56
221(PLC: 40222) t_DI_max
222(PLC: 40223) t_DI_hightemp
223(PLC: 40224) t_interval_C
224(PLC: 40225) dT1SC
225(PLC: 40226) dTSC
226(PLC: 40227) T4cmax
227(PLC: 40228) T4cmin
228(PLC: 40229) t_interval_H
229(PLC: 40230) dT1SH
230(PLC: 40231) dTSH
231(PLC: 40232) T4hmax
232(PLC: 40233) T4hmin
233(PLC: 40234) T4_IBH_on
234(PLC: 40235) dT1_IBH_on
235(PLC: 40236) t_IBH_delay
237(PLC: 40238) T4_AHS_on
238(PLC: 40239) dT1_AHS_on
240(PLC: 40241) t_AHS_delay
Default setting: 2°C, range: 1~10°C, setting interval: 1°C
Default setting: 25°C, range: 20~35°C, setting interval: 1°C
Default setting: -15
°
C, range: -25-30
°
C, Setting interval1
°
C
Default setting: 10°C, range: -5~25°C, setting interval: 1°C
Time interval of compressor start-up in the heating mode; range:
5~5 min, default setting: 5 min
Default setting: 5
°
C, range: 2-20
°
C;
Maximum disinfection duration, range: 90~300 min, default
setting: 210 min
Disinfection high temperature duration, range: 5~60 min, default
setting: 15 min
Time interval of compressor start-up in cooling mode; range: 5~5
min, default setting: 5 min
Default setting: 5°C, range: 2~10°C, setting interval: 1°C
Default setting: 2°C, range: 1~10°C, setting interval: 1°C
Default setting: 52°C, range: 35~52°C, setting interval: 1°C
Delay time for enabling the external heater AHS, range: 5~120
min;
default setting: 30 min
The temperature difference between the heat pump ’ s leaving
water set temperature (T1S) and the heat,range: 2~20°C;
default setting: 5°C
Ambient temperature for enabling the hydraulic module auxiliary
electric
heating IBH, range: -15~10°C; default setting: -5°C
Temperature return difference for enabling the hydraulic module
auxiliary, range: 2~10°C; default setting: 5°C
Delay time of enabling the hydraulic module auxiliary electric
heating IBH,range: 15~120 min; default setting: 30 min
The trigger ambient temperature for turning on AHS
range: -15~30°C;default setting: -5°C
Содержание AIWD URBAN II Series
Страница 23: ...20 2...
Страница 24: ...21 15...
Страница 33: ...30 6 2 3 Add Home Appliances 1 Add your device following the guidance...
Страница 34: ...31 2 Operate the wired controller according to APP prompts...
Страница 35: ...32 3 Wait for the home appliance to connect and click Sure...
Страница 43: ...40 7 3 1 Structure size figure 19mm 84mm 44mm 46mm 60mm 120mm 20mm 120mm Figure A...
Страница 64: ...Eurofred S A Marqu s de Sentmenat 97 08029 Barcelona www eurofred es...