OMM WCT
Centrifugal Chillers
D-EOMWC01302-16EN - 48/84
Table 18, Problem Alarm Description
Description
Occurs When:
Action Taken
Reset
Low Evaporator Pressure
– Inhibit Loading
Pressure < Low Evap Pressure
–
Inhibit setpoint
Inhibit loading
Evap Press rises
above (SP + 3psi)
Low Evaporator Pressure
– Unload
Pressure < Low Evap Pressure
–
Unload setpoint
Unload
Evap Press rises
above (SP + 3psi)
Evaporator Freeze Protect
Evap Sat Refr Temp < Evaporator
Freeze SP
Start evaporator
pump
Temp > (Evaporator
Freeze SP + 2°F)
Condenser Freeze Protect
Cond Sat Refr Temp < Condenser
Freeze SP
Start condenser
pump
Temp > (Condenser
Freeze SP + 2°F)
High Discharge
Temperature
Temperature > High Discharge
Temperature-Load SP AND Suction
superheat < 15°F
Load
Temp < (High Dsch
Temp Load SP
– 3°F)
OR Superheat > 18°F
A warning is annunciated whenever an abnormal condition exists which does not affect chiller operation.
Table 19, Warning Alarm Description
WARNING
CONDITION
Liquid Line Refrigerant
Temperature Sensor Fall Warning
Sensor is shorted or open
Entering Evaporator Water
Temperature Sensor Fall Warning
Sensor is shorted or open
Leaving Condenser Water
Temperature Sensor Fail Warning
Sensor is shorted or open
Entering Condenser Water
Temperature Sensor Fail Warning
Sensor is shorted or open
Evaporator Pressure Sensor Fault
Sensor is shorted or open