DALGAKIRAN L-8 Скачать руководство пользователя страница 8

 

7

 

 

PARAMETERS 

 

 

 

 

 

 

 

 

 

 

 

 

  

CODE 

 DESCRIPTION 

     SET 

VALUE 

  

 PRESSURE 

CONTROL 

    0 

* ( 0 = TRANSDUCER, 1 = PRESURE 

SWITCH 

    

 

TOP RANGE PRESSURE TRANSDUCER 

 

15 Bar   

 

 

HIGH PRESSURE ALARM 

 

 

 

8,8 – 11 – 14,3 Bar

 

 STOP 

PRESSURE 

    

7,5 – 10 – 13 Bar 

 

 START 

PRESSURE 

    

6,5 – 9 – 12 Bar

 

 

OFFSET PRESSURE TRANSDUCER   

 

 MAX. 

TEMPERATURE 

SET 

   110 

°

C  

 

HIGH TEMPERATURE ALARM SET 

 

 

105 

°

C  

 

 

FOREWARNING HIGH TEMPERATURE SET   

100 

°

C  

 

 LOW 

TEMPERATURE 

SET 

   0 

°

C  

 

  

TEMPERATURE SENSOR OFFSET 

 

 

°

   

 

STAR TIMER   

 

 

 

 

5 sec.   

 

 

STAR/DELTA SWITCHING TIMER 

 

 

50 msec. 

 

 

 LOAD 

DELAY 

TIMER 

    2 

sec. 

  

 UNLOAD 

STOP 

TIMER 

    2 

min. 

 

 

UNLOAD STOP TIMER VARIABLE 

 

 

0

 

 

 

STOP TIMER   

 

 

 

 

30 sec.

 

 

AIR FILTER CHANGE TIME 

 

 

 

2000 Hours

 

 

OIL 

FILTER 

CHANGE 

TIME 

   2000 

Hours

 

 

 

SEPARATOR 

CHANGE 

TIME 

   4000 

Hours

 

 

 

OIL 

CHANGE 

TIME 

    2000 

Hours

 

 

CHECK 

KOMPRESOR 

    2000 

Hours

 

 

STARTS/ HOURS ALLOWED TO THE MOTOR 

 

 

LOW 

VOLTAGE 

ALARM    1 

 

RL5 SET 

 

 

 

 

 

 

FAN ON (RL5)   

 

 

 

 

85 

°

C  

 

DELTA T FAN OFF (RL5) 

 

 

 

10 

°

 

 

 

ATTENTION : P18- P22 COUNTDOWN IDENTIFY THE MOTOR RUNNING TIME, WHEN THE COUNTDOWN IS ELAPSED THE TIMER 

WILL GO ON AS NEGATIVE COUNTING. 

 

 

 

 

 

Содержание L-8

Страница 1: ...HAVA KOMPRES RLER ROTARY SCREW AIR COMPRESSORS KONTROL N TES KULLANICI EL K TABI CONTROLLER UNIT USER MANUAL L 8 GELECEK BA VURULAR N SAKLAYINIZ KEEP FOR FUTURE REFERENCE MANUEL NO KU L8 D REV 00 01...

Страница 2: ...EKRANDA MESAJI YANIP S NER KOMPRES R P15 BO TA BEKLEME ZAMANI S RES KADAR BO TA ALI MAYA DEVAM EDER S RE SONUNDA MESAJ SAB T HALE GEL R VE KOMPRES R DURUR KOMPRES R DURANA KADAR BASIN D ER VE KOMPRES...

Страница 3: ...UNA KISA S REL BASARAK SERV S S RELER N G REB L RS N Z 1 CALI MA BASINCI 2 ALI MA SICAKLI I 3 HAVA F LTRES DE M N KALAN ZAMAN 4 YA F LTRES DE M N KALAN ZAMAN 5 SEPARAT R DE M N KALAN ZAMAN 6 YA DE M...

Страница 4: ...Z ALI MA S RES 5 sn YILDIZ GEN ARA ZAMANI 50 msn Y KE GE ME GEC KME ZAMANI 2 sn BO TA BEKLEME ZAMANI 2 dak DE KEN BO TA BEKLEME ZAMAIN 0 STOPTA DURMA ZAMANI 30 sn HAVA F LTRE DE M ZAMANI 2000 saat YA...

Страница 5: ...HA SO UK DU UK ENERJ KAYNA I KOMPRESOR 1 SAAT YUK BO OLARAK DURMADAN ALI ACAK BIR SAAT ER S NDE SET DE ER NE ULA ILDI YUKSEK BASIN S V C A ILDI P03 BASIN DE ER A ILDI BASIN TRASMITTERI BASIN ALTER BA...

Страница 6: ...OP TIMER P15 IF THE PRESSURE SWITCH IS STILL OPEN AT THE END OFTHE COUNTDOWN MESSAGE COMES TO BE FIXED IF THE PRESSURE SWITCH CLOSES DURING THE COUNTDOWN THE UNLOAD STOP TIMER P15 RESET 3 BY PUSHING T...

Страница 7: ...SSURE 2 WORKING TEMPERATURE 3 HOURS TO THE NEXT AIR FILTER CHANGE 4 HOURS TO THE NEXT OIL FILTER CHANGE 5 HOURS TO THE NEXT SEPARATOR CHANGE 6 HOURS TO THE NEXT OIL CHANGE 7 CHECK KOMPRESSOR 8 RUNNING...

Страница 8: ...TEMPERATURE SENSOR OFFSET 0 C STAR TIMER 5 sec STAR DELTA SWITCHING TIMER 50 msec LOAD DELAY TIMER 2 sec UNLOAD STOP TIMER 2 min UNLOAD STOP TIMER VARIABLE 0 STOP TIMER 30 sec AIR FILTER CHANGE TIME 2...

Страница 9: ...RATURE SENSOR IS DEFECTIVE LOW TEMPERATURE TEMPERATURE LOWER THAN LOW POWER SUPPLY THE COMPRESSOR WILL NEVER STOP 1 HOUR FROM THE FRIST START IT WILL RUN LOAD UPLOAD ACCORDING THE PRESSURE WITHIN A 1...

Страница 10: ...9 L8 10 10 100 100 1 2 3 30 30...

Страница 11: ...10 1 1 2 3 4 5 6 7 8 10 100 10 100 3 1 2 3 4...

Страница 12: ...11 0 15 Bar 8 8 11 14 3 Bar 7 5 10 13 Bar 6 5 9 12 Bar 0 110 C 105 C 100 C 0 C 0 C 5 50 2 2 0 30 2000 2000 4000 2000 2000 6 1 0 1 3 6 0 1 0 85 C 10 C...

Страница 13: ...12 Pr 02 103 C Pr 03 100 C Pr 03 2 C...

Страница 14: ...0V AC F2 220V AC F1 12V AC 0V AC 3 2 1 4 K1 Y1 F3 6 6 4 2 1 1 2 5 4 1 F4 6 5 0 0 S1 TR 380V AC 5 2 1 4 3 7 PE X1 X1 X2 1 16 13 RC 14 15 5 7 X1 M3 M1 PH L O G I K 8 10 6 0 5 6 6 7 8 1 4 X1 220 V AC 12...

Страница 15: ...12V AC 0V AC 3 2 1 4 K1 Y1 K2 K3 K2 K3 F3 6 6 2 12 4 2 1 1 2 5 3 12 4 1 F4 6 5 0 0 0 S1 TR 380V AC 5 2 1 4 3 7 0 3 11 4 11 PE X1 X1 X2 1 3 2 16 13 RC 14 15 5 7 X1 M3 M1 PH L O G I K 8 10 6 0 5 6 6 7 8...

Страница 16: ...AC 1 6A F1 12V AC 0V AC 4 3 2 1 5 TMP 2 2 F5 K1 Y1 K2 K3 K2 K3 F3 1 6A 2 3 3 2 1 4 3 6 5 4 1 F4 2 5A S1 TR 380V AC 6 4 3 2 1 3 PE X1 2 X1 X2 9 12V AC 220V AC RC 1 M2 M3 L O G I K A 8 S2 _ K4 F6 M2 3...

Страница 17: ...ANA MOTOR TERM OVERLOAD RELAY MAIN MOTOR F6 FAN MOTOR TERM FAN MOTOR OVERLOAD RELAY M1 ANA MOTOR MAIN MOTOR M2 FAN MOTORU FAN MOTOR PH FAZ KONTROL ROLES PHASES CONTROLLER UNIT F1 F2 TR G R S GORTASI...

Отзывы: