IM 1072-1
Water to Water Source Heat Pumps
Page 15 of 44
Wiring Diagram
Legend
208-230/60/1, Unit Sizes 036, 048, 060 and 072
FIELD POWER SUPPLY PER UNIT RATING PLATE. MINIMUM CIRCUIT AMPACITY AND
MAXIMUM SIZE OF TIME-DELAY FUSE OR HACR-TYPE CIRCUIT BREAKER PER UNIT
RATING PLATE. PROVIDE DISCONNECTING MEANS AND EQUIPMENT GROUNDING AS
REQUIRED.
TRANSFORMER MAY HAVE TAPS FOR 120V, 208V, 240V, OR 480V SYSTEM POWER
SUPPLY. BEFORE APPLYING POWER TO THE UNIT, ENSURE TRANSFORMER IS WIRED
FOR APPROPRIATE SYSTEM POWER SUPPLY. INSULATE SEPARATELY ANY UNUSED
LEADS. POLARITY IS NOT INDICATED. TYPICAL TRANSFORMER SHOWN. SEE
TRANSFORMER LABEL FOR LEAD COLOR CODING.
“RVS” IS USED ONLY WITH WWR MODELS AND IS ENERGIZED IN COOLING MODE (LOAD
COIL IS HEAT SOURCE, SOURCE COIL IS HEAT SINK).
“RVS” IS NOT USED WITH WWC AND WWH MODELS.
IF POWER MONITOR OUTPUT CONTACTS DO NOT TRANSFER WHEN POWER IS APPLIED
TO UNIT (BICOLOR LED GLOWS GREEN UNDER NORMAL CONDITIONS AND RED
DURING FAULT CONDITIONS):
1. VERIFY THAT ALL THREE PHASES ARE PRESENT AND ARE OF THE CORRECT
VOLTAGE. IF ALL THREE PHASES ARE PRESENT AND ARE OF THE CORRECT VOLTAGE,
PHASE ROTATION MAY BE INCORRECT. PERFORM STEP 2.
2. DISCONNECT POWER TO THE WW* UNIT. VERIFY THAT POWER IS IN FACT
DISCONNECTED. SWAP ANY TWO OF THE THREE UNIT POWER SUPPLY WIRES. WHEN
POWER IS REAPPLIED, OUTPUT CONTACTS SHOULD NOW TRANSFER.
1
3
6
5
LEGEND
FUNCTIONAL
DESIGNATION
LINE
NUMBER
DESCRIPTION
CL
17
OPTIONAL INDICATOR LIGHT - COMPRESSOR ON
CC
32
COMPRESSOR CONTACTOR
CCH
10
CRANKCASE HEATER
CCM
26
COMPRESSOR CONTROL MODULE
CHR
41
CHANGEOVER RELAY (WHEN USED)
CM
2
COMPRESSOR
EGL
4
EQUIPMENT GROUNDING LUG(S)
F1,F2
6,4
FUSING (WHEN USED) - SEE FUSE TABLE
FL
37
OPTIONAL INDICATOR LIGHT - FAULT
FS-L
28
OPTIONAL FLOW PROVING SWITCH – LOAD COIL
FS-S
28
OPTIONAL FLOW PROVING SWITCH – SOURCE COIL
HP
30
HIGH DISCHARGE PRESSURE CUTOUT SWITCH
HRPR
18
HEAT RECOVERY PUMP RELAY (WHEN USED)
IR
39
INTERLOCK RELAY
LP1
30
LOW SUCTION PRESSURE CUTOUT SWITCH NO. 1
LP2
26
LOW SUCTION PRESSURE CUTOUT SWITCH NO. 2
LTC
20,30
LOW FLUID TEMPERATURE CUTOUT MODULE
PCT
18
WASTE HEAT RECOVERY PUMP CONTROL THERMOSTAT (WHEN USED)
PM
8,14
OPTIONAL POWER MONITOR
RC
2
MOTOR RUN CAPACITOR
RVS
15
REVERSING VALVE SOLENOID (WHEN USED)
TB1
+
TERMINAL BOARD NO. 1
TB2
46,47
TERMINAL BOARD NO. 2
TB3
26
TERMINAL BOARD NO. 3
TB4
4,6
TERMINAL BOARD NO. 4 (WHEN USED)
TR
13
CONTROL TRANSFORMER
TC
23
TEMPERATURE CONTROLLER (OPTIONAL)
TS-C
23
AQUASTAT – COOLING (WHEN USED)
TS-H
22
AQUASTAT – HEATING (WHEN USED)
WHR
5
OPTIONAL WASTE HEAT RECOVERY PUMP
WTL
4
WATER TEMPERATURE LIMIT THERMOSTAT (WHEN USED)
# SEE LINE NUMBER TO THE RIGHT OF CONTACTOR COIL ON WIRING DIAGRAM.
+ MULTIPLE LINE NUMBERS.
7
SEE FIGURE 1 ON SHEET 3 OF THIS DRAWING FOR BOARD LAYOUT, SENSOR
LOCATIONS, TEMPERATURE SETTING NOTE, AND SENSOR RESISTANCE VERSUS
TEMPERATURE GRAPH.
BK: BLACK
PK: PINK
BL: BLUE
PR: PURPLE
BR: BROWN
R:
RED
G:
GREEN
W:
WHITE
O:
ORANGE
Y:
YELLOW
WIRE COLOR LEGEND
NOTES:
NUMBER PLACED AFTER DASH FOLLOWING
COLOR CODE INDICATES WIRE GAGE. FOR
EXAMPLE> BK-12 IS A BLACK, 12 AWG WIRE.
NO NUMBER AFTER COLOR CODE
INDICATES 18 AWG WIRE. FOR EXAMPLE>
BK IS A BLACK 18 AWG WIRE.
ASTERISK AFTER DASH FOLLOWING COLOR
CODE INDICATES REFERRAL TO
COMPRESSOR WIRE SIZE TABLE.
8
“CHR” IS USED ONLY WITH “WWR” UNITS.
“CHR” IS NOT USED WITH “WWC” AND “WWH” UNITS.
17
14 WHEN “FS-L” AND “FS-S” ARE NOT USED, THIS WIRE CONNECTS DIRECTLY TO
TERMINAL Y OF “CCM”.
WHEN “PM” IS NOT USED, THIS WIRE CONNECTS DIRECTLY TO TERMINAL R ON “TB1”.
4
THIS WIRE CONNECTS DIRECTLY FROM TERMINAL S TO TERMINAL Y ON “TB1” WHEN
OPTIONAL TEMPERATURE CONTROLLER “TC” IS NOT FURNISHED.
HEAT RECOVERY OPTION:
FIELD INSTALLED WASTE HEAT RECOVERY PUMP WIRING. USE 14 AWG, 75C
CONDUCTORS MINIMUM . COMPLY WITH LOCAL CODES WHICH MAY REQUIRE
LARGER SIZE WIRING. INSTALL ADDITIONAL DISCONNECTING MEANS WHERE
REQUIRED TO COMPLY WITH ELECTRICAL CODE. THIS EQUIPMENT MUST BE
PERMANENTLY GROUNDED IN ACCORDANCE WITH ELECTRICAL CODE. TERMINAL
BOARD “TB4” IS RATED FOR BOTH 14 AND 12 AWG WIRE SIZES.
THE FOLLOWING COMPONENTS ARE USED ONLY WHEN WASTE HEAT RECOVERY
(DESUPERHEATER) OPTION IS FURNISHED: “F1”, “F2”, “HRPR”, “PCT”, “TB4”, “WHR”,
AND “WTL”. “WHR” IS ORDERED SEPARATELY FOR FIELD INSTALLATION.
2
TYPICAL FIELD CONTROL WIRING SHOWN. ACTUAL FIELD WIRING MAY DIFFER FROM
WIRING SHOWN HERE. USE 18 AWG MINIMUM FOR FIELD 24 VOLT CONTROL WIRING.
TYPICAL REMOTE SWITCH SHOWN. REMOTE SWITCH MAY BE SUPPLIED BY OTHERS
OR IS AVAILABLE AS AN OPTIONAL ACCESSORY FROM THE FACTORY. MINIMUM PILOT
DUTY RATING OF EACH POLE OF REMOTE SWITCH IS 24 VOLT-AMPERES @ 24 VOLTS
AC WHEN CONNECTED AS SHOWN.
AQUASTATS “TS-H” AND “TS-C” ARE NOT USED WHEN OPTIONAL FACTORY INSTALLED
TEMPERATURE CONTROLLER “TC” IS FURNISHED. TYPICAL AQUASTATS SHOWN.
AQUASTATS MAY BE SUPPLIED BY OTHERS OR ARE AVAILABLE AS AN OPTIONAL
ACCESSORY FROM THE FACTORY. MINIMUM PILOT DUTY RATING OF EACH POLE OF
AQUASTAT IS 24 VOLT-AMPERES @ 24 VOLTS AC WHEN CONNECTED AS SHOWN.
9
10
SEE FIGURE 2 ON SHEET 3 OF THIS DRAWING FOR COMPRESSOR CONTROL MODULE
OPERATION.
12
WIRED AS SHOWN FOR OPEN LOOP OR HIGH TEMPERATURE CLOSED LOOP
APPLICATIONS. FOR LOW TEMPERATURE CLOSED LOOP APPLICATIONS, MOVE THIS
WIRE FROM TERMINAL 6 TO TERMINAL 7 ON "TB3".
13
WHEN OPTIONAL “LTC” IS NOT USED, THESE TWO WIRES ARE SPLICED TOGETHER.
15
16 CONDUCTOR “O” REQUIRED WITH WWR REVERSE CYCLE UNITS.
CONDUCTOR “O” NOT USED WITH WWC COOLING AND WWR HEATING UNITS.
INTERLOCK RELAY CONTACTS ARE PROVIDED TO OPERATE AN EXTERNAL PILOT DUTY
LOAD (SUCH AS A PUMP RELAY COIL) WITH A CALL FOR COMPRESSOR.
AN EXTERNAL LOAD POWERED BY TRANSFORMER “TR” IN THE WW* UNIT MUST
NOT EXCEED 12 VA SEALED (96 VA INRUSH) @ 24 VOLTS AC.
EXTERNAL LOADS POWERED FROM AN EXTERNAL SOURCE ARE LIMITED TO
CLASS 2 CIRCUITS ONLY (30 VOLTS AC MAXIMUM). EXTERNAL LOAD
CHARACTERISTICS MUST NOT EXCEED 10 AMPS MAKE, 1 AMP BREAK.
MAINTAIN
SEPARATION BETWEEN CLASS 2 CIRCUITS OF DIFFERENT SOURCES.
PROVIDE DISCONNECTING MEANS, EQUIPMENT GROUNDING, AND
OVERCURRENT PROTECTION AS REQUIRED.
18
FUSE NO.
CLASS VOLTS AC AMPERES TIME DELAY
F1,F2
CC
600
1.5
YES
FUSE TABLE
WHEN OPTIONAL TEMPERATURE CONTROLLER “TC” IS FURNISHED, INSTALLER MUST
PROGRAM CONTROLLER. REFER TO TEMPERATURE CONTROL INSTALLATION
INSTRUCTIONS.
WITH REVERSE-CYCLE WWR UNITS, PROGRAM CONTROLLER AS ONE STAGE
COOLING AND ONE STAGE HEATING. STAGE 1 IS THE COOLING STAGE AND STAGE 2 IS
THE HEATING STAGE.
INSTALL SENSOR @ WATER INLET PIPE (LOAD).
11
FACTORY WIRING
FIELD WIRING
EARTH GROUND
CHASSIS (PANEL) GROUND
COIL
NORMALLY OPEN CONTACTS
IDENTIFIABLE TERMINAL
NON-IDENTIFIABLE TERMINAL,
OTHER WIRE JUNCTIONS,
INCLUDING SCHEMATIC
NORMALLY CLOSED CONTACTS
TERMINAL BOARD NO. 1 (TB1)
SYMBOL LEGEND
OPTIONAL FIELD WIRING
OPTIONAL FACTORY WIRING
TERMINAL BOARD NO. 2 (TB2)
TERMINAL BOARD NO. 3 (TB3)
TERMINAL BOARD NO. 4 (TB4)
WIRING DIAGRAM # 0962I-2631B, REV.B
WW* 036, 048, 060, 072
SINGLE PHASE