Dairyland SWX-100-PED Скачать руководство пользователя страница 1

External Isolation Switch

Installation and Operating Instructions 

SWX-100-PED

INTRODUCTION

The Dairyland Isolation Switch, model SWX-100-PED, is 

designed to be externally mounted to the cover of Dairyland 

pedestal models including the current MTP-36 pedestal as 

well as older generation MTP-36 pedestals and discontinued 

MTP-42 pedestals. These instructions address connection of 

the switch to a PCR or SSD model installed in any of the ped-

estal models listed and assumed to be in service. 

Each Isolation Switch must be ordered with a lead kit unique 

to the decoupler model to which it will be connected.  Lead 

kit model  MTL-2-32-SWP is required for connection to a PCR 

rated 10kA and below, model MTL-2/0-32-SWP is for use with 

PCR models rated 15kA,  and model MTL-2-32-SWS for con-

nection to an SSD.

WORKER SAFETY

For worker safety during installation, it is recommended that 

the user obtain certain equipment; namely a pair of electri-

cally insulated gloves, a shorting cable of approximate 3 ft 

length with insulated clamps on each end, and a multi-meter 

to measure ac voltage.  (Of these items, Dairyland offers 

a suitable 3 ft long 1/0AWG shorting cable with insulated 

clamps, Model# BCL-1/0 for decouplers rated 10kA or higher 

or Model# BCL-2 for decouplers rated less than 10kA.) The 

following installation procedure assumes that these items are 

available. It is suggested that a grounding jumper be used 

as a safety precaution in the event the pipeline lead rises to 

an unsafe potential when it is removed from the decoupler, 

which is a necessary step during the installation process or if 

an electrical disturbance occurred while the Isolation Switch 

is being installed. If the voltage one is working with is not at a 

safe touch potential (i.e., >15Vac to ground), then insulating 

gloves should be used.

Dairyland Electrical Industries  •  P.O. Box 187 Stoughton, WI 53589  •  608-877-9900  •  www.dairyland.com  •  [email protected]

3567 - Rev. A - August 2015

WARNING: 

When  isolation  switches  are  used  in  ac  voltage  mitigation 

applications,  if  multiple  or  all  decouplers  are  disconnected, 

the pipeline voltage may rise to an unsafe level (i.e., above the 

15Vac that NACE standards consider safe).  Therefore, safety 

precautions  should  be  taken  by  the  user  when  decouplers 

used  for  ac  voltage  mitigation  are  isolated  from  the  pipeline, 

particularly  at  any  pipeline  contact  point.  Dairyland  provides 

suggested procedures for installing and operating the Isolation 

Switch, but the user must be responsible for and approve the 

procedures to be used by its workers when initially installing the 

Isolation Switch in a field retrofit installation because Dairyland 

cannot be familiar with each user’s safety guidelines. 

WARNING: 

Measure the ac voltage at the decoupler, as outlined in step 9, 

before contacting any terminals or connections, and follow the 

described safety procedures.

CAUTION: 

When  a  decoupler  is  being  used  to  provide  ac  grounding 

for  electrical  equipment,  via  installation  in  a  code-covered 

grounding conductor or bond, an Isolation Switch should not 

be installed because per electric codes such equipment must 

always be solidly AC grounded under all conditions.

Model SWX-100-PED

WARNING: 

Isolation Switches are not to be installed in a defined hazardous 

location, but rather in an “ordinary” location.

Model: MTL-2-32-SWS (SSD) 

& MTL-2-32-SWP (PCR)