ELECTRICAL WIRING CONNECTION
IMPORTANT :
* These values are for information only. They should be checked and selected to comply with local and/or
national codes and regulations. They are also subject to the type of installation and size of conductors.
** The appropriate voltage range should be checked with data label on the unit.
FHC20JEVLK - RD20JEVLK
FHC25JEVLK - RD25JEVLK
Model
Indoor
FHC30JEVLK
Outdoor
RD30JEVLK
Voltage range**
Indoor
220V/1Ph/60Hz +
!
Outdoor
220V/1Ph/60Hz +
!
Power supply cable size*
mm
2
Number of conductors
4.0
3
Interconnection cable size*
mm
2
Number of conductors
2.5
4
Recommended time delay fuse*
A
30
There must be an all pole
disconnection in the supply
mains with a contact separation
of at least 3mm.
FHC30JEVLK - RD30JEVLK
COMP
L
N
COMP
L
N
L
N
Model
Indoor
FHC20JEVLK
FHC25JEVLK
Outdoor
RD20JEVLK
RD25JEVLK
Voltage range**
Indoor
220V/1Ph/60Hz +
!
Outdoor
220V/1Ph/60Hz +
!
Power supply cable size*
mm
2
Number of conductors
2.5
3
2.5
3
Interconnection cable size*
mm
2
Number of conductors
1.0
4
1.0
4
Recommended time delay fuse*
A
20
25
There must be an all pole
disconnection in the supply
mains with a contact separation
of at least 3mm.
Interconnection Cable
Indoor Unit
Terminal Block
Outdoor Unit
Terminal Block
Power Supply Cable