Cooling mode-low water temperature
The automatic setting curve
The automatic setting curve is the ninth curve,this is the calculation method:
T4
- 10
≤
T4
<
15
15
≤
T4
<
22
22
≤
T4
<
30
30
≤
T4
1- T1S
16
11
8
5
2- T1S
17
12
9
6
3- T1S
18
13
10
7
4- T1S
19
14
11
8
5- T1S
20
15
12
9
6- T1S
21
16
13
10
7- T1S
22
17
14
11
8- T1S
23
18
15
12
State:In the setting of the wired controller, if T4H2<T4H1, then exchange
their value; if T1SETH1<T1SETH2, then exchange their value.
(T1SETH1, T1SETH2,T4H1,T4H2 can be set in "FOR SERVICEMAN" .)
T1SETH1
T1SETH2
T4H1
T4H2
T1S
T4