BEFORE YOU BEGIN 

Read these instructions completely and carefully.

Save these instructions for future use.

1

Installation Process

Installation Guide 

WOS2-CM  |  DT108

Risk of electrical shock. Disconnect power before servicing or  

installing product. 

Install in accordance with National Electric Code and local codes.

WARNING

Risk of injury. Wear safety glasses and gloves during installation and 

servicing.

CAUTION

The 

Ceiling Mounted Wireless Occupancy Sensor (WOS2-CM) 

operates seamlessly within the Daintree Networked platform. 

The WOS2-CM is a battery-powered occupancy sensor using 

passive infrared (PIR) sensing technology to detect movement. 

As part of the Daintree Networked platform and using open, 

standards based ZigBee wireless communications, the WOS2-CM 

reports real-time occupancy events to turn on lights or keep them 

on when movement is detected, and turn off lights when a space 

is left vacant. The sensor’s off-delay timer is user-configurable 

from any location using the Daintree Controls Software (DCS) 

web application, eliminating the need for on-site, manual 

sensor adjustment.
The WOS2-CM-S provides the standard coverage area, 500SF 

with a 360 degree (lateral) coverage. The WOS2-CM-E provides 

an extended coverage area of up to 1000SF.

•  Keep the sensor lens clean. Avoid touching the sensor lens.
•  After first-time installation or reinstallation of a new battery, 

  allow up to three minutes for initialization. 

1.  

Determine the mounting local on for the sensor based on day 

  light availability and task area. See 

Placement

 for details.

2. 

Remove the sensor from the base by twisting it. Locate the  

  sensor’s IEEE address on the label inside the base. Record the  

  sensor’s IEEE address in its local on the facility floor plan.

3. 

Attach the mounting base to the ceiling in the specified location.  

  Be sure the label is visible after mounting the base.

4. 

Install the batteries in the orientation (+ -) shown on  

  the bottom of the battery compartments.

5. 

Secure the sensor to the ceiling by twisting it onto the base.

6. 

After the batteries have been installed for at least 3 minutes,    

  initiate the Installation Test Mode: Momentarily press the  

 

  Utility button. The green LED flashes once then the red  

 

  LED flashes each time the sensor detects motion. (The test  

  mode times out after 5 minutes.)

Daintree

®

 Wireless Occupancy 

Sensor, Ceiling Mount

Occupancy

Sensor

Lens

Network LED

(green)

Infrared Detection 

&Test Mode LED 

(red)

Utility

Button

Base