background image

 

Page 6 of 51

 

SK2018 GLOBAL FDLA-V/P-AC-001 

 

General Specifications 

A.2.1.

 

2-pipe Systems 

Product range

:  FDLA(3R) Low Static Hydronic Ducted Fan Coil Unit 

FDLA(3R)-V~ Hydronic Ducted 2-pipe Unit with 3-row Coils and AC motor 

FDLA(3R)-

[Size]

-V~ 

09 

12 

15 

18 

24 

30 

34 

40 

54 

60 

Uni

C

on

fi

gu

ra

ti

on

 

Configuration 

2-pipe 

Number Of Fan Blowers 

Single 

Twin 

Three 

Four 

Three 

Four 

Power Supply (V/Ph/Hz) 

230 / 1 / 50

220 / 1 / 60 

Operation Control 

~S: Complete function onboard PCB with integrated group control functionality. 
~T: Terminal strip only. 

P

e

rf

or

m

anc

e

 D

ata

 

Ai

Air Flow 

m3/hr 

463   

574   

784   

913   

1085   

1363   

1611 

1915 

2477 

3198 

429   

553   

746   

892   

1051   

1310   

1554 

1871 

2374 

3019 

401   

524   

656   

749   

953   

1146   

1413 

1767 

2247 

2912 

ESP 

Pa 

58 

54 

59 

55 

62 

56 

52 

60 

60 

57 

50 

50 

50 

50 

50 

50 

50 

50 

50 

50 

35 

35 

30 

32 

39 

31 

35 

40 

43 

39 

C

oo

lin

Cooling Capacity

e

 

kW 

2.82 

3.39 

4.34 

5.13 

5.84 

8.39 

8.74 

10.21 

13.25 

15.54 

2.66 

3.29 

4.19 

5.02 

5.7 

8.13 

8.53 

10.06 

12.86 

14.85 

2.52 

3.17 

3.79 

4.43 

5.3 

7.35 

7.95 

9.67 

12.27 

14.4 

Sensible Cooling 

Capacity

e

 

2.03 

2.42 

3.15 

3.69 

4.16 

5.98 

6.31 

7.39 

9.55 

11.14 

1.91 

2.34 

3.03 

3.6 

4.05 

5.78 

6.15 

7.27 

9.25 

10.62 

1.8 

2.25 

2.72 

3.14 

3.74 

5.18 

5.7 

6.95 

8.77 

10.25 

Latent Cooling 

Capacity 

kW 

0.79 

0.97 

1.19 

1.44 

1.68 

2.41 

2.43 

2.82 

3.7 

4.4 

0.75 

0.95 

1.16 

1.42 

1.65 

2.35 

2.38 

2.79 

3.61 

4.23 

0.72 

0.92 

1.07 

1.29 

1.56 

2.17 

2.25 

2.72 

3.5 

4.15 

FCEER

Rating 

42.4   

40.8   

33.5   

39.1   

33.2   

38.7   

37.5   

31.8   

35.2   

32.3   

Class 

H

e

ati

ng

 

Heating Capacity

e

 

kW 

2.43 

3.04 

3.98 

4.67 

5.52 

7.13 

8.23 

9.52 

12.2 

15.3 

2.32 

2.95 

3.82 

4.6 

5.38 

6.94 

8.02 

9.36 

11.9 

14.6 

2.2 

2.82 

3.47 

3.99 

5.03 

6.26 

7.42 

8.96 

11.4 

14.3 

Max. Electric Heater 

Capacity@220V 

FCCOP

Rating 

37.1   

36.4   

30.5   

35.2   

31.3   

32.9   

35.0   

29.5   

32.7   

32.3   

Class 

Sou

nd

 

Sound Pressure Level ( Outlet ) 

dB(A) 

48/47/43  50/49/46  52/50/44  52/51/46  54/52/49  53/52/47  56/54/50  58/55/52  58/54/50  59/57/55 

Sound Pressure Level   
( Inlet + Radiated ) 

50/49/45  52/51/48  54/52/46  54/53/48  56/54/51  55/54/49  58/56/52  60/57/54  60/56/52  61/59/57 

Sound Power Level ( Outlet )

57/56/52  59/58/55  61/59/53  61/60/55  63/61/58  62/61/56  65/63/59  67/64/61  67/63/59  68/66/64 

Sound Power Level   
( Inlet + Radiated )

59/58/54  61/60/57  63/61/55  63/62/57  65/63/60  64/63/58  67/65/61  69/66/63  69/65/61  70/68/66 

El

e

ctr

ic

al

 

Fan Motor Power

e

 

67 

82 

120 

123 

167 

204 

222 

314 

430 

554 

66 

80 

120 

122 

166 

203 

220 

310 

365 

494 

58 

78 

116 

117 

163 

194 

216 

307 

345 

424 

Fan Motor Running Current @ H 

0.29   

0.36   

0.52   

0.53   

0.73   

0.89   

0.97   

1.37   

1.87   

2.41   

Fan Motor Starting Current @ H 

0.87   

1.07   

1.57   

1.60   

2.18   

2.66   

2.90   

4.10   

5.61   

7.23   

H

yd

ra

ul

ic

 

Cooling Water Flow 

Rate 

L/h 

483 

581 

744 

880 

1002 

1438 

1498 

1751 

2272 

2663 

456 

564 

718 

861 

976 

1394 

1463 

1724 

2205 

2546 

433 

543 

649 

760 

908 

1260 

1363 

1658 

2104 

2468 

Cooling Pressure 

Drop 

kPa 

23.6 

36.47 

20.51 

30.04 

41.16 

46.3 

17.45 

24.15 

44.88 

63.92 

21.42 

34.68 

19.29 

28.9 

39.41 

43.94 

16.75 

23.52 

42.65 

59.2 

19.58 

32.5 

16.27 

23.4 

34.82 

37 

14.86 

22 

39.38 

56.14 

Heating Water 

Flow Rate 

L/h 

417 

522 

682 

801 

947 

1223 

1412 

1632 

2099 

2615 

397 

505 

655 

788 

922 

1190 

1374 

1605 

2033 

2501 

377 

484 

596 

685 

862 

1074 

1272 

1535 

1947 

2444 

Heating Pressure 

Drop 

kPa 

15.4 

25.5 

14.8 

21.6 

31.6 

29.8 

13.3 

18.1 

33.4 

52.9 

14.2 

24.1 

13.8 

21 

30.2 

28.4 

12.7 

17.6 

31.6 

49.1 

12.9 

22.4 

11.7 

16.5 

27 

23.8 

11.1 

16.3 

29.4 

47.2 

water content 

0.72 

0.87 

1.02 

1.17 

1.32 

1.92 

2.07 

2.22 

2.59 

2.87 

C

on

str

uc

ti

on

 a

nd

  

P

ac

ki

ng

 D

ata

 

Water 

Connections 

Type 

Socket (Threaded Female) 

In 

mm 

[in] 

19.05 [3/4] 

Out 

Condensate Drainage 

Connection 

Dimensions 

mm 

755   

855   

955   

1155   

1255   

1655   

1755   

1855   

1755   

1955   

550   

620   

250   

300   

Net Weight 

kg 

17   

23   

24   

28   

31   

36   

43   

45   

51   

60   

"e": Above specifications are based on declared Eurovent test data for the year of publication of this document. To confirm the most updated specifications, 
please visi

www.eurovent-certification.com

. 

 
Eurovent testing conditions: 

a. Cooling mode:

 

 

b. Heating mode: 

- Return air temperature: 27C DB/ 19C WB.

 

- Return air temperature: 20C. 

- Inlet/ outlet water temperature: 7C/ 12C. 

 

- Inlet/ Outlet water temperature: 45C/ 40C. 

Содержание FDLA-09

Страница 1: ...SK2018 GLOBAL FDLA V P AC 001 FDLA V P AC MOTOR...

Страница 2: ...stage in the manufacturing of our products Throughout the production process we maintain strict control starting with our extensive resources in research and development through to the design and man...

Страница 3: ...ection 19 C Maintenance 21 C 1 General Maintenance 21 C 2 Regular Maintenance 21 C 3 Filter Cleaning 21 C 4 Fan Motor Assembly Maintenance 21 C 5 Coil Direction Interchange 22 C 6 Electric Heater Repl...

Страница 4: ...rror Description 35 D 14 LED Display on Master Slave Connection 36 D 15 Master Slave Network 37 D 15 1 Master Unit Control Settings 37 D 15 2 Master Slave Network Setup 38 D 15 3 Master Slave Communic...

Страница 5: ...onboard PCB with integrated group control functionality T Terminal strip only P Chilled Hot Water 4 Pipe V Chilled Hot Water 2 Pipe 09 60 Unit Sizes See General Specification Section A for cooling an...

Страница 6: ...and dynamically balanced for smooth quite operation The housing is constructed from heavy gauge galvanized steel with die formed inlet cones AC Motor Standard motors are PSC permanently lubricated typ...

Страница 7: ...Level Inlet Radiated 50 49 45 52 51 48 54 52 46 54 53 48 56 54 51 55 54 49 58 56 52 60 57 54 60 56 52 61 59 57 Sound Power Level Outlet e 57 56 52 59 58 55 61 59 53 61 60 55 63 61 58 62 61 56 65 63 5...

Страница 8: ...52 58 54 50 59 57 55 Sound Pressure Level Inlet Radiated 50 49 45 52 51 48 54 52 46 54 53 48 56 54 51 55 54 49 58 56 52 60 57 54 60 56 52 61 59 57 Sound Power Level Outlet 57 56 52 59 58 55 61 59 53...

Страница 9: ...let Radiated 50 49 45 52 51 48 54 52 46 54 53 48 56 54 51 55 54 49 58 56 52 60 57 54 60 56 52 61 59 57 Sound Power Level Outlet 57 56 52 59 58 55 61 59 53 55 50 32 63 61 58 62 61 56 65 63 59 67 64 61...

Страница 10: ...r Inch No of Rows Fin width mm No of Circuits Tube mm FDLA 4R 09 200 480 12 7 4 88 2 9 52 FDLA 4R 12 580 2 FDLA 4R 15 680 2 FDLA 4R 18 780 3 FDLA 4R 24 880 3 FDLA 4R 30 1280 4 FDLA 4R 34 1380 4 FDLA 4...

Страница 11: ...13 FDLA 40 1575 1525 1525 1550 1855 400 14 250 213 FDLA 54 1435 1385 1385 1410 1755 470 14 300 263 FDLA 60 1695 1645 1645 1670 1955 470 14 300 263 Model J K L M N P Q V W FDLA 09 25 153 546 35 25 152...

Страница 12: ...47 8 44 315 44 5 43 8 39 9 45 6 44 9 41 6 48 7 48 42 2 48 4 47 3 43 7 53 4 50 2 47 4 400 49 9 47 7 43 7 49 6 49 3 45 5 51 3 49 5 45 1 52 3 50 8 45 8 54 3 52 8 50 8 500 53 1 52 4 47 2 54 2 53 8 50 9 5...

Страница 13: ...6 315 50 48 8 44 5 51 52 3 47 2 55 7 54 9 50 4 55 50 3 46 8 57 9 56 4 56 2 400 53 2 53 4 48 3 54 5 53 9 49 9 57 3 56 52 2 58 7 55 5 51 9 59 7 59 4 57 6 500 56 4 55 52 1 57 9 56 5 53 3 59 4 58 6 55 8...

Страница 14: ...V Power Consumption 6W during valve position change Running Times 15 sec Pipe Fitting NPT internal thread Body Forged brass nickel plated Ball Chrome plated brass Stem Brass Seats Fiberglass reinforce...

Страница 15: ...al Bi directional modulating proportional control Technical data Working media cool hot water or with 60 glycol Media Temp Range 34 F to 203 F 1 C to 95 C Rating pressure 2 0MPa Max Differential Press...

Страница 16: ...cing fan coil unit should be performed by qualified service personnel only This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or...

Страница 17: ...e specification table for weight of the unit 4 The unit must be installed horizontally to ensure proper operation and condensate draining 5 The external static pressure of the ducting must be within t...

Страница 18: ...drain pan is designed with a slight gradient to facilitate drainage CAUTIONS Dimension M and N are determined by air duct design Air duct should be fire proof Please refer to concerned country nationa...

Страница 19: ...and local regulations Piping Connections 1 Using suitable fittings as water pipe connections with reference to the outline and dimensions 2 The water inlet is on the bottom while outlet on top 3 The c...

Страница 20: ...S Control Wiring Diagram Please refer to section D T1 Control Wiring Diagram T2 24Vac Control Wiring Diagram CONTROL LOAD Fuse EH element Protection switch L N Hi M Lo V1 V2 N Heating signal 230V Coo...

Страница 21: ...ignal contact A2 Heating status signal contact DA1 0 10Vdc signal DA2 0 10Vdc signal A B RS485 port AC EC S4 Thermostat Wiring scheme Rt CONTROL LOAD Fuse EH element Protection switch L N Hi M Lo V1 V...

Страница 22: ...t brush or vacuumed with a vacuum cleaner 6 If the water coil is not being used during the winter season it should be drained or an anti freezing solution should be added to the water circuit to avoid...

Страница 23: ...eed to be exchanged too After interchanged the upper is water inlet and the bottom is water outlet Electric Heater Replacement 1 Unscrew the old FDLA EH module from the unit Prepare a new FDLA EH modu...

Страница 24: ...Ts cool operation will be terminated Heating operation will only be activated when Tr Ts 4 C If Tr Ts heating operation will be terminated Float switch Float Voltage free NC The contact is closed befo...

Страница 25: ...set unit type master or slave Mode Configuration DIPB S2 SW1 Occupancy contact setting SW2 Unit configuration setting 0 2 pipe system 1 4 pipe system SW3 On off vavle configuration setting 0 no vavle...

Страница 26: ...sor Tr LED display IRreceiver chilled hot water Ti2 hot water louver stepping moter connections CN2 A B A B S1 S2 FLOAT EH2 EH1 PR2 PR1 AUX2 AUX1 HF MF LF VALVE1VALVE2 WP CONNECT GY RD WH BK BL PUMP L...

Страница 27: ...Page 26 of 51 SK2018 GLOBAL FDLA V P AC 001 Configuration Settings...

Страница 28: ...ure or cessation of power supply The restored parameter data set depends on the type of user interface a Handset only user interface When the power ON signal is received by the fan coil unit and no wi...

Страница 29: ...TV1 and AUX1 are turned off Indoor fan repeatedly runs at low fan speed for 30 seconds and then stops for 3 minutes d The range of Ts is 16 30 C e Indoor fan speed can be adjusted to low medium high a...

Страница 30: ...ram DEHUMIDIFICATION MODE a MTV2 AUX1 and heater are always off b If Tr 25 C then MTV1 and AUX2 will be ON for 3 minutes and then OFF for 4 minutes c If 16 C Tr 25 C then MTV1 and AUX2 will be ON for...

Страница 31: ...heat operation is terminated and AUX1 is turned off Indoor fan repeatedly runs at low fan speed for 30 seconds and then stops for 3 minutes d The range of Ts is 16 30 C e Indoor fan speed can be adjus...

Страница 32: ...to low medium and high HEAT MODE Without Electrical Heater a MTV1 AUX2 and are heater always off b If Tr Ts 1 C or 4 C if economy contact is activated then heat operation is activated MTV2 and AUX1 ar...

Страница 33: ...75 C then MTV2 and AUX1 are turned off indoor fan remains on and runs at high speed b If Ti2 70 C then MTV2 and AUX1 are turned on indoor fan remains on and runs at set speed c If the indoor coil tem...

Страница 34: ...operation will cancel the sleep mode The cool mode sleep profile is The heat mode sleep profile is Auto Fan Speed COOL MODE HEAT MODE Fan speed cannot change until it has run for more than 30 seconds...

Страница 35: ...1 second or the fan is not working the heater will be turned off immediately and report an error and fan speed will change to high speed Once the contact is returned to the closed position 60 seconds...

Страница 36: ...amaged 1 Check if Ti2 plug is connected or not 2 Check if sensor s resistance is correct or not Return air sensor failure Green LED blinks 3 times stops for 3s Room sensor unplugged or damaged 1 Check...

Страница 37: ...s stops for 3s Check unit 15 communication plug and fix it Unit 16 failure RED LED blinks 16 times stops for 3s Check unit 16 communication plug and fix it Unit 17 failure RED LED blinks 17 times stop...

Страница 38: ...l Handset to Set Master Control Unit 1 Connect all the units PCBs according to the wire color and type of connector 2 Select the master unit by setting DIPA S1 SW6 to ON 1 in the PCB 3 Ensure the DIPA...

Страница 39: ...box 2 Communication plug A B A B is printed on the main PCB When you connect the wires please ensure connection of A to A and B to B 3 Connection wire i If the total length of wire is more than 1000m...

Страница 40: ...wire contact by using a multimeter c Check 1 and 2 3 and 4 5 and 6 to be sure the connections are correct d If the resistance between two wire contacts is too high please check and reconnect the wire...

Страница 41: ...IPA S1 SW5 DIPA S1 SW4 DIPA S1 SW3 DIPA S1 SW2 DIPA S1 SW1 Unit No Remark 1 0 0 0 0 0 01 Master 0 0 0 0 0 1 02 Slave 0 0 0 0 1 0 03 Slave 0 0 0 0 1 1 04 Slave 0 0 0 1 0 0 05 Slave 0 0 0 1 0 1 06 Slave...

Страница 42: ...re used to test unit Valid Error code table Error code Description Definition 01 01H Invalid commands Received commands beyond valid commands 02 02H Invalid data address Data addresses beyond valid da...

Страница 43: ...W Calibration wired wall pad and set timer function Minute 300008 W Calibration wired wall pad and set timer function Second 300009 W Calibration wired wall pad and set timer function Hours in Timer...

Страница 44: ...ved Bit7 Electrical heater failure Bit8 Motor1 Error Bit9 Motor2 Error Bit10 System parameters error Bit11 Anti frozen protection Bit12 Reserved Bit13 Reserved Bit14 Reserved Bit15 Reserved Fan speed...

Страница 45: ...omatically sent to the slave units Auto Cool Heat operation will be applicable in 4 pipe system only Swing and Louver functions are not applicable European version only uses degree C setting Swing It...

Страница 46: ...51 SK2018 GLOBAL FDLA V P AC 001 Wired Wall Pad Controller Day display Mode display Temperature display Fan speed display Timer display Real Time display Master Slave Button display Wifi icon Sleep ic...

Страница 47: ...ON blinks press to set timer date from Monday to Sunday Press to set hour and minute of timer on or timer off alternately ON blinks when timer is set to on and OFF blinks when timer is set to off Pre...

Страница 48: ...OFF unit Press button once H blinks in master slave display area then press to turn on unit H blinks or turn OFF unit S blinks 2 Temperature Press twice temperature blinks in temperature display area...

Страница 49: ...r area and Error code blinks on real time minute area The Error codes display alternately if more than one error is detected If there is no slave unit online only error code is shown in real time minu...

Страница 50: ...3 35 6 36 6 517 6 675 2 28 85 29 76 30 68 36 6 099 6 252 6 407 3 27 44 28 29 29 15 37 5 85 6 6 151 T Rmin Rnom Rmax T Rmin Rnom Rmax C K K K C K K K 38 5 614 5 759 5 907 75 1 417 1 474 1 532 39 5 387...

Страница 51: ...ck fuse on board Place in the ON position Check the room control Check fan motor Filter clogged Air flow obstructed Room control regulation Incorrect water temperature Air present Insufficient output...

Страница 52: ...em Description 1 Top Panel 9 Fan blower 2 Right side panel 10 Fan deck 3 Return air flange 11 Motor 4 Filter 12 Coil 5 Bottom panel 13 Control box 6 Filter fixture 14 Terminal block 7 Drain pan 15 Dis...

Страница 53: ...FDHD V P AC MOTOR...

Страница 54: ...opean Community to guarantee correct standards of safety In order to guarantee the very highest standards and performance we manage every stage in the manufacturing of our products Throughout the prod...

Страница 55: ...ING DIAGRAM 22 D 2 CONFIGURATION SETTINGS 24 D 3 CONTROL LOGIC FOR 2 PIPE SYSTEM 26 D 4 With Valve Configuration 26 D 4 1 Without Valve Configuration 29 D 4 2 CONTROL LOGICS FOR 4 PIPE SYSTEM 31 D 5 S...

Страница 56: ...oard PCB with integrated group control functionality T Terminal strip only P Chilled Hot Water 4 Pipe V Chilled Hot Water 2 Pipe 18 100 Unit Sizes See General Specification section A for cooling and h...

Страница 57: ...onded to copper tubes FAN The 3 Speed centrifugal fan is statically and dynamically balanced ELECTRICAL SWITCHBOARD The electrical switchboard is constructed in accordance with IEC 204 1 EN60204 1 com...

Страница 58: ...und Power Level Outlet e dB A 54 52 51 58 56 54 59 57 56 63 62 60 Sound Power Level Inlet Radiated e 57 55 54 62 59 59 62 60 59 66 65 63 Electrical Fan Motor Powere H 3 W 300 236 346 542 M 2 232 202 2...

Страница 59: ...B A 66 65 63 69 67 64 71 68 65 74 73 71 Sound Power Level Inlet Radiated e 69 68 66 72 70 67 74 71 68 77 76 74 Electrical Fan Motor Powere H 3 W 570 625 813 988 M 2 450 520 600 860 L 1 395 464 483 780...

Страница 60: ...Heating Pressure Drop 3 kPa 4 98 16 5 22 3 26 0 2 4 39 14 6 19 3 23 0 1 3 51 12 4 15 8 19 3 Water Content Hot Water L 0 37 0 638 0 638 0 638 FDHD Size P 48 60B 75 100 Performance Data Heating Heating...

Страница 61: ...Pressure Drop 3 kPa 3 9 12 6 17 3 20 4 2 3 41 11 0 14 9 17 9 1 2 69 9 32 12 0 14 9 Water Content Hot Water L 0 74 1 27 1 27 1 27 FDHD Size P 48 60B 75 100 Performance Data Heating Heating Capacity H...

Страница 62: ...ngth mm Fins per Inch No of Rows Fin width mm No of Circuits Tube mm FDHD 18R P 275 534 12 7 1 21 65 2 9 52 FDHD 24R P 275 934 12 7 1 21 65 2 FDHD 30R P 275 934 12 7 1 21 65 2 FDHD 36R P 275 934 12 7...

Страница 63: ...DHD 48 60B 1460 1392 1430 495 650 60 14 380 FDHD 75 1460 1392 1430 595 750 70 14 430 FDHD 100 1760 1692 1730 595 750 70 14 430 Model I J K L M X Y R FDHD 18R 240 30 40 50 630 65 150 3 4 FDHD 24R 30R 3...

Страница 64: ...way or Three way Operating Mode On Off Power Supply AC220V Power Consumption 6W during valve position change Running Times 15 sec Pipe Fitting NPT internal thread Body Forged brass nickel plated Ball...

Страница 65: ...tors If the supply cord is damaged it must be replaced by qualified personnel Installing and servicing air conditioning equipment should be done by qualified service personnel only This appliance is n...

Страница 66: ...must be installed horizontally to ensure proper operation and condensate draining 5 The external static pressure of the ducting must be within the unit s static pressure range 6 Confirm that the unit...

Страница 67: ...onnection B 1 3 Step 1 Loosen the screws on the drain pan and the 4 screws on both side panels of the unit Remove the coil Step 2 Change the coil direction and install it properly Reassemble the drain...

Страница 68: ...ope of at least 2 cm m without obstructions or bottlenecks 3 Fit a siphon By eliminating the pressure drop caused by the fan this prevents air being sucked up the drain hose 4 Connect the condensate d...

Страница 69: ...B 1 4 4 Electrical connections T Configuration standard version...

Страница 70: ...r to remove dust dirt or lint They can be brushed with a soft brush or vacuumed with a vacuum cleaner 6 If the water coil is not being used during the winter season it should be drained or an anti fre...

Страница 71: ...Fan Motor Assembly Maintenance C 4 1 Loosen the screws on the bottom panel 1 2 Loosen the 4 screws on both sides of the unit Bottom Panel 1 4 Screws on both sides...

Страница 72: ...Occupancy contact PR1 PR2 This contact may be connected to occupancy sensor or BMS system DIP SWITCH IS ON Window contact The contact is normally open If the contact has been closed for 10 minutes the...

Страница 73: ...output L Voltage of electrical heater Live L EH Voltage output L maximum 30A Output Stepping motor CN1 2 Power supply to louver stepping motors Voltage output L Cold water free contact AUX2 Voltage fr...

Страница 74: ...Wiring Diagram D 2 SK NCPDWH 001b S Configuration Full Control PCB...

Страница 75: ...5 CN6 CN7 S1 S2 5 6 PR O RS485 CPU PR O AUX2 AUX2 AUX1 AUX1 N pump electrical heating 30A heating value cooling value low speed medial speed high speed VALVE1 VALVE2 N HF LF MF N ON DIP1 8 8 7 6 5 4 3...

Страница 76: ...Configuration Settings D 3...

Страница 77: ...The restored parameter data set depends on the type of user interface a Handset only user interface When the power ON signal is received by the air conditioner and no wired wall pad is installed the...

Страница 78: ...ctrical heater a MTV2 AUX2 and electric heater are always off b If Tr Ts 1 C or 4 C if economy contact is activated then heat operation is activated and MTV1 and AUX1 are turned on Indoor fan runs at...

Страница 79: ...ff then indoor fan continues to run at set speed b If 36 C Ti1 38 C then MTV1 and AUX1 are turned off Then indoor fan maintains its original state c If Ti1 36 C then MTV1 and AUX1 are turned off Then...

Страница 80: ...user changes the mode manually or restarts the unit Should the Ti1 sensor be damaged auto mode will not function Auto heat with electric heater as primary heat source all configuration auto changeover...

Страница 81: ...1 and AUX2 are turned off b Indoor fan speed can be adjusted to low medium and high HEAT MODE Heat mode without electrical heater a MTV1 MTV2 AUX2 and heater are always off b If Tr Ts 1 C or 4 C if ec...

Страница 82: ...the unit will work according to the pre heat and post heat program DEHUMIDIFICATION MODE a MTV1 MTV2 AUX1 and heater are always off b If Tr 25 C then indoor fan and AUX2 will be ON for 3 minutes and...

Страница 83: ...gh HEAT MODE Without Electrical Heater a MTV1 AUX2 and are heater always off b If Tr Ts 1 C or 4 C if economy contact is activated then heat operation is activated MTV2 and AUX1 are turned on Indoor f...

Страница 84: ...X1 are turned off indoor fan remains on and runs at high speed b If Ti2 70 C then MTV2 and AUX1 are turned on indoor fan remains on and runs at set speed c If the indoor coil temperature sensor is dam...

Страница 85: ...2 hours c If the sleep mode is activated when the unit is in heat mode then the indoor fan will run at set speed and Ts will decrease by 2 C over 2 hours d Changing the mode of operation will cancel...

Страница 86: ...Control Version Louver angle 0 100 opens clockwise with widest angle at 100 Swing angle 35 100 opens clockwise to 68 User may stop louver at any desired position between 35 100 Buzzer D 9 If a command...

Страница 87: ...when unit is turned on If the float switch is opened continuously 5 seconds then the drain pump will work and MTV1 will remain off After the float switch is closed the drain pump will run for an addit...

Страница 88: ...Green LED blinks 3 times stops for 3s Room sensor unplugged or damaged 1 Check if Tr plug is connected or not 2 Check if sensor s resistance is correct or not Indoor coil sensor 1 failure Green LED b...

Страница 89: ...ck unit 15 communication plug and fix it Unit 16 failure RED LED blinks 16 times stops for 3s Check unit 16 communication plug and fix it Unit 17 failure RED LED blinks 17 times stops for 3s Check uni...

Страница 90: ...ster unit settings are unit ON OFF Mode Fan Speed Timer Clock Set Temperature Swing Function and Sleep Function for wall pad operation SLAVE UNIT FUNCTION a The slave unit receives data regarding its...

Страница 91: ...lug A B A B is printed on the main PCB When you connect the wires please ensure connection of A to A and B to B c Connection wire 1 If the total length of wire is more than 1000m please use shielded w...

Страница 92: ...the wire contact by using a multimeter iii Check 1 and 2 3 and 4 5 and 6 to be sure the connections are correct iv If the resistance between two wire contacts is too high please check and reconnect th...

Страница 93: ...ad to Set Master Control Unit a Connect all the units PCBs according to the wire color and type of connector b Select the master unit by setting DIPA S1 SW6 to ON 1 in the PCB c Ensure the DIPA S1 SW6...

Страница 94: ...DIPA S1 SW3 DIPA S1 SW2 DIPA S1 SW1 Unit No Remark 1 0 0 0 0 0 01 Master 0 0 0 0 0 1 02 Slave 0 0 0 0 1 0 03 Slave 0 0 0 0 1 1 04 Slave 0 0 0 1 0 0 05 Slave 0 0 0 1 0 1 06 Slave 0 0 0 1 1 0 07 Slave...

Страница 95: ...Read Discrete Inputs 03 03H Read Holding Registers 04 04H Read Input Registers 05 05H Write Single Coil 06 06H Write Single Register 15 0FH Write Multiple Coils 16 10H Write Multiple Registers 255 FFH...

Страница 96: ...eserved 100012 Reserved 100013 Reserved 100014 Reserved 100015 R read only W write only R W read and write Discrete table Description Address Type Remark MTV1 200000 R MTV2 200001 R AUX1 200002 R AUX2...

Страница 97: ...all pad and set timer function Minute 300008 W Calibration wired wall pad and set timer function Second 300009 W Calibration wired wall pad and set timer function Hours in Timer on 300010 R W Timer ON...

Страница 98: ...ical heater failure Bit8 Motor1 Error Bit9 Motor2 Error Bit10 System parameters error Bit11 Reserved Bit12 Reserved Bit13 Reserved Bit14 Reserved Bit15 Reserved Fan speed status 400006 R Low 04 H Medi...

Страница 99: ...with handset is the master unit its settings are automatically sent to the slave units Auto Cool Heat operation will be applicable in 4 pipe system only Swing function is not applicable European versi...

Страница 100: ...automatically whether it is 2 pipe or 4 pipe system Auto Cool Heat operation is applicable in 4 pipe system only When the wall pad is installed the wall pad temperature sensor automatically overrides...

Страница 101: ...s CANCEL key to cancel the current ON timer setting and the timer display area will show Press DAY button to change the day the ON timer is to be programmed for 2 Press TIMER button again and O FF sym...

Страница 102: ...l cancel all timer settings in all slave units Timer settings will be broadcast to all slave units e Clock synchronization by master unit is as follows Press TIME and TIME buttons for 3 seconds to act...

Страница 103: ...e units n Unit operation parameters browsing Hold down CANCEL and FAN buttons for 3 seconds to enter into operation parameters browsing mode Unit display area shows the address of the slave unit being...

Страница 104: ...16 14 69 15 05 15 41 17 79 8 83 17 86 64 17 14 03 14 37 14 7 16 75 39 78 53 81 76 18 13 41 13 72 14 03 15 71 26 74 18 77 19 19 12 81 13 1 13 4 14 67 37 70 1 72 9 20 12 24 12 52 12 79 13 63 73 66 26 6...

Страница 105: ...52 3 225 3 326 3 43 89 0 8998 0 9401 0 9818 53 3 105 3 204 3 305 90 0 8721 0 9115 0 9522 54 2 99 3 086 3 185 91 0 8455 0 8839 0 9237 55 2 88 2 974 3 07 92 0 8198 0 8573 0 8961 56 2 774 2 866 2 959 93...

Страница 106: ...ard Place in the ON position Check the room control Check fan motor Filter clogged Air flow obstructed Room control regulation Incorrect water temperature Air present Insufficient output Clean the fil...

Страница 107: ...OFF motorized actuator 1 11 SK DFPS A 005d 2 way ball valve with 1 inch connectors and ON OFF motorized actuator for PDW H 75 100 1 12 SK DFPS A 005c 3 way ball valve with 1 inch connectors and ON OFF...

Страница 108: ...able damper for PDW H 18 1 39 SK DFPS DH N015b 2 way inlet plenum with adjustable damper for PDW H 24 30 36 1 40 SK DFPS DH 015c 2 way inlet plenum with adjustable damper for PDW H 48 60 1 41 SK DFPS...

Страница 109: ...AMPER SK DFPS DH 015 The two way intake plenum with damper enables the room air intake duct and the external air intake duct to be connected when required The width of the external air intake duct acc...

Страница 110: ...with rated airflow and the ducts fully open AUXILIARY 1 ROW or 2 ROWS HEATING COIL MODULE FOR 4 PIPE SYSTEM SK DFPS DH 009 Install the auxiliary 1 row or 2rows heating coil module to the unit with 8 s...

Страница 111: ......

Страница 112: ...SK2019 FCSD H V P ECM 001 FCSD H V P ECM MOTOR...

Страница 113: ...tage in the manufacturing of our products Throughout the production process we maintain strict control starting with our extensive resources in research and development through to the design and manuf...

Страница 114: ...Layout and Ceiling Opening 32 Interconnecting Wiring 36 Mounting Front Panel Assembly 37 Start Up 37 Maintenance 38 For Units Out Of Use for Extended Period 38 Extra Maintenance 38 Filter Removal 38 A...

Страница 115: ...ave Communication Method 62 Open Modbus protocol 63 Control Specifications Flexible Function PCB EC W1 Control 66 Features 66 I O Port Definitions 66 Onboard Configurations 66 Wiring Diagrams 67 Stand...

Страница 116: ...ic Heater 04 16 Unit Sizes See General Specification section A for cooling and heating capacities FCSD Hydronic Cassette G Series FCSD H 12 V S ECM ECM EC Motor Configuration S Complete function onboa...

Страница 117: ...fixed to a mounting bracket The pump can be withdrawn from the bottom after removing the front panel A float switch is fitted to stop the cooling action should the pump become blocked or fail Louver L...

Страница 118: ...essure Level Outlet dB A 43 39 27 50 40 26 50 40 26 45 42 30 Sound Power Level Outlet e 49 46 39 58 47 39 60 49 40 54 51 42 Electrical Power input in cooling modee H W 15 38 38 38 M 11 18 18 27 L 5 13...

Страница 119: ...42 30 56 45 32 58 50 37 Sound Power Level Outlet e 63 51 42 65 54 41 67 59 46 Electrical Power input in cooling modee H W 69 72 205 M 32 37 70 L 20 16 25 Power input in heating modee H W 69 72 205 M...

Страница 120: ...evel Outlet e 58 49 40 58 55 50 63 51 42 67 54 41 67 57 46 Electrical Power input in cooling modee H W 48 38 69 72 205 M 20 27 32 37 60 L 14 20 20 16 25 Power input in heating modee H W 39 38 69 72 20...

Страница 121: ...2 6 3 8 4 Pipe Systems Cooling Coil Model Fin Height mm Fin Length mm Fins inch No of rows No of circuits Tube Diameter inch Inner Outer FCSD 08 P 250 1196 1299 13 2 3 3 8 FCSD 09 P 200 2148 2286 13 2...

Страница 122: ...627 62 124 255 FCSD 08 08R V 680 582 280 627 112 174 290 FCSD H 12 V 830 730 344 775 84 149 260 FCSD H 20 V 980 830 487 875 106 177 290 Model H I J K L M N FCSD 04 V 283 118 110 50 162 124 100 FCSD 08...

Страница 123: ...001 Model A B C D E F G H FCSD 09 V 680 1240 1145 585 750 630 100 520 FCSD 16 V 680 1240 1145 585 750 630 100 520 Model I J K L M N O FCSD 09 V 50 123 62 124 255 283 118 FCSD 16 V 50 135 112 174 290...

Страница 124: ...G H FCSD 08 P 680 582 280 627 112 174 290 318 FCSD H 12 P 830 730 344 775 84 149 260 288 FCSD H 20 P 980 830 487 875 106 177 290 318 Model I J K L M N O FCSD 06 08 P 118 110 50 162 174 100 50 FCSD H 1...

Страница 125: ...1 Model A B C D E F G H FCSD 09 P 680 1240 1145 585 750 630 100 520 FCSD 16 P 680 1240 1145 585 750 630 100 520 Model I J K L M N O P FCSD 09 P 70 86 62 124 255 283 118 50 FCSD 16 P 70 110 112 174 290...

Страница 126: ...42 9 45 9 50 2 52 0 315 0 Hz 47 8 40 8 32 6 38 1 34 7 36 0 45 5 46 3 48 4 56 4 55 1 56 6 400 0 Hz 53 5 39 1 27 0 30 4 28 6 37 5 40 7 43 6 49 1 50 2 52 3 55 1 500 0 Hz 43 7 39 9 29 7 33 7 34 0 40 5 39...

Страница 127: ...15 0 Hz 49 5 39 3 16 5 15 8 15 7 19 5 28 2 34 2 40 4 43 9 46 6 49 5 52 6 400 0 Hz 50 3 37 0 21 5 17 5 23 0 22 6 27 0 32 8 37 4 41 1 45 7 50 3 51 8 500 0 Hz 51 6 39 0 25 4 25 4 28 0 25 0 32 1 37 4 39 6...

Страница 128: ...9 55 0 60 2 315 0 Hz 55 1 43 5 35 8 31 2 33 2 35 0 39 9 43 9 47 7 50 7 53 9 56 9 400 0 Hz 51 5 42 7 37 8 28 1 31 6 39 9 49 2 43 9 47 3 50 9 54 5 62 2 500 0 Hz 56 1 47 7 31 4 23 0 26 0 35 6 40 2 47 1 5...

Страница 129: ...7 5 315 0 Hz 59 4 50 5 38 2 27 7 28 4 36 8 43 1 49 7 51 7 55 0 56 9 58 7 400 0 Hz 56 9 49 6 35 0 23 4 26 0 35 0 42 4 46 8 49 8 53 6 56 5 58 4 500 0 Hz 54 0 46 3 31 3 20 0 23 0 30 9 38 5 44 8 48 7 51 3...

Страница 130: ...3 29 8 28 7 33 3 41 44 5 45 9 48 9 53 2 55 315 Hz 50 8 43 8 35 6 41 1 37 7 39 48 5 49 3 51 4 59 4 58 1 59 6 400 Hz 56 5 42 1 30 33 4 31 6 40 5 43 7 46 6 52 1 53 2 55 3 58 1 500 Hz 46 7 42 9 32 7 36 7...

Страница 131: ...5 43 6 46 4 50 6 54 5 315 Hz 53 5 43 3 20 5 19 8 19 7 23 5 32 2 38 2 44 4 47 9 50 6 53 5 56 6 400 Hz 54 3 41 25 5 21 5 27 26 6 31 36 8 41 4 45 1 49 7 54 3 55 8 500 Hz 55 6 43 29 4 29 4 32 29 36 1 41...

Страница 132: ...dy Differential Pressure Chart Valve Code valve body ON OFF thermoelectric actuator Valve Body Dimensions mm DN A B C D SGS14HFCA 23010101 D20 G3 4 56 47 22 63 Valve Code valve body ON OFF thermoelect...

Страница 133: ...DR 16 24B DR 15B 24B Normal closed Normal closed Normal closed Voltage 230Vac 24Vac 24Vac Working force 90 125N 90 125N 90 125N Time 4 5min 4 5min 4 5min Power 3W 3W 3W Full stroke 3 5mm 3 5mm 5 0mm...

Страница 134: ...ervicing fan coil unit should be performed by qualified service personnel only This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities...

Страница 135: ...ompatibility Optional and standard accessories supplied with the unit are dependent on control configuration type Control Configuration Type Accessory list S1 Complete function on board PCB with integ...

Страница 136: ...r diverting a small part of the treated air into a neighboring room They must be installed in such a way as to enable treated air to circulate throughout the room and allow the minimum distances requi...

Страница 137: ...ly the best louver position is the one which allows air diffusion along the ceiling Alternative positions can be selected Confirm sufficient space is provided to allow removal of panels from the ceili...

Страница 138: ...n Installation 1 Align the two screw holes in the fixing plate to the two holes in the external drain pan Figure B 8 1 and B 8 2 2 Make sure the drain pan is horizontal 3 Tighten the two screws while...

Страница 139: ...state actuation 230VAC2 way and 3 way modulating valves thermoelectric or electric motor driven actuation with modulating state actuation W Valve control requires external wired thermostat See thermo...

Страница 140: ...Page 28 of 77 SK2019 FCSD H V P ECM 001 For 2 pipe system with modulating valve For 4 pipe systems with modulating valve...

Страница 141: ...per connection Maximum 2 fresh air connections per unit are allowed 1 The corners of the cassette allow separate ductwork to be installed for outside air intake Figure B 10 1 2 Cut and remove thermal...

Страница 142: ...Page 30 of 77 SK2019 FCSD H V P ECM 001 Figure B 10 4 Figure B 10 5 Fresh Air Flange dimension All dimensions shown in mm...

Страница 143: ...or corrugated aluminum externally insulated Branch duct flange and blanking plates are available as separate accessories items Figure B 11 1 Figure B 11 2 Installation Procedures 1 Look for the yello...

Страница 144: ...ing Using installation template remove and or modify ceiling panels and install the suspension bolts as in the images below FCSD 03 04 06 08 08R2 600 x 600 Dimensions for opening 622 x 280 Suspension...

Страница 145: ...33 of 77 SK2019 FCSD H V P ECM 001 FCSD H 09 10 12 750 750 Dimensions for opening 345 762 Suspension Bolts FCSD H 16 18 20 850 850 Dimensions for opening 485 863 Suspension Bolts All dimensions shown...

Страница 146: ...move some T bars if necessary to achieve enough clearance 4 Line up the unit to the supporting bars of the ceiling by tightening the nuts and counter nuts of the suspension rods 5 After connecting the...

Страница 147: ...Page 35 of 77 SK2019 FCSD H V P ECM 001 For Twin Fan Unit Clearance between the unit and ceiling MODEL All twin fan models Clearance 3mm...

Страница 148: ...Wiring Procedures 1 Open the terminal block cover by removing the 4 screws 2 Connect power cable to the terminal according to the wiring diagram 3 Connect room temperature sensor and coil temperature...

Страница 149: ...4 3 Start Up The unit should not be started up until the system piping has been cleaned and all the air has been purged Check condensate drain pipe slope Confirm the condensate drain pump in good work...

Страница 150: ...ng the unit Clean or replace the air filters Check and remove any obstruction from the external drain pan and the internal drain pan Extra Maintenance The electrical panel is easily accessible by remo...

Страница 151: ...ed by the red line Step 2 Operate the air vent and water purge valve by turning the knobs Fan Speed Customization Step 1 Remove grille to access the connection wires area Step 2 Remove the 4 screws of...

Страница 152: ...abeled LF MF HF may be rewired to any of the 5 input terminals for Motor labeled 1 2 3 4 5 ONE PCB output wire to ONE motor input terminal Motor and Fan Blower Replacement Refer to Section C 5 for Ste...

Страница 153: ...s shown above Step 6 Remove the drain pan and internal drain pan Step 7 Remove the pump kit including Drain pump and Float switch and replace it Control Box Replacement Refer to Section C 5 for Steps...

Страница 154: ...r to Section C 7 for Steps 1 to 6 Step 7 Snap the insulated ring of the electric heater to the electric heater mounting Step 8 Plug in the connector of electric heater REMARKS If the cassette is insta...

Страница 155: ...he PCB and all the loads connected to the voltage outputs Earth PE1 Power supply to the PCB and all the loads connected to the voltage outputs Voltage output Fan 1 CN4 Fan 1 driver and motor connectio...

Страница 156: ...1 ON L N Power supply VALVE1 230V on off valve output VALVE2 230V on off valve output WP 230V condensate pump output AUX1 Voltage free contact ON unit in heating mode AUX2 Voltage free contact ON unit...

Страница 157: ...r LED display IR receiver chilled hot water Ti2 hot water louver stepping moter connections CN2 A B A B S1 S2 FLOAT EH2 EH1 PR2 PR1 AUX2 AUX1 HF MF LF VALVE1VALVE2 WP CONNECT GY RD WH BK BL PUMP L1 N...

Страница 158: ...EH functioning as booster SW7 1 Cooling mode only available Master Slave setting SW6 1 Master SW6 0 Slave Preheat temperature setting SW4 1 28 C SW4 0 36 C 230VAC on off valve setting SW3 1 With valve...

Страница 159: ...essation of power supply The restored parameter data set depends on the type of user interface a Handset only user interface When the power ON signal is received by the fan coil unit and no wired wall...

Страница 160: ...djusted to low medium and high HEAT MODE Heat mode without electrical heater a MTV2 AUX2 and electric heater are always off b If Tr Ts 1 C or 4 C if economy contact is activated then heat operation is...

Страница 161: ...Pre heat with electrical heater a If the indoor fan speed at Modbus 310000 setting then the electrical heater will turn on POST HEAT Post heat without electrical heater a If Ti1 38 C then MTV1 and AU...

Страница 162: ...ing cycle until the user changes the mode manually or restarts the unit Should the Ti1 sensor be damaged auto mode will not function Auto heat with electric heater as primary heat source all configura...

Страница 163: ...ys off b If Tr Ts 1 C or 4 C if economy contact is activated then heat operation is activated and AUX1 is turned on Indoor fan runs at the set speed c If Tr Ts then heat operation is terminated and AU...

Страница 164: ...rned off b Indoor fan speed can be adjusted to low medium and high HEAT MODE Without Electrical Heater a MTV1 AUX2 and are heater always off b If Tr Ts 1 C or 4 C if economy contact is activated then...

Страница 165: ...rned off indoor fan remains on and runs at high speed b If Ti2 70 C then MTV2 and AUX1 are turned on indoor fan remains on and runs at set speed c If the indoor coil temperature sensor is damaged then...

Страница 166: ...lated according to the difference between the room temperature and the set temperature The controller adjusts the motor signal input from 0 to 5VDC by PID calculation every 10 seconds The air flow is...

Страница 167: ...There are no timer and sleep modes d Master unit that does not use a wall pad will globally broadcast Drain Pump Drain pump turns ON if the unit is turned on in cooling or dehumidification mode It re...

Страница 168: ...witch is opened 3 times within 60 minutes the heater is not allowed to start anymore Turn off the unit to reset the fault provided that the switch has returned to the closed position Low Temperature P...

Страница 169: ...ct or not Indoor coil sensor 1 failure Green LED blinks 4 times stops for 3s Ti1 sensor unplugged or damaged 1 Check if Ti1 plug is connected or not 2 Check if sensor s resistance is correct or not In...

Страница 170: ...stops for 3s Check unit 15 communication plug and fix it Unit 16 failure RED LED blinks 16 times stops for 3s Check unit 16 communication plug and fix it Unit 17 failure RED LED blinks 17 times stops...

Страница 171: ...ntrol Handset to Set Master Control Unit 1 Connect all the units PCBs according to the wire color and type of connector 2 Select the master unit by setting DIPA S1 SW6 to ON 1 in the PCB 3 Ensure the...

Страница 172: ...Communication plug A B A B is printed on the main PCB When you connect the wires please ensure connection of A to A and B to B 3 Connection wire i If the total length of wire is more than 1000m pleas...

Страница 173: ...ire contact by using a multimeter 3 Check 1 and 2 3 and 4 5 and 6 to be sure the connections are correct 4 If the resistance between two wire contacts is too high please check and reconnect the wire c...

Страница 174: ...SW5 DIPA S1 SW4 DIPA S1 SW3 DIPA S1 SW2 DIPA S1 SW1 Unit No Remark 1 0 0 0 0 0 01 Master 0 0 0 0 0 1 02 Slave 0 0 0 0 1 0 03 Slave 0 0 0 0 1 1 04 Slave 0 0 0 1 0 0 05 Slave 0 0 0 1 0 1 06 Slave 0 0 0...

Страница 175: ...e used to test unit Valid Error code table Error code Description Definition 01 01H Invalid commands Received commands beyond valid commands 02 02H Invalid data address Data addresses beyond valid dat...

Страница 176: ...set timer function Minute 300008 W Calibration wired wall pad and set timer function Second 300009 W Calibration wired wall pad and set timer function Hours in Timer on 300010 R W Timer ON Minute in...

Страница 177: ...heater failure Bit8 Motor1 Error Bit9 Motor2 Error Bit10 System parameters error Bit11 Anti frozen error Bit12 Reserved Bit13 Reserved Bit14 Reserved Bit15 Reserved Fan speed status 400006 R Low 04 H...

Страница 178: ...to the PCB Neutral N1 N2 Earth GND Signal Input Modulating signal Low voltage modulating signal input standard 0 5VDC S1 Open optional 0 10VDC S1 Closed Digital input Programming interface TTL Low vol...

Страница 179: ...are N com m on to therm astat custom er care M ax speed M ed speed Low speed Alarm signal EC W 1 Unit wiring schem e CN1 ALARM G Y RD G R S1 PUM P N2 N1 L1 BL RD W H BR O R BK BL YL GR RD RD O R BR YL...

Страница 180: ...pump turns OFF b When the unit turns OFF the drain pump will remain ON for 5 minutes and then turn OFF c At any time i If the float switch is OPEN the drain pump will turn ON ii If the float switch i...

Страница 181: ...Ti1 sensor connection is not good or damaged 1 Check if Ti1 plug is connected or not 2 Check sensor s resistor is good or not Water pump failure Green LED blinks 7 times stops for 3s Float switch is o...

Страница 182: ...unit its settings are automatically sent to the slave units Auto Cool Heat operation will be applicable in 4 pipe system only Swing function is not applicable European version only uses degree C setti...

Страница 183: ...77 SK2019 FCSD H V P ECM 001 Wired Wall Pad Controller Day display Mode display Temperature display Fan speed display Timer display Real Time display Master Slave Button display Network icon Sleep ico...

Страница 184: ...ON OFF timer settings for each day of the week Press twice to enter Timer setting interface and timer icon is on When ON blinks press to set timer date from Monday to Sunday Press to set hour and min...

Страница 185: ...slave units Press four times to set network control and Network icon is on The slave unit number is blinking in real time display area Press or to select slave unit which is online The offline slave...

Страница 186: ...ch setting C3 Indoor coil 2 temperature 14 Error codes When unit error is detected unit number blinks on real time hour area and Error code blinks on real time minute area The Error codes display alte...

Страница 187: ...18 84 5 88 11 91 85 16 14 69 15 05 15 41 17 79 8 83 17 86 64 17 14 03 14 37 14 7 16 75 39 78 53 81 76 18 13 41 13 72 14 03 15 71 26 74 18 77 19 19 12 81 13 1 13 4 14 67 37 70 1 72 9 20 12 24 12 52 12...

Страница 188: ...0 9284 0 9697 1 012 52 3 225 3 326 3 43 89 0 8998 0 9401 0 9818 53 3 105 3 204 3 305 90 0 8721 0 9115 0 9522 54 2 99 3 086 3 185 91 0 8455 0 8839 0 9237 55 2 88 2 974 3 07 92 0 8198 0 8573 0 8961 56 2...

Страница 189: ...ge Check fuse on board Place in the ON position Check the room control Check fan motor Filter clogged Air flow obstructed Room control regulation Incorrect water temperature Air present Insufficient o...

Страница 190: ...SK2019 FCSD H V P ECM 001...

Страница 191: ...Page 1 of 59 SK2015 FMCD V EC 001 FMCD ECM MOTOR...

Страница 192: ...ards and performance we manage every stage in the manufacturing of our products Throughout the production process we maintain strict control starting with our extensive resources in research and devel...

Страница 193: ...CONTROL SPECIFICATIONS 19 D SK NCSWC 001 COMPLETE FUNCTION FCU CONTROLLER 19 D 1 D 1 1 Abbreviations 19 D 1 2 Definition of Input Output 19 D 1 3 Wiring Diagram SK NCSWC 001 20 D 1 4 Configuration Se...

Страница 194: ...EC 001 REMOTE CONTROL HANDSET 50 E 1 WIRED WALL PAD 51 E 2 E 2 1 Wall Pad Display 51 E 2 2 Wall Pad Operation Guidelines 52 E 2 3 EC unit RPM setting 55 SENSOR RESISTANCE R T CONVERSION TABLE 56 E 3 T...

Страница 195: ...omplete function onboard PCB with integrated group control functionality W Limited function onboard PCB with drain pump louver and zone control functionality V 2 Pipe System 04 See General Specificati...

Страница 196: ...cated on the front of the unit can be unsnapped allowing the filter to be easily slid downward and removed No tools are required nor any dismantling of the equipment Air Grille Distribution all units...

Страница 197: ...city 1 FCCOPe Rating 164 43 166 46 245 83 220 72 Class B B B B Sound Sound PressureLevel Outlet dB A 31 26 24 39 31 26 40 33 28 45 34 31 Sound Power Level Outlet e 40 35 33 48 40 35 49 42 37 54 43 40...

Страница 198: ...B B B C Soun d Sound PressureLevel Outlet dB A 49 44 37 43 39 36 47 43 37 50 47 40 Sound Power Level Outlet e 58 53 46 52 48 45 56 52 46 59 56 49 Electrical Fan Motor Powere H W 30 30 40 50 M 26 20 3...

Страница 199: ...Fin Length mm Fins per Inch No of Rows No of Copper No of Circuits Tube Diameter mm FMCD 04 230 680 19 5 2 8 2 7 FMCD 06 230 680 2 14 3 7 FMCD 12 230 680 2 22 4 7 FMCD 15 230 680 2 22 4 7 FMCD 18 357...

Страница 200: ...06 12 15 18 ECM Model Unit Dimensions mm A B C D E F G H FMCD 04 06 12 15 18 40 105 875 55 105 R20 60 74 All dimensionsshown in mm Model Unit Dimensions mm a b c d e f g h FMCD 04 06 12 15 18 200 55...

Страница 201: ...D 20 24 30 ECM Model Unit Dimensions mm A B C D E F G FMCD 20 24 30 90 1050 51 90 15 73 74 Model Unit Dimensions mm 1 2 3 4 FMCD 20 24 30 855 155 820 175 All dimensionsshown in mm Model Unit Dimension...

Страница 202: ...Page 12 of 59 SK2015 SWC V EC 001 Valve Information B 4 B 4 1 2 Way Valve Body Valve Dimensions mm DN A B C D D15 G1 2 52 47 19 5 63...

Страница 203: ...re the clearance around the fan coil unit conforms to the following drawing 5 From the floor the height of the unit should be above eye level 6 Avoid installing the unit in direct sunlight Required cl...

Страница 204: ...Page 14 of 59 SK2015 SWC V EC 001 C 1 2 Mounting Plate Dimensions FMCD 04 06 12 15 18 ECM FMCD 20 24 30 ECM All dimensions shown in mm...

Страница 205: ...bove figure or by means of gradiometer Failure to follow this may cause water to drip indoors and create atypical noise 4 Fix the mounting plate by means of expansion screws or tapping screws C 1 4 Dr...

Страница 206: ...the hooks of the mounting plate C 1 6 Drainage Piping Works 1 Install the drain hose so that it slopes downward slightly for free drainage Avoid installing it as shown in the below illustrations marke...

Страница 207: ...rasp the lower part of the front cover and pull the entire assembly out and up towards you C 2 3 Air Purging 1 After connecting the water inlet and outlet pipes to the main supply lines turn on the ma...

Страница 208: ...Page 18 of 59 SK2015 SWC V EC 001 Pipe Connections with Valve C 3 Pre assembly Complete Assembly Flexible hose Valve body with actuator gasket Coil connector...

Страница 209: ...witch EH Voltage free NC The contact is closed before the EH is turned on Power input Phase L1 Power supply to the PCB and all the loads connected to the voltage outputs Max length 5 m Neutral N1 Powe...

Страница 210: ...Page 20 of 59 SK2015 SWC V EC 001 D 1 3 Wiring Diagram SK NCSWC 001...

Страница 211: ...pipe 4 pipe configuration selection SW3 Thermoelectric valve configuration selection 2 pipe system only SW4 Pre heat protection temperature selection SW5 SW6 brushless DC fan motor configuration Defa...

Страница 212: ...el SW7 SW8 Model setting 0 0 Cool Heat 0 1 Cool Heat booster heater 1 0 Cooling only 1 1 Cool primary heater 7 Air Conditioner ON OFF There are 3 ways to turn the system on or off a By the ON OFF butt...

Страница 213: ...urned off b Indoor fan speed can be adjusted to low medium and high HEAT MODE Without Electrical Heater a MTV2 AUX2 and electric heater are always off b If Tr Ts 1 C or 4 C if economy contact is activ...

Страница 214: ...38 C or 30 C is selected by DIPB S2 position SW4 then MTV1 and AUX1 are turned on indoor fan runs at set speed c If the indoor coil temperature sensor is damaged then the pre heat time is set for 2 mi...

Страница 215: ...cording to the following i If the coil temperature sensor Ti1 36 C then MTV1 AUX1 and fan turn on or off according to HEAT mode ii If Ti1 36 C then MTV1 AUX2 and fan turn on or off according to COOL m...

Страница 216: ...speed while heater AUX1 AUX2 MTV1 and MTV2 are turned off b Indoor fan speed can be adjusted to low medium and high HEAT MODE Without electrical heater a MTV1 MTV2 AUX2 and heater are always off b If...

Страница 217: ...speed If indoor fan runs at medium or high speed then it will run at set speed b If Ti1 5 C for 2 minutes then AUX2 is turned on Indoor fan runs at set speed OVER HEAT PROTECTION OF INDOOR COIL a If T...

Страница 218: ...if economy contact is activated then heat operation is activated and MTV2 and AUX1 are turned on Indoor fan runs at the set speed c If Tr Ts then heat operation is terminated and MTV2 and AUX1 are tur...

Страница 219: ...it has been turned off for 20 seconds LOW TEMPERATURE PROTECTION OF INDOOR COIL a If Ti1 2 C for 2 minutes then MTV1 and AUX2 are turned off If indoor fan is set for low speed then it will run at medi...

Страница 220: ...ote AUTO COOL or AUTO HEAT operations are the same as COOL or HEAT mode respectively SLEEP MODE a SLEEP mode can only be set when the unit is in COOL or HEAT mode b In COOL mode after SLEEP mode is se...

Страница 221: ...Auto Fan Speed a In COOL mode the fan speed cannot change until it has run for more than 30 seconds Fan speed is regulated according to the profile below b In HEAT mode the fan speed cannot change un...

Страница 222: ...mperature Swing and Fan Speed when using a wall pad parameters are Mode Set Temperature Swing and Fan Speed as well as the 7 day ON OFF Timer program D 1 11 Operation Of Control Panel On High Wall Uni...

Страница 223: ...Page 33 of 59 SK2015 SWC V EC 001 LED lights D 2 For all units Power Operation LED light both green Unit on Operation LED On Power LED Off Unit in standby Power LED On Operation LED Off...

Страница 224: ...n LED blinks 3 times stops for 3s Room sensor unplugged or damaged 1 Check if Tr plug is connected or not 2 Check if sensor s resistance is correct or not Indoor coil sensor 1 failure Green LED blinks...

Страница 225: ...ks 15 times stops for 3s Check unit 15 communication plug and fix it Unit 16 failure RED LED blinks 16 times stops for 3s Check unit 16 communication plug and fix it Unit 17 failure RED LED blinks 17...

Страница 226: ...operation c The master unit settings are unit ON OFF Mode Fan Speed Timer Clock Set Temperature Swing Function and Sleep Function for wall pad operation SLAVE UNIT FUNCTION a The slave unit receives...

Страница 227: ...Communication plug A B A B is printed on the main PCB When you connect the wires please ensure connection of A to A and B to B 3 Connection wire i If the total length of wire is more than 1000m pleas...

Страница 228: ...correspond 2 Check the wire contact by using a multimeter 3 Check 1 and 2 3 and 4 5 and 6 to be sure the connections are correct 4 If the resistance between two wire contacts is too high please check...

Страница 229: ...ep once Using Wall pad to Set Master Control Unit a Connect all the units PCBs according to the wire color and type of connector b Select the master unit by setting DIPA S1 SW6 to ON 1 in the PCB c En...

Страница 230: ...W5 DIPA S1 SW4 DIPA S1 SW3 DIPA S1 SW2 DIPA S1 SW1 Unit No Remark 1 0 0 0 0 0 01 Master 0 0 0 0 0 1 02 Slave 0 0 0 0 1 0 03 Slave 0 0 0 0 1 1 04 Slave 0 0 0 1 0 0 05 Slave 0 0 0 1 0 1 06 Slave 0 0 0 1...

Страница 231: ...Page 41 of 59 SK2015 SWC V EC 001 D 3 4 Unit Network Wiring Scheme Wiring diagram for a master slave network connection...

Страница 232: ...unit is turned off R 2 Med R 3 Hi Power input Phase L Power supply to the PCB and all the loads connected to the voltage outputs Max length 5 m Neutral N Power supply to the PCB and all the loads con...

Страница 233: ...Page 43 of 59 SK2015 SWC V EC 001 D 4 2 Wiring diagram SK NCSWC 002...

Страница 234: ...Code State Description SW1 0 PCB configured for 0 5VDC modulating signal input 1 PCB configured for 0 10VDC modulating signal input MODEL SW2 SW3 SW4 Hi Med Low FMCD 04 0 0 0 700 600 500 FMCD 06 0 0...

Страница 235: ...runs at 200 RPM EC motor RPM will be changed by the signal voltage D 4 5 LED Indication For all units Power Operation LED light both green Unit on Operation LED On Power LED Off Unit in standby Power...

Страница 236: ...ead Coils 02 02H Read Discrete Inputs 03 03H Read Holding Registers 04 04H Read Input Registers 05 05H Write Single Coil 06 06H Write Single Register 15 0FH Write Multiple Coils 16 10H Write Multiple...

Страница 237: ...Reserved 100011 Reserved 100012 Reserved 100013 Reserved 100014 Reserved 100015 R read only W write only R W read and write Discrete table Description Address Type Remark MTV1 200000 R MTV2 200001 R A...

Страница 238: ...libration wired wall pad and set timer function Minute 300008 W Calibration wired wall pad and set timer function Second 300009 W Calibration wired wall pad and set timer function Hours in Timer on 30...

Страница 239: ...erved Bit7 Electrical heater failure Bit8 Motor1 Error Bit9 Motor2 Error Bit10 System parameters error Bit11 Reserved Bit12 Reserved Bit13 Reserved Bit14 Reserved Bit15 Reserved Fan speed status 40000...

Страница 240: ...1 Attention When unit with handset is the master unit its settings are automatically sent to the slave units Auto Cool Heat operation will be applicable in 4 pipe system only Swing function is not app...

Страница 241: ...board model automatically whether it is 2 pipe or 4 pipe system b Auto Cool Heat operation is applicable in 4 pipe system only c When the wall pad is installed the wall pad temperature sensor automat...

Страница 242: ...will show Press DAY button to change the day the ON timer is to be programmed for 2 Press TIMER button again and O FF symbol blinking indicates OFF timer programming mode The setting method is the sa...

Страница 243: ...unit is as follows Press TIME and TIME buttons for 3 seconds to activate clock synchronization in all slave units Master wall pad will respond with a beeping sound f Key lock In order to prevent unaut...

Страница 244: ...onds to enter into operation parameters browsing mode Unit display area shows the address of the slave unit being viewed Slave unit selection method is the same as in networking control above Press or...

Страница 245: ...ed wall pad LED will display the following 5 To complete the RPM setting turn the DIP switch 1 to OFF position The wired wall pad display will resume its normal appearance This is the motor RPM settin...

Страница 246: ...84 5 88 11 91 85 16 14 69 15 05 15 41 17 79 8 83 17 86 64 17 14 03 14 37 14 7 16 75 39 78 53 81 76 18 13 41 13 72 14 03 15 71 26 74 18 77 19 19 12 81 13 1 13 4 14 67 37 70 1 72 9 20 12 24 12 52 12 79...

Страница 247: ...326 3 43 89 0 8998 0 9401 0 9818 53 3 105 3 204 3 305 90 0 8721 0 9115 0 9522 54 2 99 3 086 3 185 91 0 8455 0 8839 0 9237 55 2 88 2 974 3 07 92 0 8198 0 8573 0 8961 56 2 774 2 866 2 959 93 0 795 0 831...

Страница 248: ...Page 58 of 59 SK2015 SWC V EC 001 Troubleshooting Guide E 4...

Страница 249: ...Page 59 of 59 SK2015 SWC V EC 001...

Страница 250: ...FSTD C V P ECM MOTOR...

Страница 251: ...st standards and performance we manage every stage in the manufacturing of our products Throughout the production process we maintain strict control starting with our extensive resources in research a...

Страница 252: ...y Maintenance 25 B 2 3 Filter Installation Cleaning 25 B 2 4 Fan Motor Assembly Maintenance 26 C CONTROL SPECIFICATIONS SK NCPFWB 001 ECM S CONFIGURATION FULL CONTROL PCB 27 C 1 I O PORT DEFINITIONS 2...

Страница 253: ...5 1 Unit Power ON OFF 59 E 5 2 Alarm Protection and Error Display 59 E 5 3 Drain Pump Run Management 59 E 5 4 Swing and Louver Control 59 E 5 5 Modulating Signal Input 59 E 6 LED INDICATION AND ERROR...

Страница 254: ...zes See General Specification section A for cooling and heating capacities FSTD Universal Uncased Unit FSTDC 06 V S VAR ECM ECM EC Motor Configuration VAR Vertical air return HAR Horizontal air return...

Страница 255: ...access to control planet HEAT EXCHANGER The heat exchanger is a highly efficient coil in which copper pipes and aluminum fins are fixed by mechanical expansion Coil connections are provided with an an...

Страница 256: ...Page 7 of 73 SK2015 FSTDC V P ECM 001 A 2 Unit Appearance FSTDC VAR FSTDC HAR FSTD...

Страница 257: ...1 94 2 51 3 15 4 48 4 93 L 1 1 4 2 3 2 72 3 97 4 23 Max Electric Heater Capacity 1 1 5 2 2 2 FCCOP e Rating 161 24 160 24 160 17 171 5 121 78 Class B B B B D Sound Sound Pressure Level Outlet dB A 38...

Страница 258: ...34 10 4 L 1 5 71 6 97 7 74 9 49 Max Electric Heater Capacity 3 3 3 3 FCCOP e Rating 126 94 115 66 103 3 94 89 Class C C D D Soun d Sound Pressure Level Outlet dB A 47 45 43 48 46 44 50 48 46 52 50 48...

Страница 259: ...Capacity H 3 kW 2 50 3 59 4 67 5 70 7 18 M 2 2 17 3 19 4 02 4 91 6 33 L 1 1 64 2 63 3 44 4 34 5 38 Max Electric Heater Capacity 1 1 5 2 2 2 FCCOP Rating 187 16 189 76 203 15 189 21 155 31 Class B B B...

Страница 260: ...ng Heating Capacity H 3 kW 9 45 11 03 13 34 14 28 M 2 8 49 10 31 12 18 13 44 L 1 7 39 9 03 10 02 12 29 Max Electric Heater Capacity 3 3 3 3 FCCOP Rating 164 58 150 00 133 66 122 84 Class B C C C Soun...

Страница 261: ...g Water Flow Rate 3 2 1 3 L h 137 190 250 306 378 2 121 171 219 268 337 1 95 145 192 241 293 Heating Pressure Drop 3 kPa 4 09 7 72 14 9 24 6 37 2 2 3 3 6 46 11 8 19 5 30 6 1 2 15 4 81 9 36 16 1 23 8 W...

Страница 262: ...Model Fin height mm Fin Length mm Fins per Inch No of Rows Fin width mm No of Circuits Tube mm FSTD C 06 200 441 12 7 4 88 3 9 52 FSTD C 09 491 3 FSTD C 12 641 4 FSTD C 15 791 4 FSTD C 18 841 4 FSTD C...

Страница 263: ...134 52 112 5 50 FSTD 12 778 808 270 230 223 460 57 134 52 112 5 50 FSTD 15 928 958 270 230 223 460 57 134 52 112 5 50 FSTD 18 978 1008 270 230 223 460 57 134 52 112 5 50 FSTD 24 1478 1508 270 230 223...

Страница 264: ...0 235 484 494 57 134 52 112 5 242 50 FSTDC 15 1208 928 958 270 250 235 484 494 57 134 52 112 5 242 50 FSTDC 18 1258 978 1008 270 250 235 484 494 57 134 52 112 5 242 50 FSTDC 24 1758 1478 1508 270 250...

Страница 265: ...lve Dimensions mm DN A B C D SK DFPS A 003c D20 G3 4 56 47 22 63 A 6 Valve Information A 6 1 2 Way 3 4 Valve Body A 6 2 3 Way 3 4 Valve Body Differential Pressure Chart Valve Model Valve Dimensions mm...

Страница 266: ...alve Model Valve Dimensions mm DN A B C D SK DFPS A 003a D15 G1 2 52 47 19 5 63 A 6 3 2 Way 1 2 Valve Body A 6 4 3 Way 1 2 Valve Body Differential Pressure Chart Valve Model Valve Dimensions mm DN A B...

Страница 267: ...servicing air conditioning equipment should be done by qualified service personnel only This appliance is not intended for use by persons including children with reduced physical sensory or mental ca...

Страница 268: ...n should allow the treated air to circulate freely throughout the room and leave sufficient space to access the unit in order to carry out maintenance or servicing operations FOR FLOOR FREE STANDING 1...

Страница 269: ...ges and brackets see the dimensional data 4 Complete the hydraulic connection and check for leakage 5 Complete the electrical connection as shown in the wiring diagrams Make electrical connection as s...

Страница 270: ...Manual bleeds 4 Joint 5 Ball on off valve Attach the connections by tightening the fan coil fitting using 2 wrenches CONDENSATE DRAINAGE For use in air conditioning systems the fan coils are fitted w...

Страница 271: ...ght Side Connection Step 1 Remove the front panel Step 2 Remove 2 screws on the coil s metal plate Step 3 Remove 8 screws from both sides of the coil then take out coil Step 4 Change the coil directio...

Страница 272: ...B 1 5 Valve and External drain pan Installation Horizontal type Piping for 2 Pipe System Piping for 4 Pipe System 3 Way 4 Outlet Valve 3 4 3 Way 4 Outlet Valve 3 4 for Cooling Coil 3 Way 4 Outlet Val...

Страница 273: ...nto forced drainage by attaching the condensate drain pump available as an accessory Cold Water Outlet 3 4 Cold Water Inlet 3 4 Hot Water Inlet 1 2 Vertical Drain Pan 3 Way 4 Outlet Valve 3 4 for Cool...

Страница 274: ...nt They can be brushed with a soft brush or vacuumed with a vacuum cleaner 6 If the water coil is not being used during the winter season it should be drained or an anti freezing solution should be ad...

Страница 275: ...P ECM 001 B 2 4 Fan Motor Assembly Maintenance Step 1 Remove the front panel Step 2 Loosen 6 screws on both sides of the fan deck then remove Step 3 Once finished with maintenance put the fan motor a...

Страница 276: ...ts for remote activation of economy mode when DIPB SW1 0 Float switch Float Voltage free NC Electrical heater safety switch EH Voltage free NC The contact is closed before the EH is turned on Power in...

Страница 277: ...of the connection please make sure max wiring length 30 m Serial BUS port CN3 Master slave network serial connection OR MODBUS local PC host network serial connection 24VAC power input DA1 24VAC exte...

Страница 278: ...Page 29 of 73 SK2015 FSTDC V P ECM 001 C 2 Wiring Diagram SK NCPFWB 001 ECM S Configuration Full Control PCB...

Страница 279: ...WP CN1 2 CN3 CN4 CN5 CN6 CN7 S1 S2 5 6 PR O RS485 CPU PR O AUX2 AUX2 AUX1 AUX1 N pump electrical heating 30A heating value cooling value low speed medial speed high speed VALVE1 VALVE2 N HF LF MF N ON...

Страница 280: ...e only available SW8 0 SW7 1 Cooling and heating modes available SW8 1 with EH functioning as primary Master Slave setting SW6 1 Master SW6 0 Slave Preheat temperature setting SW4 1 28 o C SW4 0 36 o...

Страница 281: ...f power supply The restored parameter data set depends on the type of user interface a Handset only user interface When the power ON signal is received by the air conditioner and no wired wall pad is...

Страница 282: ...re turned on Indoor fan runs at the set speed c If Tr Ts then heat operation is terminated and MTV1 and AUX1 are turned off Indoor fan runs at 200rpm d The range of Ts is 16 30 C e Indoor fan speed ca...

Страница 283: ...MTV1 and AUX1 are turned off Then indoor fan maintains its original state c If Ti1 36 C then MTV1 and AUX1 are turned off Then indoor fan runs at 200rpm d If the indoor coil temperature sensor is dama...

Страница 284: ...ng cycle until the user changes the mode manually or restarts the unit Should the Ti1 sensor be damaged auto mode will not function Auto heat with electric heater as primary heat source all configurat...

Страница 285: ...ical heater a MTV1 MTV2 AUX2 and heater are always off b If Tr Ts 1 C or 4 C if economy contact is activated then heat operation is activated and AUX1 is turned on Indoor fan runs at the set speed c I...

Страница 286: ...rding to the pre heat and post heat program DEHUMIDIFICATION MODE a MTV1 MTV2 AUX1 and heater are always off b If Tr 25 C then indoor fan and AUX2 will be ON for 3 minutes and then OFF for 4 minutes c...

Страница 287: ...1 and AUX2 are turned off b Indoor fan speed can be adjusted to low medium and high HEAT MODE Without Electrical Heater a MTV1 AUX2 and are heater always off b If Tr Ts 1 C or 4 C if economy contact i...

Страница 288: ...oor fan remains on and runs at high speed b If Ti2 70 C then MTV2 and AUX1 are turned on indoor fan remains on and runs at set speed c If the indoor coil temperature sensor is damaged then the protect...

Страница 289: ...ncrease by 2 C over 2 hours c If the sleep mode is activated when the unit is in heat mode then the indoor fan will run at set speed and Ts will decrease by 2 C over 2 hours d Changing the mode of ope...

Страница 290: ...ing valve signal input from 0 to 10VDC by PID calculation every 10 seconds C 9 Swing Louver For remote handset with Control Box I Integrated Full Control Version Whenever the indoor fan is running the...

Страница 291: ...inutes C 14 Float Switch Float switch opens before unit is turned on If the float switch N C is opened before the unit is turned on then MTV1 is turned off The drain pump and indoor fan will operate A...

Страница 292: ...ugged or damaged 1 Check if Tr plug is connected or not 2 Check if sensor s resistance is correct or not Indoor coil sensor 1 failure Green LED blinks 4 times stops for 3s Ti1 sensor unplugged or dama...

Страница 293: ...mes stops for 3s Check unit 15 communication plug and fix it Unit 16 failure RED LED blinks 16 times stops for 3s Check unit 16 communication plug and fix it Unit 17 failure RED LED blinks 17 times st...

Страница 294: ...operation c The master unit settings are Unit ON OFF Mode Fan Speed Timer Clock Set Temperature Swing Function and Sleep Function for wall pad operation SLAVE UNIT FUNCTION a The slave unit receives...

Страница 295: ...x b Communication plug A B A B is printed on the main PCB When you connect the wires please ensure connection of A to A and B to B c Connection wire i If the total length of wire is more than 1000m pl...

Страница 296: ...correspond 2 Check the wire contact by using a multimeter 3 Check 1 and 2 3 and 4 5 and 6 to be sure the connections are correct 4 If the resistance between two wire contacts is too high please check...

Страница 297: ...beep once Using Wall pad to Set Master Control Unit a Connect all the units PCBs according to the wire color and type of connector b Select the master unit by setting DIPA S1 SW6 to ON 1 in the PCB c...

Страница 298: ...IPA S1 SW5 DIPA S1 SW4 DIPA S1 SW3 DIPA S1 SW2 DIPA S1 SW1 Unit No Remark 1 0 0 0 0 0 01 Master 0 0 0 0 0 1 02 Slave 0 0 0 0 1 0 03 Slave 0 0 0 0 1 1 04 Slave 0 0 0 1 0 0 05 Slave 0 0 0 1 0 1 06 Slave...

Страница 299: ...Read Coils 02 02H Read Discrete Inputs 03 03H Read Holding Registers 04 04H Read Input Registers 05 05H Write Single Coil 06 06H Write Single Register 15 0FH Write Multiple Coils 16 10H Write Multipl...

Страница 300: ...10 Reserved 100011 Reserved 100012 Reserved 100013 Reserved 100014 Reserved 100015 R read only W write only R W read and write Discrete table Description Address Type Remark MTV1 200000 R MTV2 200001...

Страница 301: ...Calibration wired wall pad and set timer function Minute 300008 W Calibration wired wall pad and set timer function Second 300009 W Calibration wired wall pad and set timer function Hours in Timer on...

Страница 302: ...eserved Bit7 Electrical heater failure Bit8 Motor1 Error Bit9 Motor2 Error Bit10 System parameters error Bit11 Reserved Bit12 Reserved Bit13 Reserved Bit14 Reserved Bit15 Reserved Fan speed status 400...

Страница 303: ...e input High fan speed H 230VAC input signals from wired thermostat Medium fan speed M Low fan speed L Phase L External 230VAC power supply connection to the PCB Max length 5 m Neutral N Earth GND Aut...

Страница 304: ...can be configured for different modulating signal inputs Refer to jumper configuration table below Code State Description S1 Open PCB configured for 0 5VDC modulating signal input S1 Closed PCB config...

Страница 305: ...Page 56 of 73 SK2015 FSTDC V P ECM 001 E 4 Wiring Diagrams E 4 1 Standard Unit Wiring Diagram of SK NCPFWB 002 ECM...

Страница 306: ...BL BL BL M BL RELAY RELAY BLDC EC MOTOR HV Gnd Vcc Vsp FG FLOAT float control switch for pump RELAY CPU SM1 SM2 CN2 AI1 NC CN4 X DIS TTL L M H AUTO N 0 5VDC 0 10VDC S3 closed BK YL BR OR Auto speed si...

Страница 307: ...ump RELAY CPU SM1 SM2 CN 2 AI1 NC CN4 X DIS TTL L M H AUTO N 0 10VDC S1 closed V1 V2 Lo M H N L N BL YL BR OR L N L1 phase to thermastat customer care N common to thermastat customer care 230V 50HZ Au...

Страница 308: ...ump turns OFF ii When the unit turns OFF and the drain pump is ON The drain pump will remain ON for 5 minutes and then turn OFF iii At any time a If the float switch is OPEN the drain pump will turn O...

Страница 309: ...scription Blink Reason Remedy Indoor coil sensor 1 failure Green LED blinks 4 times stops for 3s Ti1 sensor connection is not good or damaged 1 Check if Ti1 plug is connected or not 2 Check sensor s r...

Страница 310: ...Attention When unit with handset is the master unit its settings are automatically sent to the slave units Auto Cool Heat operation will be applicable in 4 pipe system only Swing function is not appli...

Страница 311: ...l automatically whether it is 2 pipe or 4 pipe system Auto Cool Heat operation is applicable in 4 pipe system only When the wall pad is installed the wall pad temperature sensor automatically override...

Страница 312: ...a will show Press DAY button to change the day the ON timer is to be programmed for Press TIMER button again and O FF symbol blinking indicates OFF timer programming mode The setting method is the sam...

Страница 313: ...TIME and TIME buttons for 3 seconds to activate clock synchronization in all slave units Master wall pad will respond with a beeping sound f Key lock In order to prevent unauthorized access to the sy...

Страница 314: ...N buttons for 3 seconds to enter into operation parameters browsing mode Unit display area shows the address of the slave unit being viewed Slave unit selection method is the same as in networking con...

Страница 315: ...tion d Wired wall pad LED will display the following e To complete the RPM setting turn the DIP switch 1 to OFF position The wired wall pad will resume its normal operation This is the motor RPM setti...

Страница 316: ...18 84 5 88 11 91 85 16 14 69 15 05 15 41 17 79 8 83 17 86 64 17 14 03 14 37 14 7 16 75 39 78 53 81 76 18 13 41 13 72 14 03 15 71 26 74 18 77 19 19 12 81 13 1 13 4 14 67 37 70 1 72 9 20 12 24 12 52 12...

Страница 317: ...0 9284 0 9697 1 012 52 3 225 3 326 3 43 89 0 8998 0 9401 0 9818 53 3 105 3 204 3 305 90 0 8721 0 9115 0 9522 54 2 99 3 086 3 185 91 0 8455 0 8839 0 9237 55 2 88 2 974 3 07 92 0 8198 0 8573 0 8961 56 2...

Страница 318: ...age Check fuse on board Place in the ON position Check the room control Check fan motor Filter clogged Air flow obstructed Room control regulation Incorrect water temperature Air present Insufficient...

Страница 319: ...5 SK DFPS DL FS 009b Auxiliary 1 row heating coil 1 16 SK DFPS DL FS 009c Auxiliary 1 row heating coil 1 17 SK DFPS DL FS 009d Auxiliary 1 row heating coil 1 18 SK DFPS DL FS 009e Auxiliary 1 row heat...

Страница 320: ...sories The electric heater module is supplied for winter heating as an alternative to the auxiliary hot water coil Electric Heater is installed in the same way and same position as the Auxiliary 1 row...

Страница 321: ...inted steel drain pan for suspended ceiling installation or built in horizontal installation with left sided coil connections SK DFPS FS 012 is a painted steel drain pan for floor standing installatio...

Страница 322: ...Page 73 of 73 SK2015 FSTDC V P ECM 001...