6 - CLEANING
6.0 General information
The firebox and the flues must be periodically cleaned from the combustion solid residues
(ashes).
Keeping the flues free from ashes ensure the draught efficacy and then the best efficiency of
the
heat .
6.1 Operation mode and periodicity
Firebox: The check and the cleaning of the amount of combustion residues in the
firebox [3] must be carried out every day by opening the door [6]. The
combustion residues in the low part [4] must be cleaned by opening the door
[5].
Tube nest: The check and the cleaning of the amount of combustion residues in the tube
nest [8] must be carried out about every 4-5 days, by opening the door[7] and
using the proper brush supplied with the machine.
Fume pipe fittings: The check and the cleaning of the amount of combustion residues in the
fume pipe fitting [16] must be carried out every 15 days by means of the ash removal little
door [15]. Check and clean the flue periodically.
6.2 Cleaning of the fuel hopper
The fuel hopper is equipped of a hinged lid. The cleaning of the fuel hopper [16] must be
carried out only after stopping the machine, removing the hopper from the flange that
connect it
to the screw.
BEFORE OPENING THE MACHINE MAKE SURE THE FUEL CONTAINED IN THE
FIREBOX IS COMPLETELY EXTINGUISHED
7 - MAINTENANCE
7.0 General information
The heat generator must be subjected to regular maintenance. The maintenance must be carried
out by specialised staff.
7.1 Periodical maintenance
At the beginning of every season clean the fan blades (The accumulation of dust and other material
on the fan blades decreases the efficiency and compromises the balancing, causing vibrations and
noises)