Technical Notes
Installation:
•
Installation and maintenance must only be carried out by qualified personnel in accordance with the regulations in force.
•
The product must be installed inside a surge-protected electrical cabinet.
•
The product must be installed in a vertical or horizontal position with the front cover/label upwards or vertically; no other position is
permitted; a bottom-up position (with the front cover/label downwards) is not permitted.
•
Keep 230V (LV) and non-SELV circuits separate from safety extra-low voltage (SELV) circuits and all connections of this product. It
is absolutely forbidden to connect, for any reason, directly or indirectly, the 230V mains voltage to the bus or other parts of the circuit.
Power supply:
•
Use only SELV-type power supplies with limited current and short-circuit protection and appropriately sized power for the power
supply. In the case of power supply units equipped with earth terminals, it is mandatory to connect ALL protection earth points (PE =
Protection Earth) to a professionally installed and certified earth installation.
•
The connecting cables between the extra-low voltage power source and the product must be correctly sized and must be isolated
from any wiring or non-SELV voltage parts. Use double-insulated wires.
Commands:
•
The length of the connecting cables between the local controls (Push Button, 0-10V, 1-10V, Potentiometer, or other) and the product
must be less than 10m; the cables must be correctly sized and must be isolated from any wiring or non-SELV voltage parts. Use
double-insulated shielded and twisted cables.
•
The length and type of connection cables to the buses (DMX512, Modbus, DALI, Ethernet or other) must comply with the specifications
of the respective protocols and current standards; they must be isolated from any wiring or non-SELV voltage parts. Use double-
insulated shielded and twisted cables.
•
All devices and control signals connected to buses (DMX512, Modbus, DALI, Ethernet or other) and local controls (Push Button, 0-
10V, 1-10V, Potentiometer, or other) must be SELV (connected devices must be SELV or in any case provide a SELV signal).
In addition
•
The device routes the DALI devices
•
It supports DALI DT4, DT6 and DT8 protocols
•
The Gateway feeds the communication bus and cannot coexist with other controllers
•
The gateway can only receive commands via IP (Control4) and re-route them to the available 512 channels, regardless of the bus
type