situated on the scales 

before recovery takes place.

G.  Start the recovery machine and operate in 

accordance with the manufacturer’s instructions.

H.  Do not overfi ll cylinders. No more than 80% 

volume liquid charge.

I.  Do not exceed the maximum working pressure 

of the cylinder, even temporarily.

J.  When the cylinders have been fi lled correctly 

and the process is completed, make sure that the 

cylinders and the equipment are removed from 

the site promptly and all isolation valves on the 

equipment are closed off.

K.  Recovered refrigerant shall not be charged into 

another refrigeration system unless it has been 

cleaned and checked.

Labeling

Equipment shall be labeled stating that it has been 

decommissioned and emptied of refrigerant. The 

label shall be dated and signed. Ensure that there 

are labels on the equipment stating the equipment 

contains fl ammable refrigerant.

Recovery

When removing refrigerant from a system, either for 

servicing or decommissioning, it is recommended 

good practice that all refrigerants are removed 

safely.

When transferring refrigerant into cylinders, ensure 

that only appropriate refrigerant recovers cylinders 

are employed. Ensure that the correct number of 

cylinders for holding the total system charge are 

available. All cylinders to be used are designed 

for the recovered refrigerant and labeled for that 

refrigerant, i.e. special cylinders for the recovery 

of refrigerant. Cylinders shall be complete with 

pressure relief valve and associated shut-off valves 

in good working order. Empty recovery cylinders 

are evacuated and, if possible, cooled before 

recovery occurs.

The recovery equipment shall be in good working 

order with a set of instructions concerning the 

equipment that is at hand and shall be suitable for 

the recovery of fl ammable refrigerants. In addition, 

a set of calibrated weighing scales shall be 

available and in good working order. Hoses shall 

be complete with leak-free disconnect couplings 

and in good condition. Before using the recovery 

machine, check that is it in satisfactory working 

order, has been properly maintained and that any 

associated electrical components are sealed to 

prevent ignition in the event of a refrigerant leak. 

Consult the manufacturer if in doubt.

The recovered refrigerant shall be returned to the 

refrigerant supplier in the correct recovery cylinder 

and the relevant waste transfer note shall be 

arranged. Do not mix refrigerants in recovery units 

and especially not in cylinders. If compressors or 

compressor oils are to be removed, ensure that they 

have been evacuated to an acceptable level to make 

certain that fl ammable refrigerant does not remain 

within the lubricant. The evacuation process shall be 

carried out prior to returning the compressor to the 

suppliers. Only electric heating to the compressor 

body shall be employed to accelerate this process. 

When oil is drained form a system, it shall be 

carried out safely.

5

Содержание DPA050E2WDB-RF

Страница 1: ...nada ou aux tats Unis Impreso en Canad o EE UU Trademark of Danby Products Marque de commerce de Danby Products Marca registrada de Danby Products www Danby com Printed in Canada or USA PORTABLE AIR C...

Страница 2: ...bove the power cord contains electrical and other technical data This appliance is not intended for use by persons including children whose physical sensory or mental capabilities may be different or...

Страница 3: ...ant detector prior to and during work to ensure the technician is aware of potentially ammable atmospheres Ensure that the leak detection equipment being used is suitable for use with ammable refriger...

Страница 4: ...recovering or purging the system That there is continuity of earth bonding Repairs to sealed components 1 During repairs to sealed components all electrical supplies shall be disconnected from the equ...

Страница 5: ...d Extreme care shall be taken not to over ll the refrigeration system Prior to recharging the system it shall be pressure tested with OFN The system shall be leak tested on completion of charging but...

Страница 6: ...hat there are labels on the equipment stating the equipment contains ammable refrigerant Recovery When removing refrigerant from a system either for servicing or decommissioning it is recommended good...

Страница 7: ...either end of the exhaust hose 2 Insert the air outlet adapter into the back of the appliance by placing over the air exhaust and then pushing in the direction of the arrow to lock into place 3 Measur...

Страница 8: ...ing window are the same 1 Cut the adhesive foam seals A and B to the correct length for the window Attach them to the window sash and frame as shown 2 Insert the assembled window slider kit into the w...

Страница 9: ...n The appliance must be installed near a grounded receptacle and the over ow drain outlet on the rear of the appliance must be accessible Do not cover air inlets or outlets or the remote control recei...

Страница 10: ...mode button to choose cool mode Use the temperature control buttons to choose the desired temperature Use the fan button to choose the desired fan speed The temperature can be set within a range of 1...

Страница 11: ...lluminate Notes Turning the appliance on or off at any time or adjusting the timer setting to 0 hours will cancel the timer settings CHILD LOCK The child lock can be activated by pressing the temperat...

Страница 12: ...del 7 Sleep button Used to set the sleep function 8 Fan button Used to set the fan speed 9 C F button Used to change the temperature scale between Celsius and Fahrenheit Note The remote control will f...

Страница 13: ...approved by the party responsible for FCC compliance could void the user s authority to operate the equipment This appliance complies with Part 15 of the FCC Rules Operation is subject to the followi...

Страница 14: ...may continue to operate Drain Plug 1 Turn the appliance off and unplug it from the power source 2 Carefully move the appliance to a location where the water can be drained 3 Remove the drain plug and...

Страница 15: ...liance and unplug it wrap the cord and bundle it with tape 4 Remove the battery from the remote control 5 Clean the air lters and reinstall them 6 Store the appliance in a cool dark place Prolonged ex...

Страница 16: ...mode or if using the continuous drain Where do I drain water from The water drains from the drainage port If you are not using the continuous drain the internal pan drains from the bottom outlet Odors...

Страница 17: ...small for application Noise The ground is not level The air lter is dirty or blocked Gurgling sounds are normal this is coolant moving inside the appliance Odors Formation of mold or mildew on intern...

Страница 18: ...A 45840 Telephone 419 425 8627 FAX 419 425 8629 04 13 1 800 263 2629 Warranty Service Carry In C ERTIFIE D C E R T I F I E D This quality product is warranted to be free from manufacturer s defects i...

Страница 19: ...plosion Fluide frigorig ne in ammable utilis Ne pas endommager le circuit de r frig rant Assurez vous que les r parations sont effectu es par du personnel autoris par l usine a n de minimiser les domm...

Страница 20: ...que le technicien est conscient des atmosph res potentiellement in ammables Assurez vous que l quipement de d tection des fuites utilis convient aux uides frigorig nes in ammables c est dire qu il ne...

Страница 21: ...mise la terre R paration de composants scell s 1 Lors de la r paration de composants scell s toutes les alimentations lectriques doivent tre d branch es de l quipement utilis avant toute d pose de co...

Страница 22: ...r me doit tre pris pour ne pas trop remplir le syst me de r frig ration Avant de recharger le syst me il doit tre test sous pression avec OFN Le syst me doit tre soumis un test d tanch it la n du char...

Страница 23: ...sur l quipement indiquant que celui ci contient du r frig rant in ammable R cup ration Lorsque vous retirez du uide frigorig ne d un syst me que ce soit pour un entretien ou une mise hors service il e...

Страница 24: ...n tre l une des extr mit s du tuyau d chappement 2 Ins rez l adaptateur de sortie d air l arri re de l appareil en le pla ant sur l chappement d air puis en poussant dans le sens de la che pour le ver...

Страница 25: ...te sont les m mes 1 Couper les joints de mousse adh sive A et B la longueur correcte pour la fen tre Fixez les sur le cadre de la fen tre et l image comme indiqu 2 Ins rez le kit de curseur de fen tre...

Страница 26: ...re de l appareil doit tre accessible Ne pas couvrir les entr es d air ou les prises de courant ou le r cepteur de la t l commande sur le panneau de commande L appareil n cessite un d gagement de 45 cm...

Страница 27: ...les boutons de contr le de la temp rature pour choisir la temp rature d sir e Utilisez le bouton du ventilateur pour choisir la vitesse du ventilateur souhait e La temp rature peut tre r gl e dans un...

Страница 28: ...mera Remarques Allumer ou teindre l appareil tout moment ou r gler le minuteur sur 0 heure annulera les r glages VERROUILLAGE ENFANT Le verrouillage d enfants peut tre activ e en appuyant simultan men...

Страница 29: ...ce mod le 7 Bouton de sommeil utilis pour r gler la fonction de sommeil 8 Bouton de ventilateur utilis pour r gler la vitesse du ventilateur 9 Bouton C F utilis pour changer l chelle de temp rature e...

Страница 30: ...l appareil aux r glements de la FCC pourraient faire retirer l autorisation d utilisation de l appareil Cet appareil est conforme la Section 15 des r glementations de la FCC Son utilisation est soumi...

Страница 31: ...z l appareil hors tension et d branchez le de la source d alimentation 2 D placez soigneusement l appareil un endroit o l eau peut tre vidang e 3 Retirez le bouchon de vidange et laissez l eau s coule...

Страница 32: ...sissure 3 teignez l appareil et d branchez le enroulez le cordon et collez le avec du ruban adh sif 4 Retirez les piles de la t l commande 5 Nettoyez les ltres air et r installez les 6 Conserver l app...

Страница 33: ...si vous utilisez la vidange continue D o dois je vidanger l eau L eau s coule du port de drainage Si vous n utilisez pas le drain continu le bac interne s coule de la sortie inf rieure Les odeurs L od...

Страница 34: ...it Le sol n est pas de niveau Le ltre air est sale ou obstru Les bruits de gargouillis sont normaux il s agit du liquide de refroidissement circulant l int rieur de l appareil Odeurs Formation de mois...

Страница 35: ...D Cet appareil de qualit est garantie exempt de tout vice de mati re premi re et de fabrication s il est utilis dans les conditions normales recommand es par le fabricant Cette garantie n est offerte...

Страница 36: ...STRUCCIONES DE SEGURIDAD REQUERIMIENTOS DE SEGURIDAD PELIGRO Riesgo de incendio o explosi n Refrigerante in amable utilizado No da e el circuito de refrigerante Aseg rese de que el servicio sea realiz...

Страница 37: ...nte el trabajo para garantizar que el t cnico tenga conocimiento de las atm sferas potencialmente in amables Aseg rese de que el equipo de detecci n de fugas que se est utilizando sea adecuado para el...

Страница 38: ...ientras se est cargando recuperando o purgando el sistema Que hay continuidad de la uni n de la tierra Reparaciones a componentes sellados 1 Durante las reparaciones de componentes sellados todos los...

Страница 39: ...ener mucho cuidado de no sobrecargar el sistema de refrigeraci n Antes de recargar el sistema se someter a prueba de presi n con OFN El sistema debe ser probado contra fugas al nalizar la carga pero a...

Страница 40: ...o que indiquen que el equipo contiene refrigerante in amable Recuperaci n Cuando se retira refrigerante de un sistema ya sea para servicio o cierre se recomienda que todos los refrigerantes se elimine...

Страница 41: ...emo de la manguera de escape 2 Inserte el adaptador de salida de aire en la parte posterior del aparato coloc ndolo sobre el escape de aire y luego empujando en la direcci n de la echa para bloquearlo...

Страница 42: ...ismos 1 Corte los sellos de espuma adhesiva A y B a la longitud correcta para la ventana Adj ntelos a la hoja y marco de la ventana como se muestra 2 Inserte el kit deslizante de la ventana ensamblada...

Страница 43: ...ida de drenaje de desbordamiento en la parte posterior del electrodom stico No cubra las entradas o salidas de aire ni el receptor de control remoto en el panel de control El aparato requiere 45 cm 17...

Страница 44: ...Use los botones de control de temperatura para elegir la temperatura deseada Use el bot n del ventilador para elegir la velocidad deseada del ventilador La temperatura se puede ajustar dentro de un ra...

Страница 45: ...r Notas Al encender o apagar el aparato en cualquier momento o ajustar la con guraci n del temporizador a 0 horas se cancelar la con guraci n del temporizador BLOQUEO INFANTIL El bloqueo para ni os se...

Страница 46: ...o est disponible en este modelo 7 Bot n de sue o se utiliza para con gurar la funci n de sue o 8 Bot n de ventilador se utiliza para con gurar la velocidad del ventilador 9 Bot n C F se utiliza para c...

Страница 47: ...funcionamiento est sujeto a las siguientes condiciones 1 Este dispositivo no puede causar interferencias perjudiciales 2 Este dispositivo debe aceptar cualquier interferencia recibida incluida la int...

Страница 48: ...ntinuar funcionando Tap n de drenaje 1 Apague el aparato y desench felo de la fuente de alimentaci n 2 Mueva con cuidado el aparato a un lugar donde pueda drenarse el agua 3 Retire el tap n de drenaje...

Страница 49: ...to har una pausa en el funcionamiento si se forma hielo en la estructura interna El aparato reanudar su funcionamiento normal autom ticamente cuando el hielo se derrita PF falla del sensor desenchufe...

Страница 50: ...o calor modo seco o si usa el drenaje continuo De d nde dreno el agua El agua sale del puerto de drenaje Si no est utilizando el drenaje continuo la bandeja interna se drena desde la salida inferior O...

Страница 51: ...e o para la aplicaci n Ruido El suelo no est nivelado El ltro de aire est sucio o bloqueado Los sonidos de gorgoteo son normales se trata de refrigerante que se mueve dentro del aparato Olores Formaci...

Страница 52: ...bra siempre y cuando la unidad se utilice bajo las condiciones normales de funcionamiento para las que fue dise ado Esta garant a est solamente disponible para la persona que haya comprado originalmen...

Отзывы: