SK2018 GLOBAL FDLA-V/P-AC-001
D.4.2.
Without Valve Configuration
COOL MODE
a)
Electric heater, AUX1, MTV1 and MTV2 are always off.
b)
If Tr ≥ Ts + 1ºC (or + 4ºC if economy contact is activated), then cool operation is activated and AUX2 is turned on. Indoor
fan runs at set speed.
c)
If Tr < Ts, then cool operation is terminated and AUX2 is turned off. Indoor fan is turned off.
d)
The range of Ts is 16 - 30ºC
e)
Indoor fan speed can be adjusted to low, medium, high and auto.
Note: When the unit is turned off, the indoor fan shut down after 5 seconds.
LOW TEMPERATURE PROTECTION OF INDOOR COIL
a)
If Ti1 ≤
2ºC for 2 minutes, then AUX2 is turned off. If low speed is selected via user interface, then indoor fan runs at
medium speed. If medium or high speed is selected via user interface, then indoor fan runs at set speed.
b)
If Ti1 ≥ 5ºC for
2 minutes, then AUX2 is turned on. Indoor fan runs at set speed.
FAN MODE
a)
Indoor fan runs at the set speed while heater, MTV1, MTV2, AUX1 and AUX2 are turned off.
b)
Indoor fan speed can be adjusted to low, medium and high.
HEAT MODE
Heat mode without electrical heater
a)
MTV1, MTV2, AUX2 and heater are always off.
b)
If Tr ≤ Ts
- 1ºC (or - 4ºC if economy contact is activated), then heat operation is activated and AUX1 is turned on. Indoor
fan runs at the set speed.
c)
If Tr > Ts, then heat operation is terminated and AUX1 is turned off. Indoor fan repeatedly runs at low fan speed for 30
seconds and then stops for 3 minutes.
d)
The range of Ts is 16 - 30ºC.
e)
Indoor fan speed can be adjusted to low, medium, high and auto.
PRE-HEAT
Pre-heat without electrical heater
a)
MTV1, MTV2 and AUX2 are off.
b)
If Ti1 < 36 ºC [or 28 ºC depending on DIP setting], AUX1 is on while indoor fan remains off.
c)
If Ti1
≥
38 ºC [or 30 ºC depending on DIP setting], AUX1 is on while indoor fan runs at set speed.
d)
If indoor coil temperature sensor is damaged, pre-heat time is set for 2 minutes and indoor fan runs at set speed.
OVERHEAT PROTECTION OF INDOOR COIL
a)
If Ti1 ≥ 75ºC, then AUX1 is turned off, indoor fan remains on and runs at high speed.
b)
If Ti1 < 70ºC, then AUX1 is turned on, indoor fan remains on and runs at set speed.
c)
If the indoor coil temperature sensor is damaged, then the protection mode will be overridden and the unit will work
according to the pre-heat and post-heat program.
DEHUMIDIFICATION MODE
a)
MTV1, MTV2, AUX1 and heater are always off.
b)
If Tr ≥ 25ºC, then indoor fan and AUX2 will be ON for 3 minutes, and then OFF for 4 minutes.
c)
If 16ºC ≤ Tr < 25ºC, then indoor fan and AUX2 will be ON for 3 minutes, and then OFF for 6 minutes.
d)
If Tr < 16ºC, then indoor fan and AUX2 will be turned off.
e)
At the end of the above dehumidification cycle, the system will decide the next dehumidification control option. Indoor
fan will run at low speed throughout the dehumidification process.
AUTOMODE
Not available.
Содержание FDLA-09
Страница 1: ...SK2018 GLOBAL FDLA V P AC 001 FDLA V P AC MOTOR...
Страница 27: ...Page 26 of 51 SK2018 GLOBAL FDLA V P AC 001 Configuration Settings...
Страница 53: ...FDHD V P AC MOTOR...
Страница 69: ...B 1 4 4 Electrical connections T Configuration standard version...
Страница 74: ...Wiring Diagram D 2 SK NCPDWH 001b S Configuration Full Control PCB...
Страница 76: ...Configuration Settings D 3...
Страница 111: ......
Страница 112: ...SK2019 FCSD H V P ECM 001 FCSD H V P ECM MOTOR...
Страница 140: ...Page 28 of 77 SK2019 FCSD H V P ECM 001 For 2 pipe system with modulating valve For 4 pipe systems with modulating valve...
Страница 190: ...SK2019 FCSD H V P ECM 001...
Страница 191: ...Page 1 of 59 SK2015 FMCD V EC 001 FMCD ECM MOTOR...
Страница 210: ...Page 20 of 59 SK2015 SWC V EC 001 D 1 3 Wiring Diagram SK NCSWC 001...
Страница 231: ...Page 41 of 59 SK2015 SWC V EC 001 D 3 4 Unit Network Wiring Scheme Wiring diagram for a master slave network connection...
Страница 233: ...Page 43 of 59 SK2015 SWC V EC 001 D 4 2 Wiring diagram SK NCSWC 002...
Страница 248: ...Page 58 of 59 SK2015 SWC V EC 001 Troubleshooting Guide E 4...
Страница 249: ...Page 59 of 59 SK2015 SWC V EC 001...
Страница 250: ...FSTD C V P ECM MOTOR...
Страница 256: ...Page 7 of 73 SK2015 FSTDC V P ECM 001 A 2 Unit Appearance FSTDC VAR FSTDC HAR FSTD...
Страница 278: ...Page 29 of 73 SK2015 FSTDC V P ECM 001 C 2 Wiring Diagram SK NCPFWB 001 ECM S Configuration Full Control PCB...
Страница 305: ...Page 56 of 73 SK2015 FSTDC V P ECM 001 E 4 Wiring Diagrams E 4 1 Standard Unit Wiring Diagram of SK NCPFWB 002 ECM...
Страница 322: ...Page 73 of 73 SK2015 FSTDC V P ECM 001...