Water to Water Source Heat Pumps 

Page 15 of 44

Wiring Diagram

Legend

208-230/60/1, Unit Sizes 036, 048, 060 and 072

FIELD POWER SUPPLY PER UNIT RATING PLATE. MINIMUM CIRCUIT AMPACITY AND

MAXIMUM SIZE OF TIME-DELAY FUSE OR HACR-TYPE CIRCUIT BREAKER PER UNIT

RATING PLATE. PROVIDE DISCONNECTING MEANS AND EQUIPMENT GROUNDING AS

REQUIRED.

TRANSFORMER MAY HAVE TAPS FOR 120V, 208V, 240V, OR 480V SYSTEM POWER

SUPPLY. BEFORE APPLYING POWER TO THE UNIT, ENSURE TRANSFORMER IS WIRED

FOR APPROPRIATE SYSTEM POWER SUPPLY.  INSULATE SEPARATELY ANY UNUSED

LEADS. POLARITY IS NOT INDICATED. TYPICAL TRANSFORMER SHOWN. SEE

TRANSFORMER LABEL FOR LEAD COLOR CODING.

“RVS” IS USED ONLY WITH WWR MODELS AND IS ENERGIZED IN COOLING MODE (LOAD

COIL IS HEAT SOURCE, SOURCE COIL IS HEAT SINK).

“RVS” IS NOT USED WITH WWC AND WWH MODELS.

IF POWER MONITOR OUTPUT CONTACTS DO NOT TRANSFER WHEN POWER IS APPLIED

TO UNIT (BICOLOR LED GLOWS GREEN UNDER NORMAL CONDITIONS AND RED

DURING FAULT CONDITIONS):

1. VERIFY THAT ALL THREE PHASES ARE PRESENT AND ARE OF THE CORRECT

VOLTAGE. IF ALL THREE PHASES ARE PRESENT AND ARE OF THE CORRECT VOLTAGE,

PHASE ROTATION MAY BE INCORRECT. PERFORM STEP 2.

2. DISCONNECT POWER TO THE WW* UNIT. VERIFY THAT POWER IS IN FACT

DISCONNECTED. SWAP ANY TWO OF THE THREE UNIT POWER SUPPLY WIRES. WHEN

POWER IS REAPPLIED, OUTPUT CONTACTS SHOULD NOW TRANSFER.

1

3

6

5

LEGEND

FUNCTIONAL

DESIGNATION

LINE

NUMBER

DESCRIPTION

CL

17

OPTIONAL INDICATOR LIGHT - COMPRESSOR ON

CC

32

COMPRESSOR CONTACTOR

CCH

10

CRANKCASE HEATER

CCM

26

COMPRESSOR CONTROL MODULE

CHR

41

CHANGEOVER RELAY (WHEN USED)

CM

2

COMPRESSOR

EGL

4

EQUIPMENT GROUNDING LUG(S)

F1,F2

6,4

FUSING (WHEN USED) - SEE FUSE TABLE

FL

37

OPTIONAL INDICATOR LIGHT - FAULT

FS-L

28

OPTIONAL FLOW PROVING SWITCH – LOAD COIL

FS-S

28

OPTIONAL FLOW PROVING SWITCH – SOURCE COIL

HP

30

HIGH DISCHARGE PRESSURE CUTOUT SWITCH

HRPR

18

HEAT RECOVERY PUMP RELAY (WHEN USED)

IR

39

INTERLOCK RELAY

LP1

30

LOW SUCTION PRESSURE CUTOUT SWITCH NO. 1

LP2

26

LOW SUCTION PRESSURE CUTOUT SWITCH NO. 2

LTC

20,30

LOW FLUID TEMPERATURE CUTOUT MODULE

PCT

18

WASTE HEAT RECOVERY PUMP CONTROL THERMOSTAT (WHEN USED)

PM

8,14

OPTIONAL POWER MONITOR

RC

2

MOTOR RUN CAPACITOR

RVS

15

REVERSING VALVE SOLENOID (WHEN USED)

TB1

+

TERMINAL BOARD NO. 1

TB2

46,47

TERMINAL BOARD NO. 2

TB3

26

TERMINAL BOARD NO. 3

TB4

4,6

TERMINAL BOARD NO. 4 (WHEN USED)

TR

13

CONTROL TRANSFORMER

TC

23

TEMPERATURE CONTROLLER (OPTIONAL)

TS-C

23

AQUASTAT – COOLING (WHEN USED)

TS-H

22

AQUASTAT – HEATING (WHEN USED)

WHR

5

OPTIONAL WASTE HEAT RECOVERY PUMP

WTL

4

WATER TEMPERATURE LIMIT THERMOSTAT (WHEN USED)

# SEE LINE NUMBER TO THE RIGHT OF CONTACTOR COIL ON WIRING DIAGRAM.

+ MULTIPLE LINE NUMBERS.

7

SEE FIGURE 1 ON SHEET 3 OF THIS DRAWING FOR BOARD LAYOUT, SENSOR

LOCATIONS, TEMPERATURE SETTING NOTE, AND SENSOR RESISTANCE VERSUS

TEMPERATURE GRAPH.

BK: BLACK

PK: PINK

BL: BLUE

PR: PURPLE

BR: BROWN

R:

RED

G:

GREEN

W:

WHITE

O:

ORANGE

Y:

YELLOW

WIRE COLOR LEGEND

NOTES:

NUMBER PLACED AFTER DASH FOLLOWING

COLOR CODE INDICATES WIRE GAGE. FOR

EXAMPLE> BK-12 IS A BLACK, 12 AWG WIRE.

NO NUMBER AFTER COLOR CODE

INDICATES 18 AWG WIRE. FOR EXAMPLE>

BK IS A BLACK 18 AWG WIRE.

ASTERISK AFTER DASH FOLLOWING COLOR

CODE INDICATES REFERRAL TO

COMPRESSOR WIRE SIZE TABLE.

8

“CHR” IS USED ONLY WITH “WWR” UNITS.

“CHR” IS NOT USED WITH “WWC” AND “WWH” UNITS.

17

14 WHEN “FS-L” AND “FS-S” ARE NOT USED, THIS WIRE CONNECTS DIRECTLY TO

TERMINAL Y OF “CCM”.

WHEN “PM” IS NOT USED, THIS WIRE CONNECTS DIRECTLY TO TERMINAL R ON “TB1”.

4

THIS WIRE CONNECTS DIRECTLY FROM TERMINAL S TO TERMINAL Y ON “TB1” WHEN

OPTIONAL TEMPERATURE CONTROLLER “TC” IS NOT FURNISHED.

HEAT RECOVERY OPTION:

FIELD INSTALLED WASTE HEAT RECOVERY PUMP WIRING. USE 14 AWG, 75C

CONDUCTORS MINIMUM . COMPLY WITH LOCAL CODES WHICH MAY REQUIRE

LARGER SIZE WIRING. INSTALL ADDITIONAL DISCONNECTING MEANS WHERE

REQUIRED TO COMPLY WITH ELECTRICAL CODE. THIS EQUIPMENT MUST BE

PERMANENTLY GROUNDED IN ACCORDANCE WITH ELECTRICAL CODE. TERMINAL

BOARD “TB4” IS RATED FOR BOTH 14 AND 12 AWG WIRE SIZES.

THE FOLLOWING COMPONENTS ARE USED ONLY WHEN WASTE HEAT RECOVERY

(DESUPERHEATER) OPTION IS FURNISHED: “F1”, “F2”, “HRPR”, “PCT”, “TB4”, “WHR”,

AND “WTL”. “WHR” IS ORDERED SEPARATELY FOR FIELD INSTALLATION.

2

TYPICAL FIELD CONTROL WIRING SHOWN. ACTUAL FIELD WIRING MAY DIFFER FROM

WIRING SHOWN HERE. USE 18 AWG MINIMUM FOR FIELD 24 VOLT CONTROL WIRING.

TYPICAL REMOTE SWITCH SHOWN. REMOTE SWITCH MAY BE SUPPLIED BY OTHERS

OR IS AVAILABLE AS AN OPTIONAL ACCESSORY FROM THE FACTORY. MINIMUM PILOT

DUTY RATING OF EACH POLE OF REMOTE SWITCH IS 24 VOLT-AMPERES @ 24 VOLTS

AC WHEN CONNECTED AS SHOWN.

AQUASTATS “TS-H” AND “TS-C” ARE NOT USED WHEN OPTIONAL FACTORY INSTALLED

TEMPERATURE CONTROLLER “TC” IS FURNISHED. TYPICAL AQUASTATS SHOWN.

AQUASTATS MAY BE SUPPLIED BY OTHERS OR ARE AVAILABLE AS AN OPTIONAL

ACCESSORY FROM THE FACTORY. MINIMUM PILOT DUTY RATING OF EACH POLE OF

AQUASTAT IS 24 VOLT-AMPERES @ 24 VOLTS AC WHEN CONNECTED AS SHOWN.

9

10

SEE FIGURE 2 ON SHEET 3 OF THIS DRAWING FOR COMPRESSOR CONTROL MODULE

OPERATION.

12

WIRED AS SHOWN FOR OPEN LOOP OR HIGH TEMPERATURE CLOSED LOOP

APPLICATIONS. FOR LOW TEMPERATURE CLOSED LOOP APPLICATIONS, MOVE THIS

WIRE FROM TERMINAL 6 TO TERMINAL 7 ON "TB3".

13

WHEN OPTIONAL “LTC” IS NOT USED, THESE TWO WIRES ARE SPLICED TOGETHER.

15
16 CONDUCTOR “O” REQUIRED WITH WWR REVERSE CYCLE UNITS.

CONDUCTOR “O” NOT USED WITH WWC COOLING AND WWR HEATING UNITS.

INTERLOCK RELAY CONTACTS ARE PROVIDED TO OPERATE AN EXTERNAL PILOT DUTY

LOAD (SUCH AS A PUMP RELAY COIL) WITH A CALL FOR COMPRESSOR.

AN EXTERNAL LOAD POWERED BY TRANSFORMER “TR” IN THE WW* UNIT MUST

NOT EXCEED 12 VA SEALED (96 VA INRUSH) @ 24 VOLTS AC.

EXTERNAL LOADS POWERED FROM AN EXTERNAL SOURCE ARE LIMITED TO

CLASS 2 CIRCUITS ONLY (30 VOLTS AC MAXIMUM). EXTERNAL LOAD

CHARACTERISTICS MUST NOT EXCEED 10 AMPS MAKE, 1 AMP BREAK.

MAINTAIN

SEPARATION BETWEEN CLASS 2 CIRCUITS OF DIFFERENT SOURCES.

PROVIDE DISCONNECTING MEANS, EQUIPMENT GROUNDING, AND

OVERCURRENT PROTECTION AS REQUIRED.

18

FUSE NO.

CLASS VOLTS AC AMPERES TIME DELAY

F1,F2

CC

600

1.5

YES

FUSE TABLE

WHEN OPTIONAL TEMPERATURE CONTROLLER “TC” IS FURNISHED, INSTALLER MUST

PROGRAM CONTROLLER. REFER TO TEMPERATURE CONTROL INSTALLATION

INSTRUCTIONS.

WITH REVERSE-CYCLE WWR UNITS, PROGRAM CONTROLLER AS ONE STAGE

COOLING AND ONE STAGE HEATING. STAGE 1 IS THE COOLING STAGE AND STAGE 2 IS

THE HEATING STAGE.

INSTALL SENSOR @ WATER INLET PIPE (LOAD).

11

FACTORY WIRING

FIELD WIRING

EARTH GROUND

CHASSIS (PANEL) GROUND

COIL

NORMALLY OPEN CONTACTS

IDENTIFIABLE TERMINAL

NON-IDENTIFIABLE TERMINAL,

OTHER WIRE JUNCTIONS,

INCLUDING SCHEMATIC

NORMALLY CLOSED CONTACTS

TERMINAL BOARD NO. 1 (TB1)

SYMBOL LEGEND

OPTIONAL FIELD WIRING

OPTIONAL FACTORY WIRING

TERMINAL BOARD NO. 2 (TB2)

TERMINAL BOARD NO. 3 (TB3)

TERMINAL BOARD NO. 4 (TB4)

WIRING DIAGRAM # 0962I-2631B, REV.B

WW* 036, 048, 060, 072

SINGLE PHASE

Содержание WRA

Страница 1: ...Group WSHP Part Number 667691802 Date October 2013 Daikin Water to Water Source Heat Pumps 3 to 35 Tons with R 410A WRA Heating and Cooling Models WHA Heating Only Models WCA Cooling Only Models 2013...

Страница 2: ...LTC 208 230 60 3 Unit Sizes 036 048 060 and 072 20 Compressor Control Module Functional Operation 208 230 60 3 Unit Sizes 036 048 060 and 072 21 Wiring Diagram 22 208 230 60 3 Unit Sizes 120 150 180 2...

Страница 3: ...ooling 300 300 000 Btuh Nominal Cooling 360 360 000 Btuh Nominal Cooling 420 420 000 Btuh Nominal Cooling Water Piping Location F Front T Top L Left Hand Side R Right Hand Side Status Lights YY None S...

Страница 4: ...nly used on product labels to signify an immedi ate hazard The signal words WARNING and CAUTION will be used on product labels and throughout this manual and other manuals that may apply to the produc...

Страница 5: ...0 15 4 517 632 9 6 15 15 120 208 230 60 1 2 23 1 134 0 46 2 197 253 52 0 70 70 208 230 60 3 16 1 91 0 32 2 187 253 36 2 50 50 460 60 3 7 1 46 0 14 2 414 506 16 0 20 20 575 60 3 5 6 37 0 11 2 517 632 1...

Страница 6: ...ter pressure and sized for proper flow rate The supply and the discharge pipes should be insulated to prevent condensation damage caused by low water temperature in the pipes If water hammer should oc...

Страница 7: ...rejected from the unit into the source water loop To reject excess heat from the water loop the use of a closed circuit evaporative cooler or an open type cooling tower with a secondary heat exchange...

Страница 8: ...the tables 11 Check for vibrations noise water leaks etc 12 Adjust thermostat to correct mode and set to maintain desired temperature 13 Instruct the equipment owner operator of correct thermostat an...

Страница 9: ...3 4 KO 1 2 KO 3 4 FPT 1 2 FPT Dimensions Size 048 060 Dimensions in Pipe Size FPT Connection Size A B C D E F G H J K L M N P Control Electric Auxiliary Electric Load Source Domestic Hot Water 28 28...

Страница 10: ...ions Size 120 150 Dimensions in Water Connection Size A B C D E F G H K L M N P Q R S Load Source FPT 26 19 12 4 8 22 4 18 41 22 34 1 113 16 37 29 42 1 Dimensions Size 180 Dimensions in Water Connecti...

Страница 11: ...Source Heat Pumps Page 11 of 44 Dimensional Data WRA WCA WHA Size 240 420 Dimensions Size 240 420 Dimensions in Water Connection Size A B C D E F K L M N P Q R S Load Source FPT 31 20 16 4 22 27 63 2...

Страница 12: ...00 50 00 63 125 1130 1230 16 0 16 0 2 00 360 34 00 50 00 63 125 1420 1540 17 5 17 5 2 00 420 34 00 50 00 63 125 1620 1750 20 0 20 0 2 00 Operating Pressures PSIG Cooling Mode Table 4 Models WRA and W...

Страница 13: ...813 0 829 0 937 1 614 50 0 922 0 770 0 789 0 922 1 816 Methanol 10 0 986 0 957 0 961 0 986 1 127 20 0 970 0 924 0 928 0 970 1 197 30 0 951 0 895 0 897 0 951 1 235 40 0 936 0 863 0 865 0 936 1 323 50 0...

Страница 14: ...C P5 P4 P3 P2 P1 300 180 120 90 LPS BYPASS SECONDS DOM ASC R LED OFF NO Y SIGNAL PRESENT ON Y SIGNAL PRESENT 1 BLINK FAULT ON HPS TERMINALS 2 BLINKS FAULT ON LPS TERMINALS LPR AL1701 PK CC Y W OPTIONA...

Страница 15: ...H UNITS 17 14 WHEN FS L AND FS S ARE NOT USED THIS WIRE CONNECTS DIRECTLY TO TERMINAL Y OF CCM WHEN PM IS NOT USED THIS WIRE CONNECTS DIRECTLY TO TERMINAL R ON TB1 4 THIS WIRE CONNECTS DIRECTLY FROM T...

Страница 16: ...ature drops below 20 F The control will re energize the output relays when the sensor temperature rises above 22 5 F Additionally the control will monitor each individual sensor to make sure it isn t...

Страница 17: ...es with the Y signal through the circuit board The 60 psig low pressure switch is connected in series with the Y signal to the processor only This will allow the control to monitor the low pressure sw...

Страница 18: ...ASS SECONDS DOM ASC R LED OFF NO Y SIGNAL PRESENT ON Y SIGNAL PRESENT 1 BLINK FAULT ON HPS TERMINALS 2 BLINKS FAULT ON LPS TERMINALS LPR AL1701 PK CC Y W OPTIONAL HP BK BL BK PR W 24 VAC LTC OPTIONAL...

Страница 19: ...K 12 AWG WIRE NO NUMBER AFTER COLOR CODE INDICATES 18 AWG WIRE FOR EXAMPLE BK IS A BLACK 18 AWG WIRE ASTERISK AFTER DASH FOLLOWING COLOR CODE INDICATES REFERRAL TO COMPRESSOR WIRE SIZE TABLE 8 CHR IS...

Страница 20: ...ature drops below 20 F The control will re energize the output relays when the sensor temperature rises above 22 5 F Additionally the control will monitor each individual sensor to make sure it isn t...

Страница 21: ...es with the Y signal through the circuit board The 60 psig low pressure switch is connected in series with the Y signal to the processor only This will allow the control to monitor the low pressure sw...

Страница 22: ...L HP1 BK BL R FL PR W R 24 VAC LTC OPTIONAL SEN 1 SEN 2 SENSOR 1 SENSOR 2 3 R TB3 4 CCM1 CR2 1 3 BK LPS Y HPS T1 T C R X P10 P11 P12 10 SEC 5 MIN P7 P8 P9 3 SEC 6 SEC P5 P4 P3 P2 P1 300 180 120 90 LPS...

Страница 23: ...4 6 CR1 4 6 PR PR PR PR TS C TS H 23 63 34 64 52 CHR 1 3 WHEN USED 21 20 BR BR WHEN REQ D SPLICE 12 CHR 4 2 WHEN REQ D SPLICE BR CLASS 2 60 HZ TR1 24V WHEN USED R R R O C O 16 TB1 TB2 A1 A2 24 COM TC...

Страница 24: ...30 VOLTS AC MAXIMUM EXTERNAL LOAD CHARACTERISTICS MUST NOT EXCEED 10 AMPS MAKE 1 AMP BREAK MAINTAIN SEPARATION BETWEEN CLASS 2 CIRCUITS OF DIFFERENT SOURCES PROVIDE DISCONNECTING MEANS EQUIPMENT GROU...

Страница 25: ...drops below 20 F The control will re energize the output relays when the sensor temperature rises above 22 5 F Additionally the control will monitor each individual sensor to make sure it isn t broken...

Страница 26: ...nnected in series with the Y signal to the processor only This will allow the control to monitor the low pressure switch status and initi ate the bypass delay If the 60 psig low pressure switch should...

Страница 27: ...W R 24 VAC LTC OPTIONAL SEN 1 SEN 2 SENSOR 1 SENSOR 2 3 R TB3 4 CCM1 CR2 1 3 BK LPS Y HPS T1 T C R X P10 P11 P12 10 SEC 5 MIN P7 P8 P9 3 SEC 6 SEC P5 P4 P3 P2 P1 300 180 120 90 LPS BYPASS SECONDS DOM...

Страница 28: ...64 52 CHR 1 3 11 WHEN USED 19 18 BR BR WHEN REQ D SPLICE 10 CHR 4 2 WHEN REQ D SPLICE BR 96 VA CLASS 2 60 HZ TR1 24V WHEN USED R R R O C Y O 14 TB1 TB2 A1 A2 OPTIONAL 208 230V 4 0A 24 COM TC OPTIONAL...

Страница 29: ...WITH THE COMPRESSORS AN EXTERNAL LOAD POWERED BY TRANSFORMER TR1 IN THE WW UNIT MUST NOT EXCEED 12 VA SEALED 96 VA INRUSH 24 VOLTS AC EXTERNAL LOADS POWERED FROM AN EXTERNAL SOURCE ARE LIMITED TO CLAS...

Страница 30: ...elow 20 F The control will re energize the output relays when the sensor temperature rises above 22 5 F Additionally the control will monitor each individual sensor to make sure it isn t broken or sho...

Страница 31: ...n series with the Y signal to the processor only This will allow the control to monitor the low pressure switch status and initi ate the bypass delay If the 60 psig low pressure switch should open the...

Страница 32: ...S R Y PR O OPTIONAL OPTIONAL 5 CC1 Y W OPTIONAL HP1 BK BL BK R FL PR W R 24 VAC LTC OPTIONAL SEN 1 SEN 2 SENSOR 1 SENSOR 2 3 R TB3 4 CCM1 CR2 1 3 BK LPS Y HPS T1 T C R X P10 P11 P12 10 SEC 5 MIN P7 P8...

Страница 33: ...BK BK CR2 4 6 CR1 4 6 PR PR PR PR TS C TS H 23 63 34 64 52 CHR 1 3 11 WHEN USED 19 18 BR BR WHEN REQ D SPLICE 10 CHR 4 2 WHEN REQ D SPLICE BR CLASS 2 60 HZ TR1 24V WHEN USED R R R O C O 14 TB1 TB2 A1...

Страница 34: ...COMPRESSORS AN EXTERNAL LOAD POWERED BY TRANSFORMER TR1 IN THE WW UNIT MUST NOT EXCEED 12 VA SEALED 96 VA INRUSH 24 VOLTS AC EXTERNAL LOADS POWERED FROM AN EXTERNAL SOURCE ARE LIMITED TO CLASS 2 CIRCU...

Страница 35: ...below 20 F The control will re energize the output relays when the sensor temperature rises above 22 5 F Additionally the control will monitor each individual sensor to make sure it isn t broken or s...

Страница 36: ...d in series with the Y signal to the processor only This will allow the control to monitor the low pressure switch status and initi ate the bypass delay If the 60 psig low pressure switch should open...

Страница 37: ...IM 1072 1 Water to Water Source Heat Pumps Page 37 of 44 WHA Circuit Diagram WHA Load Coil Heater Condenser Source Coil Evaporator...

Страница 38: ...Page 38 of 44 Water to Water Source Heat Pumps IM 1072 1 WRA Circuit Diagram WRA Reverse Cycle No Domestic Hot Water WRA Reverse Cycle With Domestic Hot Water H R Coil...

Страница 39: ...ter Source Heat Pumps Page 39 of 44 WCA Circuit Diagram WCA Load Coil Chiller Evaporator Source Coil Condenser No Domestic Hot Water WCA Load Coil Chiller Evaporator Source Coil Condenser With Domesti...

Страница 40: ...erage____________________ Phase____________________ Transformer Volts__________________ Unit Function Heating WRA WHA Entering Leaving Diff TD Load Liquid Temperature F From fan coil unit radiant coil...

Страница 41: ...tor points etc won t start 3 Compressor starts but a Run capacitor could be bad a Check capacitor hums and trips out on overload b Voltage may be low b Check it c Seized bearings on compressor c Repla...

Страница 42: ...tch HP 7 Low Pressure 844 151 844 151 844 151 844 151 844 151 844 151 844 151 844 151 844 151 844 151 844 151 Switch LP1 8 Fluid Refrigerant 512 200 512 201 512 201 512 259 512 201 512 202 512 200 512...

Страница 43: ...This page intentionally left blank...

Страница 44: ...rsuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Representative for warranty details Refer to Form 933 430285Y To find your local Daikin...

Отзывы: