background image

IM 1131-2

9

Water Piping

Glycol Solutions  

WGZ units are designed to operate with a leaving chilled fluid 
temperature from 15°F (-9.4°C) to 60°F (16°C). Leaving 
chilled fluid temperatures below 40°F (4.6°C) result in suction 
temperatures at or below the freezing point of water and a 
glycol anti-freeze solution is required. The use of glycol in the 
evaporator will reduce the performance of the unit. The 
reduction in performance depends upon the glycol 
concentration and temperature. This should be taken into 
consideration during initial system design. Glycol in the 
condenser will have a negligible effect on performance 
because glycol at these higher temperatures will perform with 
characteristics similar to water.
Daikin Applied recommends a minimum concentration of 25% 
be provided on all glycol applications. Glycol concentrations 
below 25% are too diluted for long-term corrosion protection 
of ferrous metals and corrosion inhibitors need to be 
recalculated and possibly added to the system.
Chiller capacity, flow rate, evaporator pressure drop, and 
power input for glycol solutions can be calculated using the 
following formulas and reference to 

Table 2

 for ethylene 

glycol and 

Table 3

 for propylene glycol. Test coolant with a 

clean, accurate, glycol solution hydrometer (similar to that 
found in service stations) to determine the freezing point. 

Note: 

Ethylene and propylene glycol ratings are outside the 

scope of AHRI Standard 550/590 certification program. 

Capacity

 is reduced compared to that with plain water. To find 

the reduced value, multiply the chiller's capacity when using 
water by the capacity correction factor C to find the chiller's 
capacity when using glycol.

Flow

 -To determine evaporator gpm (or  T) knowing  T (or 

gpm) and capacity:  

For Metric Applications

 -- Determine evaporator lps (or  T) 

knowing  T (or lps) and kW: 

Pressure Drop

 - To determine glycol pressure drop through 

the cooler, enter the water pressure drop graph on 

page 14

 at 

the actual glycol flow. Multiply the water pressure drop found 
there by P to obtain corrected glycol pressure drop.

Power -

To determine glycol system kW, multiply the water 

system kW by factor K.

Table 2: Ethylene Glycol Correction Factors 

Table 3: 

P

ropylene Glycol Correction Factors 

Condenser Water Piping

Arrange the condenser water so the water enters the bottom 
connection of the condenser. The condenser water will 
discharge from the top connection. Failing to arrange the 
condenser water as stated above will negatively affect the 
capacity and efficiency. 
Install pressure gauges in the inlet and outlet water lines to the 
condenser. Pressure drop through the condenser should be 
measured to determine flow on the pressure drop/flow curves 
beginning on 

page 14

. Vibration eliminators are recommended 

in both the supply and return water lines. Install a 20-mesh 
strainer in the inlet piping to the condenser.
Water-cooled condensers can be piped for use with cooling 
towers, well water, or heat recovery applications. Cooling 
tower applications must be made with consideration of freeze 
protection and scaling problems. Contact the cooling tower 
manufacturer for equipment characteristics and limitations for 
the specific application. Head pressure control must be 
provided if the entering condenser water can fall below 60°F. 
The WGZ condenser has two refrigerant circuits with a 
common condenser water circuit. This arrangement makes 
head pressure control with discharge pressure actuated control 
valves difficult. 
If the tower water temperature cannot be maintained at a 60°F 
minimum, or when pond, lake, or well water that can fall 
below 60°F (15°C) is used as the condensing medium, special 
discharge pressure control must be used. A water recirculating 
system with recirculating pump as shown in 

Figure 6

 is 

recommended. This system also has the advantage of 
maintaining tube velocity to help prevent tube fouling. The 
pump must cycle with the chiller.

Figure 5: Recirculating Discharge Water System  

CAUTION

Do not use automotive antifreeze. Industrial glycols must be used. 

Automotive antifreeze contains inhibitors that causes plating on 

copper tubes. The type and handling of glycol used must be 

consistent with local codes.

Tables

From

G

Correction

Flow

x

T

Capacity

Glycol

x

GPM

Glycol

Δ

=

24

Tables

from

G

Correction

Flow

x

T

x

kW

Lps

Glycol

Δ

=

18

.

4

° F

° C

10%

25.0

-3.9

0.997

0.999

1.030

1.113

20%

18.0

-7.8

0.993

0.997

1.060

1.226

30%

7.0

-14.0

0.987

0.995

1.092

1.369

40%

-7.0

-22.0

0.980

0.992

1.132

1.557

50%

-28.0

0.973

0.991

1.182

1.791

Flow

"G"

PD

"P"

% E.G.

Freeze Point Capacity

"C"

Power

"K"

° F

° C

10%

25.0

-3.9

0.994

0.998

1.016

1.106

20%

19.0

-7.2

0.987

0.995

1.032

1.211

30%

9.0

-13.0

0.978

0.992

1.057

1.380

40%

-5.0

-21.0

0.964

0.987

1.092

1.703

50%

-27.0

-32.8

0.952

0.983

1.140

2.250

Flow

"G"

PD

"P"

% P.G.

Freeze Point Capacity

"C"

Power

"K"

 

Circuit #1 

Outlet

Condenser

Temperature

Control

Valve

Condenser

Water

Circuit #2 

Outlet

Circuit #1 

Inlet

Circuit #2 

Inlet

Содержание WGZ030DW

Страница 1: ...1 2 Water Cooled Scroll Compressor Chiller Group Chillers Part Number IM1131 2 Date June 2014 2014 Daikin Applied WGZ030DW WGZ200DW Packaged Water Cooled Chillers WGZ030DA WGZ200DA Condenserless Chill...

Страница 2: ...ograph is an WGZ060 D This manual covers WGZ D vintage water cooled scroll chillers DANGER Dangers indicate a hazardous situation which will result in death or serious injury if not avoided WARNING Wa...

Страница 3: ...s required Inspection When the equipment is received all items should be carefully checked against the bill of lading to be sure of a complete shipment All units must be carefully inspected for damage...

Страница 4: ...opening Moving the Unit Refer to Lifting Mounting weights beginning on page 25 The packaged unit skid option is strongly recommended for ease of handling and to help prevent damage if a crane is not...

Страница 5: ...ompliance They can supply the installer with the proper building and safety codes required for a safe and proper installation The piping should be designed with a minimum number of bends and changes i...

Страница 6: ...ed far enough upstream to prevent cavitation at the pump inlet consult pump manufacturer for recommendations The use of a strainer will prolong pump life and thus maintain system performance 11 A clea...

Страница 7: ...so the chilled water circulating pump discharges into the evaporator inlet The return water line must be piped to the evaporator inlet connection and the supply water line must be piped to the evapora...

Страница 8: ...ally closed contacts on the switch that could be used for an indicator light or an alarm to indicate when a no flow condition exists 1 Apply pipe sealing compound to only the threads of the switch and...

Страница 9: ...condenser water will discharge from the top connection Failing to arrange the condenser water as stated above will negatively affect the capacity and efficiency Install pressure gauges in the inlet a...

Страница 10: ...7 to 41 4 kPa is considered good design Careful consideration must be given for sizing each section of piping to insure that gas velocities are sufficient at all operating conditions to carry oil If t...

Страница 11: ...030 WGZ035 WGZ040 WGZ045 WGZ050 WGZ055 WGZ060 WGZ070 WGZ080 WGZ090 Line Size in 1 3 8 1 3 8 1 5 8 1 5 8 1 5 8 1 5 8 1 5 8 1 5 8 2 1 8 2 1 8 Unit Size WGZ100 WGZ115 WGZ130 WGZ150 WGZ170 WGZ200 Line Siz...

Страница 12: ...l It is advisable to include a purging vent at this point to extract non condensables from the system The receiver is used when it is desired to have refrigerant storage capacity in addition to the pu...

Страница 13: ...r operation Relief Valve Piping The ANSI ASHRAE Standard 15 Safety Standard for Refrigeration Systems specifies that pressure relief valves on vessels containing Group 1 refrigerant R 410A shall disch...

Страница 14: ...169 2 9 9 10 6 29 6 282 0 26 1 17 6 78 1 WGZ060D G 113 4 5 2 7 1 15 4 181 5 12 6 11 3 37 7 302 5 33 3 18 9 99 4 WGZ070D H 131 6 4 3 8 2 12 8 210 6 10 5 13 2 31 4 351 0 27 7 21 9 82 8 WGZ080D I 146 8...

Страница 15: ...15 8 8 5 47 2 225 7 41 7 14 1 124 7 WGZ060D G 90 8 5 9 5 7 17 7 145 2 14 5 9 1 43 3 242 0 38 3 15 1 114 4 WGZ070D H 105 3 6 5 6 6 19 3 168 5 15 8 10 5 47 2 280 8 41 7 17 6 124 7 WGZ080D I 117 4 4 9 7...

Страница 16: ...INLET ON OPPOSITE SIDE REMOVABLE ONLY POWER CONTROL CONNECTIONS 770 30 3 1609 63 4 30 4 771 14 1 359 8 2 209 32 0 813 1140 44 9 1016 40 0 314 12 4 508 20 0 33 0 837 6 0 153 CONDENSER WATER CONNECTION...

Страница 17: ...CIRCUIT 1 4 IN VICTAULIC CONNECTIONS 4 0 102 ONLY REMOVE BRKT INLET FOR SHIPPING 88 KNOCKOUTS CONNECTIONS REMOVABLE 88 KNOCKOUTS CONTROL DISC HANDLE CONNECTIONS EVAPORATOR CG ON OPPOSITE SIDE OUTLET P...

Страница 18: ...OVE BRKT FOR SHIPPING ONLY EVAPORATOR INLET OUTLET 40 0 1016 56 4 1434 34 1 866 17 9 454 10 0 253 32 0 813 20 0 508 14 5 369 65 5 1664 35 2 894 40 2 1022 32 6 827 MAXIMUM OVERALL LENGTH IN MM CONDENSE...

Страница 19: ...DRAIN VENT 9 6 243 18 3 464 32 0 813 40 0 1016 20 0 508 12 5 318 H 41 0 1042 37 1 943 34 5 876 29 0 875 DIA MOUNTING HOLES 4 737 2 0 51 36 9 EVAP INLET OUTLET 938 13 3 337 35 8 908 Z POWER CONNECTIONS...

Страница 20: ...0 CONNECTIONS LIQUID 1524 2 5 64 2 0 6 1 155 34 0 864 40 0 1016 9 0 229 20 0 508 51 16 5 EVAP AND 30 0 30 4 772 88 LIQUID INLET OUTLET CONNECTIONS 1 38 DISCHARGE CONNECTIONS 98 8 178 7 0 2509 2334 91...

Страница 21: ...OSITE SIDE REMOVABLE DISCHARGE DISC HANDLE 88 KNOCKOUTS CONNECTIONS CONNECTIONS INLET LIQUID POWER CONNECTIONS REMOVE BRACKET 229 9 0 51 2 0 762 ISOLATOR HOLES 4 15 5 394 34 0 864 1 5 38 40 0 1016 4 0...

Страница 22: ...5 5 864 34 0 32 4 1 5 38 40 0 1016 4 0 101 823 30 0 40 1 1017 DISCHARGE CONNECTIONS B OUTLET LIQUID CONNECTIONS C INLET 50 9 1293 28 6 725 7 4 A 188 96 5 2451 26 0 659 971 38 2 188 7 4 2509 98 8 338 1...

Страница 23: ...VABLE DISC HANDLE POWER CONNECTIONS 88 KNOCKOUTS QTY 3 CONTROL CONNECTIONS 88 KNOCKOUTS ON OPPOSITE SIDE REMOVE BRKT FOR SHIPPING ONLY 154 0 3912 1 9 48 Y X CIRCUIT 1 CIRCUIT 2 MICROTECH II USER INTER...

Страница 24: ...69 119 3 3030 70 7 1796 20 9 530 34 2 867 17 4 443 34 0 863 96 2 2443 INLET OUTLET 2 12 O D DISCHARGE CONNECTIONS 1 38 O D LIQUID CONNECTIONS CIRCUIT 1 CIRCUIT 2 3 6 EVAPORATOR INLET OUTLET 90 2 3 DIS...

Страница 25: ...674 736 711 651 2658 2771 293 320 309 283 306 334 323 295 1206 1257 OPER WT LBS KG WGZ040DW WGZ045DW WGZ060DW LIFTING WEIGHT FOR EACH POINT LBS KG MOUNTING LOADS FOR EACH POINT LBS KG WGZ050DW WGZ030D...

Страница 26: ...0 533 2 0 51 30 0 762 2 0 51 75 ISOLATOR HOLES ARE IN THE BOTTOM OF THE BASE 19 CONTROL BOX EVAP WATER CONNECTIONS CIRCUIT 1 CIRCUIT 2 L4 L1 M4 M1 M2 L2 L3 M3 WGZ030 060D LESS COND 333611511002 p 2 o...

Страница 27: ...26 617 681 784 710 722 828 709 619 2792 2878 280 309 356 322 328 376 322 281 1266 1305 705 764 845 780 828 925 761 682 3094 3196 320 347 383 354 376 420 345 309 1403 1450 SHIP WT LBS KG OPER WT LBS KG...

Страница 28: ...332325502 332325502 332325503 332325503 WGZ DA Remote Condenser Isolator Kit Part Numbers Model Number 030 060 070 080 090 115 130 150 200 Spring Flex 332320506 332320507 332320508 332320509 33232051...

Страница 29: ...3 RP 3 RP 3 N A N A Green Green Black Black Lime Lime Lime Lime ID 900 ID 900 ID 510 ID 510 N A N A RP 3 RP 3 RP 3 RP 3 N A N A Green Green Black Black Lime Lime Lime Lime ID 900 ID 900 ID 510 ID 510...

Страница 30: ...2 7 47 21 4 136 0 3455 136 0 3455 63 4 1609 5 8 15 9 2539 1152 136 0 3455 63 4 1609 32 8 832 2606 1182 43 19 5 43 19 5 43 19 5 47 21 4 47 21 4 2484 1127 2564 1163 2615 1186 2631 1193 2719 1233 2408 10...

Страница 31: ...R410A Oper Charge lb kg 145 4 3 90 40 9 120 3048 120 3048 145 4 3 14 356 2 100 90 40 9 4515 2048 65 5 1664 149 4 3795 50 22 7 74 33 6 80 36 4 80 36 4 50 22 7 74 33 6 80 36 4 80 36 4 2658 1206 3555 161...

Страница 32: ...9 397 0 126 7 445 5 148 2 521 1 169 3 595 3 115 130 213 6 3 188 1 661 4 17 33 50 67 83 100 22 50 72 100 25 50 75 100 25 50 75 100 15 33 48 67 81 100 17 33 50 67 83 100 150 170 Oil Charge per compress...

Страница 33: ...0 3480 137 0 3480 137 0 3480 137 0 3480 653 4500 Field Field Field 653 4500 653 4500 653 4500 35 653 4500 653 4500 653 4500 110 3 3 110 3 3 1 8 6 8 2 110 3 3 27 50 77 100 50 6 177 9 50 55 31 2 109 7...

Страница 34: ...lare in mm Vent Drain UNIT DIMENSIONS Length in mm Width in mm Height in mm UNIT WEIGHTS Operating Weight lb kg Shipping Weight lb kg 56 9 215 4 75 0 1905 60 0 1524 60 0 1524 75 0 1905 75 0 1905 154 0...

Страница 35: ...either be fused or use an HACR type circuit breaker 2 All field wiring to unit power block or optional non fused disconnect switch must be copper 3 All field wire size values given in table apply to 7...

Страница 36: ...30 040 WGZ 045 090 WGZ 100 200 208 230 60 5 5 10 380 60 5 5 5 400 50 5 5 5 460 60 5 5 5 575 60 5 5 5 Voltage Hz Options Single Point Power Connection Only 208 230 60 100 380 60 65 400 50 65 460 60 65...

Страница 37: ...IM 1131 2 37 Electrical Data Figure 28 Field Wiring Diagram Packaged Units...

Страница 38: ...38 IM 1131 2 Electrical Data Figure 29 Field Wiring Diagram Units less condenser...

Страница 39: ...4 4 14 4 14 4 125 118 125 118 125 118 125 118 575V 14 7 14 7 14 7 14 7 12 0 12 0 12 0 12 0 100 100 100 100 208V 51 3 51 3 51 3 51 3 36 0 36 0 36 0 36 0 300 300 300 300 230V 51 3 51 3 51 3 51 3 32 8 32...

Страница 40: ...2 599 599 599 599 380V 69 2 69 2 69 2 69 2 47 7 47 7 47 7 47 7 358 358 358 358 400 460V 54 5 54 5 54 5 54 5 37 6 37 6 37 6 37 6 310 310 310 310 310 310 310 310 575V 49 4 49 4 49 4 49 4 30 4 30 4 30 4...

Страница 41: ...575V 63 3 6 AWG 1 0 75 70 575V 181 3 3 0 AWG 1 1 50 225 208V 218 3 4 0 AWG 1 2 00 250 208V 466 6 250 MCM 2 2 00 500 230V 218 3 4 0 AWG 1 2 00 250 230V 466 6 250 MCM 2 2 00 500 380V 115 3 2 AWG 1 1 25...

Страница 42: ...60 575V 115 3 2 AWG 1 1 25 125 208V 153 3 2 0 AWG 1 1 50 175 208V 354 6 4 0 AWG 1 3 00 400 230V 140 3 1 0 AWG 1 1 50 150 230V 320 3 400 MCM 1 2 50 350 380V 84 3 4 AWG 1 1 00 100 380V 203 3 4 0 AWG 1...

Страница 43: ...52 3 6 AWG 1 0 75 70 575V 45 3 8 AWG 1 0 50 60 45 3 8 AWG 1 0 50 60 208V 115 3 2 AWG 1 1 25 150 126 3 1 AWG 1 1 25 175 230V 115 3 2 AWG 1 1 25 150 126 3 1 AWG 1 1 25 175 380V 61 3 6 AWG 1 0 75 80 77...

Страница 44: ...123 3 1 AWG 1 1 25 175 123 3 1 AWG 1 1 25 175 575V 111 3 2 AWG 1 1 25 150 111 3 2 AWG 1 1 25 150 208V 277 3 300 MCM 1 2 50 350 277 3 300 MCM 1 2 50 350 230V 277 3 300 MCM 1 2 50 350 277 3 300 MCM 1 2...

Страница 45: ...0 50 40 31 3 10 AWG 1 0 50 40 208V 81 3 4 AWG 1 1 00 110 99 3 3 AWG 1 1 00 125 230V 74 3 4 AWG 1 1 00 100 90 3 3 AWG 1 1 00 125 380V 44 3 8 AWG 1 0 50 60 57 3 6 AWG 1 0 75 80 400 460V 38 3 8 AWG 1 0 5...

Страница 46: ...0 460V 85 3 4 AWG 1 1 00 110 85 3 4 AWG 1 1 00 110 575V 68 3 4 AWG 1 1 00 90 68 3 4 AWG 1 1 00 90 208V 211 3 4 0 AWG 1 2 00 250 211 3 4 0 AWG 1 2 00 250 230V 190 3 3 0 AWG 1 2 00 225 190 3 3 0 AWG 1 2...

Страница 47: ...3 0 380V 175A 1 2 0 14 125A 1 1 3 0 3 380V 380A 1 500 4 400A 2 500 3 0 400 460V 175A 1 2 0 14 100A 1 1 1 0 10 400 460V 380A 1 500 4 250A 1 350 6 575V 175A 1 2 0 14 100A 1 1 1 0 10 575V 380A 1 500 4 2...

Страница 48: ...00A 1 1 1 0 10 380V 380A 1 500 4 250A 1 350 6 400 460V 175A 1 2 0 14 100A 1 1 1 0 10 400 460V 175A 1 2 0 14 250A 1 350 6 575V 175A 1 2 0 14 100A 1 1 1 0 10 575V 175A 1 2 0 14 125A 1 1 3 0 3 208V 175A...

Страница 49: ...A 1 2 0 14 125A 1 1 3 0 3 380V 175A 1 2 0 14 100A 1 1 1 0 10 175A 1 2 0 14 100A 1 1 1 0 10 400 460V 175A 1 2 0 14 100A 1 1 1 0 10 175A 1 2 0 14 100A 1 1 1 0 10 575V 175A 1 2 0 14 100A 1 1 1 0 10 175A...

Страница 50: ...50A 1 350 6 380A 1 500 4 250A 1 350 6 380V 175A 1 2 0 14 250A 1 350 6 175A 1 2 0 14 250A 1 350 6 400 460V 175A 1 2 0 14 125A 1 1 3 0 3 175A 1 2 0 14 125A 1 1 3 0 3 575V 175A 1 2 0 14 100A 1 1 1 0 10 1...

Страница 51: ...1 1 1 0 10 400 460V 175A 1 2 0 14 100A 1 1 1 0 10 175A 1 2 0 14 100A 1 1 1 0 10 575V 175A 1 2 0 14 100A 1 1 1 0 10 175A 1 2 0 14 100A 1 1 1 0 10 208V 175A 1 2 0 14 100A 1 1 1 0 10 175A 1 2 0 14 100A 1...

Страница 52: ...A 1 350 6 175A 1 2 0 14 250A 1 350 6 380V 175A 1 2 0 14 100A 1 1 1 0 10 175A 1 2 0 14 100A 1 1 1 0 10 400 460V 175A 1 2 0 14 100A 1 1 1 0 10 175A 1 2 0 14 100A 1 1 1 0 10 575V 175A 1 2 0 14 100A 1 1 1...

Страница 53: ...wiring is completed per Daikin Applied diagrams 12 Verify that all mechanical and electrical inspections by code authorities have been completed 13 Make sure all auxiliary load and control equipment i...

Страница 54: ...compressor discharge valves until backseated Always replace valve seal caps 4 Open the manual liquid line shutoff valves 5 Check circuit breakers They must be in the off position 6 Check to see that t...

Страница 55: ...tend to loosen due to normal heating and cooling of the wire Compressor Lubrication The oil level should be watched carefully upon initial start up and regularly thereafter All tandem and triple comp...

Страница 56: ...e to power failure conditions phase loss and phase reversal Whenever any of these conditions occur an input relay is deactivated disconnecting power to the thermostatic control circuit The compressor...

Страница 57: ...sure alarms X III Condenser B Test water quality X C Clean condenser tubes or as required X D Eddycurrent test X E Seasonal protection X IV Evaporator B Test water quality X C Clean evaporator tubes o...

Страница 58: ...heat is the difference between refrigerant temperature as it leaves the evaporator and the saturation temperature corresponding to the evaporator pressure All WGZ chillers are factory set for between...

Страница 59: ...mbient conditions Check condenser rating tables against the operation Excessive load Reduce load or add additional equipment Expansion valve overfeeding Check remote bulb Regulate superheat Lack of re...

Страница 60: ...UP PROCEDURE II Pre Start Up Checklist Pre Start Up Checklist All NO checks require an explanation under Description Please check yes or no YES NO A Is the unit free of visible shipping damage corrosi...

Страница 61: ...Air Temperature ________ F C F C M Are all service and liquid line valves open N Have all shipping hold down plates been removed O Has a flow switch been installed per the IM bulletin P Has the chill...

Страница 62: ...quid Line Temperature F C F C Subcooling F C F C G Circuit 2 Refrigerant Temperatures Saturated Evaporator Temperature F C F C Suction Line Temperature F C F C Suction Superheat F C F C Saturated Cond...

Страница 63: ...g kPa psig kPa Q High Pressure Cut Out psig kPa psig kPa R Unit Type S Number of Compressors T Number of Stages U Number of Fan Stages V Software Version VII FOR HEAT RECOVERY CHILLERS ONLY Must Be Ta...

Страница 64: ...lied equipment is sold pursuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details To find your local...

Отзывы: