background image

daka 832 furnace manual_3-18-13 

Page 8 of 14 

 

September 26, 2012, Revised March 18, 2013 

X. 

TROUBLESHOOTING 

 

PROBLEM 

CAUSE 

REMEDY 

Smoke puff back when loading, 
poor burning, insufficient heat

 

 
 
 

1. Insufficient draft. 
2. Insufficient make-up. 
 

1.  Debris or creosote could be blocking flue.  
Inadequate chimney height or design could be 
causing downdrafts.  Check chimney connector for 
air leaks and seal with furnace cement.  Adjust 
barometric regulator to higher setting. 
 
2. The house could be so well insulated that 
infiltration air is not getting in to replace air used in 
combustion.  Open a window slightly in furnace 
room or install a vent to the outside in furnace area. 

Poor heat throughout house 
while burning wood

 

1.  Poor quality wood. 
2.  Cold air return closed or 
blocked. 
3.  Duct joints leaking air. 
4.  Check flue gas temperature. 
5.  Fan control not adjusted 
properly. 

1.  Burn only wood which has been air-dried for at 
least six months, preferably a year or more. Use 
hardwoods such as hickory, oak, maple, etc. for 
highest heat value per load. 
2.  Check to insure that all cold air return vents are 
open and not blocked with furniture, etc. 
3.  Make sure that all duct joints are airtight.  Apply 
duct tape to seal. 
4.  Normal operating range is 300-600

F.  Lower 

temperature would indicate insufficient draft or 
inadequate combustion air.  To check flue gas 
temperature, we recommend that a smoke pipe 
surface thermometer or probe-type thermometer be 
used. 
5.  Insure that primary furnace blower is turning on 
to distribute heat effectively.  Lower “FAN ON” 
settings on primary furnace fan control to start 
circulation earlier. 

Auto Damper Control won’t hold 
setting

 

1. Auto damper control not in 
 adjustment. 

1.  Adjust tension on shaft by tightening only the 
shaft nut closest to the coil spring.  Using a 7/16” 
open end or adjustable wrench, turn tension nut 
counter-clockwise moving it only a quarter of a turn 
at a time.  Check tension on knob. Do not over 
tighten. 

Loose Knob on Auto Damper 
Control

 

 

1. Loosened through usage. 

1.  With furnace in cool mode, turn shaft so that 
a

rm of coil spring is in 10 o’clock position. Turn 

loose knob to 12 noon position.  Tighten set screw 
with 5/64” Allen wrench. 

Paint discoloration 
(whitish appearance)

 

1. Overheating. 

1.  Paint is rated for 900

F surfaces.  Overheating 

of furnace will cause a whitish appearance on 
outside of combustion chamber surfaces (it is 
normal around back & door).  Reduce chimney 
draft to control overheating.  Pink or white 
discoloration on chimney also is normal.  

NOTE:

 

To cover discoloration, obtain a high-combustion 
flat black spray paint from hardware store or 
fireplace shop. 

Creosote Formation 

1. Burning too cool of a fire. 
2. Auto Damper setting too low. 

Also reference page 3. 

 

Customer Service 
DAKA CORPORATION 
955 Industrial St NE Pine City MN 55063 
320-629-6737 
Monday through Friday, 8 AM to 4:30 PM Central Time 

 
 

Содержание 832

Страница 1: ...Y o u r Gu i d eT o B e s t B u r n i n g P r a c t i c e s B u r nWi s e www d a k a c o r p c o m 5 1 1 5 P a g e1 o f 4...

Страница 2: ...P r a c t i c a l T i p s F o r B u i l d i n g a F i r e...

Страница 3: ...o t b u r nw e t o r g r e e n u n s e a s o n e d l o g s T h e s e w i l l c a u s e c r e o s o t e b u i l d u pt h a t c o u l d l e a dt o a c h i mn e y f i r e D o n o t u s e l o g s ma d e f...

Страница 4: ...o o dma y n o t b e a b l e t o b u r ne f f i c i e n t l y C h e c k f o r l o c a l b u r nb a n s a n da v o i dw o o df u r n a c e u s e w h i l e i ne f f e c t A v o i db u r n i n g g a r b a...

Страница 5: ...rea temperature above the setting on the primary furnace wall thermostat the primary furnace should not burn any gas oil or use any electricity beyond that required to run the primary distribution blo...

Страница 6: ...ion Association s NFPA Publication 211 Standard for Chimneys Fireplaces Vents Solid Fuel based Appliances National Fire Protection Association 1 Battery March Park Quincy MA 02169 7471 1 617 770 3000...

Страница 7: ...G RISK OF FIRE DO NOT OPERATE WITH FLUE DRAFT EXCEEDING 06 WATER COLUMN DO NOT OPERATE WITH FUEL LOADING OR ASH REMOVAL DOORS OPEN DO NOT STORE FUEL OR OTHER COMBUSTIBLE MATERIAL WITHIN MARKED INSTALL...

Страница 8: ...cing ribs down resting on side rails D Attach Draft Blower Adapter Plate 10 to front of furnace below fire door using six No 12 x screws provided and then attach 50 cfm draft blower 9 to adapter plate...

Страница 9: ...as template mark and cut out 2 10 round holes in the side of the supply warm air plenum of the primary furnace IMPORTANT Verify beforehand that sufficient clearance is available above air conditioner...

Страница 10: ...ould be secured with a minimum of three No 7 sheet metal screws and further sealed with furnace cement to maintain good draft Smoke pipe should normally be installed with male ends leading from chimne...

Страница 11: ...amper plate on draft blower to no more than 1 3 open 3 Continue firing the fire with smaller loads more frequently tended Do not fill above bottom of door opening 4 Use extreme care and vigilance duri...

Страница 12: ...eck flue gas temperature we recommend that a smoke pipe surface thermometer or probe type thermometer be used 5 Insure that primary furnace blower is turning on to distribute heat effectively Lower FA...

Страница 13: ...ERSAL OR TOP TAKE OFF M DUCT STARTING COLLAR RECTANGULAR N COLD AIR RETURN GRILL O COLD AIR PLENUM P WARM AIR PLENUM Q DUCT END CAP R COLD AIR RETURN DUCT CAUTION SEE DUCT CLEARANCES FOR PROPER INSTAL...

Страница 14: ...h 18 2013 FIG 3 Clearances from Horizontal Warm Air Ducts FIG 4 Clearances to Combustibles FIG 5 Alternative Warm Air Plenum Pipe Insert Designs From Sides and Top of Warm Air Plenum 6 From Horizontal...

Страница 15: ...it Insert the 2 blue wires through hole in top of filter box cover Place conduit connector nut over blue wires Secure connector to filter box top Attach 1 blue wire to the common purple wire The other...

Страница 16: ...daka 832 furnace manual_3 18 13 Page 12 of 14 September 26 2012 Revised March 18 2013 FIG 7 Wiring Schematic...

Страница 17: ...50004 2 12 Firebrick 57600001 16 13 Starter Collar 10 not shown 56660026 2 14 Blower Multi Speed 636110010 1 15 Air Jacket Top Panel 64590809 1 16 Air Jacket Bottom Panel 64590807 1 17 Air Jacket Side...

Страница 18: ...used in other than residential service connected to conventional basement type up flow central heating system if non approved fuels are used in firing of units or if unit is damaged due to accident im...

Отзывы: