RXYQ8~18P7W1BR1
VRVIII System air conditioner
4PW44039-1D
Installation manual
10
8.1.
Internal wiring – Parts table
Refer to the wiring diagram sticker on the unit. The abbreviations
used are listed below:
A1P~A7P .............Printed circuit board
BS1~BS5 .............Push button switch (mode, set, return, test, reset)
C1,C63,C66 .........Capacitor
DS1,DS2..............Dip switch
E1HC~E3HC .......Crankcase heater
F1U ......................Fuse (250 V, 8 A, B) (A4P, A8P)
F1U,F2U ..............Fuse (250 V, 3.15 A, T) (A1P)
F5U ......................Field fuse
F400U ..................Fuse (250 V, 6.3 A, T) (A2P)
H1P~H8P.............Pilot lamp (service monitor - orange)
H2P: Under preparation or in test operation when
blinking
H2P: Malfunction detection when light up
HAP .....................Pilot lamp (service monitor - green)
K1 ........................Magnetic relay
K2 ........................Magnetic contactor (M1C)
K2M,K3M .............Magnetic contactor (M2C, M3C)
K1R,K2R..............Magnetic relay (K2M, K3M)
K3R~K5R.............Magnetic relay (Y1S~Y3S)
K7R~K9R.............Magnetic relay (E1HC~E3HC)
L1R ......................Reactor
M1C~M3C ...........Motor (compressor)
M1F,M2F ..............Motor (fan)
PS ........................Switching power supply (A1P, A3P)
Q1DI ....................Earth leakage breaker (field supply)
Q1RP ...................Phase reversal detection circuit
R1T ......................Thermistor (fin) (A3P)
R1T ......................Thermistor (air) (A1P)
R2T ......................Thermistor (suction)
R4T ......................Thermistor (heat exchanger-deicer)
R5T ......................Thermistor (heat exchanger-outlet)
R6T ......................Thermistor (liquid pipe)
R7T ......................Thermistor (accumulator)
R10 ......................Resistor (current sensor) (A4P, A8P)
R31T~R33T .........Thermistor (discharge) (M1C~M3C)
R50,R59...............Resistor
R95 ......................Resistor (current limiting)
S1NPH.................Pressure sensor (high)
S1NPL .................Pressure sensor (low)
S1PH,S3PH .........Pressure switch (high)
T1A ......................Current sensor (A6P, A7P)
SD1......................Safety devices input
V1R......................Power module (A4P, A8P)
V1R,V2R..............Power module (A3P)
X1A,X4A ..............Connector (M1F, M2F)
X1M .....................Terminal strip (power supply)
X1M .....................Terminal strip (control) (A1P)
X1M .....................Terminal strip (A5P)
Y1E,Y2E ..............Expansion valve (electronic type) (main, subcool)
Y1S ......................Solenoid valve (hotgas bypass)
Y2S ......................Solenoid valve (oil return)
Y3S ......................Solenoid valve (4 way valve)
Z1C~Z7C .............Noise filter (ferrite core)
Z1F ......................Noise filter (with surge absorber)
L1,L2,L3...............Live
N.......................... Neutral
............ Field wiring
............... Terminal strip
....................... Connector
...................... Terminal
....................... Protective earth (screw)
BLK ..................... Black
BLU ..................... Blue
BRN..................... Brown
GRN .................... Green
GRY..................... Grey
ORG .................... Orange
PNK..................... Pink
RED..................... Red
WHT .................... White
YLW..................... Yellow
8.2.
Optional parts cool/heat selector
S1S ..................... Selector switch (fan, cool/heat)
S2S ..................... Selector switch (cool/heat)
NOTE
■
This wiring diagram only applies to the outdoor
unit.
■
When using the option adaptor, refer to the
installation manual.
■
Do not operate the unit by short-circuiting
protection device S1PH.
■
Refer to the installation manual, for connection
wiring to BP-outdoor transmission F1-F2.
■
When using the central control system, connect
outdoor-outdoor transmission F1-F2.
NOTE
■
Use copper conductors only.
■
For connection wiring to the central remote
controller, refer to the installation manual of the
central remote controller.
■
Use insulated wire for the power cord.