DAKA 622 Скачать руководство пользователя страница 8

Page 8 of 17 

DAKA Furnace Model 622 

2008 Edition 

 

 

Rev 2B: 11-9-12 

VII. OPERATING CONTROLS  

A. Fan Controls 

  The fan control on the side of the DAKA furnace has a rotating thermostat disc. 

Holding the disc firmly in place, adjust the three tangs for these three settings from 
left to right as follow:  

  FAN OFF - 90°, FAN ON - 130°, LIMIT - 200°. 
 
  These Fahrenheit settings will cause the 550-cfm back blowers on the DAKA furnace 

to turn ON when the temperature within the air jacket rises to 130°, and OFF when 
the temperature within falls below 90°.  The limit setting will shut off the front 60-cfm 
draft blower should an unsafe bonnet temperature over 200°F be reached.  The 
blower will be reactivated automatically when the temperature falls to 160°F. 

 

While this fan control is designed for fully automatic operation, you can turn the back 
blowers on manually at any time by pushing white button on fan control in.  Pulling 
button out will turn the blower off, unless the heat within the air jacket is above the 
"FAN ON" setting of the dial, in which case the blowers will continue to run until the 
temperature drops. 

 

The snap-disc control inside the J-box ring is an operating control for the 60-cfm 
draft blower, with a built in range of 190° OFF 170° ON, to prevent furnace 
overheating.  During normal operation this control may be activated frequently and is 
designed to help level the furnace heat output. 

 

IMPORTANT:  In a supplementary "Add-On" installation, the blowers on the 
DAKA furnace can be used as circulation blowers for heating the house. 
 
They also can be used in conjunction with your primary furnace blower to 
boost air circulation in large ductwork systems.  An optional fan control may 
need to be located in supply plenum to turn primary blower on and off when 
heat is received from the DAKA furnace.  (See FIG. 1 for fan control location). 

 

 

B.  Living Area Wall Thermostat Location

 (22) 

The Honeywell T812A1002D thermostat should be installed in any ground floor 
room on an inside wall, preferably beside the thermostat governing the primary 
furnace, which should be set approximately 5° lower than the DAKA thermostat.  
When falling room temperatures call for heat, the DAKA thermostat turns on the 60-
cfm front draft blower on the DAKA furnace; the additional combustion air increases 
the heat output until the DAKA room thermostat signals the blower to cut off. 
Combustion air then reduces to a maintenance level with a relatively low heat 
output, ready for the next firing cycle.  Should there be insufficient fuel to increase 
the room temperature as called for, the primary furnace will fire when the 
temperature falls to the 5° lower setting.  The DAKA draft blower will continue to run; 
however, to turn it off, lower the DAKA room thermostat setting below that of the 
primary furnace. 

Содержание 622

Страница 1: ...resent ductwork to distribute wood heated air throughout the home As long as the heat produced by the supplementary furnace keeps the living area temperature above the setting on the primary furnace w...

Страница 2: ...3 with adjustable settings available at extra cost 5 Installation of this furnace in mobile homes or garages is prohibited 6 This furnace must be installed on a non combustible floor surface such as c...

Страница 3: ...E MATERIAL WITHIN MARKED INSTALLATION CLEARANCES INSPECT AND CLEAN FLUES AND CHIMNEY REGULARLY CAUTION HOT SURFACES KEEP CHILDREN AWAY DO NOT TOUCH DURING OPERATION MAXIMUM DRAFT MARKED ON NAMEPLATE D...

Страница 4: ...rmit full opening of door Close door with handle in same position rotate counterclockwise to lock B Insert thermal gasket 6 between ash door 5 and ash pan 7 front and assemble using two 1 4 bolts and...

Страница 5: ...oward top of panel B Remove cover on Fan Control Using three 1 tube spacers provided proceed to mount the Fan Control 4 to the side of the panel using No 12 x 2 screws provided Fan Control is to be he...

Страница 6: ...ers the plenum Actual design and installation procedure for such a back draft damper is left to the installer due to the large number of plenum configurations involved See FIG 1 FIG 5 for illustration...

Страница 7: ...chimney draft to a maximum of 06 water column draft Barometric Regulator No 283 with adjustable draft setting is available through DAKA for this purpose 2 Smoke pipe should maintain a minimum 18 clea...

Страница 8: ...ration this control may be activated frequently and is designed to help level the furnace heat output IMPORTANT In a supplementary Add On installation the blowers on the DAKA furnace can be used as ci...

Страница 9: ...rd and possibly spilling into the room After closing fire door push damper rod fully in to seal rear vent VIII EMERGENCY OPERATION INSTRUCTIONS A Operation During Power Failure 1 Remove furnace filter...

Страница 10: ...ey contain could rust your furnace over the summer months thereby shortening the life of the unit X TROUBLE SHOOTING A Problem Smoke puff back when loading poor burning insufficient heat Solutions 1 I...

Страница 11: ...hitish appearance on outside of combustion chamber surfaces reduce chimney draft to control overheating NOTE To cover discoloration obtain a high temperature flat black spray paint from hardware or fi...

Страница 12: ...OP TAKE OFF M DUCT STARTING COLLAR RECTANGULAR N COLD AIR RETURN GRILL O COLD AIR PLENUM P WARM AIR PLENUM Q DUCT END CAP R COLD AIR RETURN DUCT CAUTION SEE DUCT CLEARANCES FOR PROPER INSTALLATION CHE...

Страница 13: ...IG 3 Clearances from Horizontal Warm Air Ducts FIG 4 Clearances to Combustibles FIG 5 Alternative Warm Air Plenum Pipe Insert Designs From Sides and Top of Warm Air Plenum 6 From Horizontal Ducts with...

Страница 14: ...Page 14 of 17 DAKA Furnace Model 622 2008 Edition Rev 2B 11 9 12 FIG 6 Wiring Schematic...

Страница 15: ...TRANFORMER RELAY 1 FROM DRAFT BLOWER WHITE WIRE 3 BLACK WIRES 1 FROM TRANFORMER 1 FROM FAN CONTROL 1 FROM POWER SUPPLY OPERATING FAN CONTROL SNAP DISC 2 GREEN GROUND WIRES 1 FROM POWER SUPPLY 1 FROM J...

Страница 16: ...08 1 17 Air Jacket Side Panel w o holes with holes 64590209 0212 1ea 18 not used 56811158 1 19 Swing Plate A 57590211 1 20 Operating Control Snap Disc 190 open C 58640005 1 21 Draft Blower Adapter Pla...

Страница 17: ...er than residential service connected to conventional basement type up flow central heating system if non approved fuels are used in firing of units or if unit is damaged due to accident improper inst...

Отзывы: