After mounting

ATTENTION! 

In case of medium pressure fans, close the throttling device (guiding device, damper, valve, etc.); switch 

on the engine, measure the current by the phases of the electric engine. Open the throttling device by observing the 
current rise. In all design positions of the throttling device (or other control device), the current must not exceed the 
nominal value indicated on the electric engine nameplate or in the data sheet. If at any position of the throttling device 
the current becomes higher than the rated current, this indicates that the fan does not match the ventilation system (or 
that the engine power is insufficient). To limit the operating current, it is necessary to fix the position of the throttling 
device at the rated current. Further, when the fan is operated, no regulation should reduce the mains resistance 
against the set fixed position of the throttle.

Ensure that the product is connected correctly and that the ground connections are properly mounted.

Ensure that the electrical terminal box is correctly assembled and it is water tight.

Ensure the impeller rotates in the right direction.

The air outlet direction should be in accordance with the direction indicated on the label.

Ensure there are no obstructions in the airflow path.

During operation of the product, there should be no vibration, internal friction, or shock sounds when the fan is 
rotating or air is being drawn in.

Check fan operation within one hour, if there are no unusual knocks, noise, increased vibration or other defects, the 
fan will run normal operation.

If you have other problems, please consult with a specialist. 

MAINTENANCE

 Periodic maintenance should be carried out at least once every six months or more often, depending on the frequency 
of its use. If these requirements are not followed, the product life time can be significantly reduced or serious damage to 
the product can occur.

Fan maintenance and cleaning should be performed by a qualified technician. 

Disconnect the fan from the mains.

Remove the fan by disconnecting it from the air ducts and air distributors and removing it from the installation site.

Remove dust from the fan net using a soft, dry brush or cloth.

Reassemble the fan and reinstall.

ATTENTION! In no case, the product must not be exposed to water.  When cleaning the product, do not use flammable 
or combustible cleaners.

ATTENTION!

 

 Inspect the product regularly: replace damaged or worn cables, bolts, or other parts.

POSSIBLE PROBLEMS AND SOLUTIONS

When connected to the power 
grid, the fan does not rotate, 
does not respond to controls.

Low air flow.

Increased noise or vibration.

The mains supply is not connected.

Internal connection fault.

The ventilation system is clogged.

The fan is not fixed or is incorrectly 
mounted.

The ventilation system is clogged.

It is necessary to address a specialist.

Clean the ventilation system.

Correct the installation error.

Clean the ventilation system.

Malfunction

Probable cause

Remedy

Содержание SKT PROFI

Страница 1: ...SKT PROFI SKT HEAVY...

Страница 2: ...install fan in the same air vent line together with smoke emission pipe of the fuel burner device All installation and connection of fans should only be carried out when the mains voltage is o and the...

Страница 3: ...02 117 40 367 120 362 205 90 90 165 148 110 12 60 178 180 233 125 175 117 20 275 120 315 161 140 140 161 113 113 8 00 178 180 233 125 175 117 20 275 120 315 161 140 140 161 113 113 7 90 178 180 233 12...

Страница 4: ...100 1100 2800 2800 1400 1400 2800 2800 1400 1400 2800 2800 1400 1400 50 52 43 45 53 53 45 46 53 55 50 46 50 220 380 220 380 220 380 220 380 220 380 220 380 2 60 3 00 2 00 1 20 2 60 3 00 2 00 1 20 5 20...

Страница 5: ...n the fan grill During installation use gloves to protect against sharp edges of the product and equipment Connection to the mains Make sure that the mains parameters frequency power and current corre...

Страница 6: ...the fan is rotating or air is being drawn in Check fan operation within one hour if there are no unusual knocks noise increased vibration or other defects the fan will run normal operation If you have...

Страница 7: ...s not exclude limit nor suspend the powers of a buyer Exclusions The guarantee does not cover defects arising as a result of mechanical forces dirt transformations constructional changes activities co...

Страница 8: ...z v prost ed s teplotami v rozmez 25 C a 60 C Je zak z no ventil tor instalovat do potrubn ch syst m slou c ch k odvodu spalin Instalace zapojen a dr ba ventil toru se sm prov d t pouze p i odpojen z...

Страница 9: ...12 208 340 200 202 117 40 367 120 362 205 90 90 165 148 110 13 95 212 208 340 200 202 117 40 367 120 362 205 90 90 165 148 110 12 60 178 180 233 125 175 117 20 275 120 315 161 140 140 161 113 113 8 00...

Страница 10: ...00 1350 670 670 450 440 1190 1420 700 710 1900 1950 1100 1100 2800 2800 1400 1400 2800 2800 1400 1400 2800 2800 1400 1400 50 52 43 45 53 53 45 46 53 55 50 46 50 220 380 220 380 220 380 220 380 220 380...

Страница 11: ...es kryt Netla te p itom na m ku ventil toru P i mont i pou vejte ochrann rukavice abyste p ede li zran n m zp soben m ostr mi hranami na ventil toru a pracovn m n in Zapojen do elektrick ho veden P e...

Страница 12: ...Ventil tor by nem l vyd vat dn nezvykl zvuky ani nadm ru vibrovat Pokud naraz te na pot e kter tato u ivatelsk p ru ka ne e obra te se pros m na odborn ka DR BA Doporu ujeme ventil tor istit ka d ch 6...

Страница 13: ...c ode dne n kupu Reklamace mus b t vy zena ve lh t 30 dn ode dne doru en reklamovan ho v robku prodejci nebo v robci N sleduj c z ruka nevylu uje neomezuje ani nijak nepop r z konn pr va kupuj c ho Z...

Страница 14: ...lektryczne i elektroniczne Raccolta differenziata apparecchi elettrici ed elettronici D chets tri s dispositifs lectriques et lectroniques Residuos clasificados equipos el ctricos y electr nicos Die E...

Отзывы: