INSTALLATION AND

OPERATION MANUAL

 

FXLQ20P7VEB
FXLQ25P7VEB
FXLQ32P7VEB
FXLQ40P7VEB
FXLQ50P7VEB
FXLQ63P7VEB

 

 System air conditioners

Содержание VRV

Страница 1: ...INSTALLATION AND OPERATION MANUAL FXLQ20P7VEB FXLQ25P7VEB FXLQ32P7VEB FXLQ40P7VEB FXLQ50P7VEB FXLQ63P7VEB System air conditioners...

Страница 2: ...UT D F1 F2 F1 F2 Control box L N L N P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 3 1 4 2 L N L N L N L N 2 1 2 3 7 9 8 10 4 5 6 NOTES L N IN D OUT D...

Страница 3: ...em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enlig...

Страница 4: ...Where volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves exist Control system may malfunction Where the air contains high levels of salt such as a...

Страница 5: ...asures Keep indoor unit outdoor unit power supply wiring and transmission wiring at least 1 meter away from televisions and radios This is to prevent image interference and noise in those electrical a...

Страница 6: ...fasten to the wall using the holes provided or fasten to the floor with a field supplied floor fastener Wallmounted installation 1 Positioning of holes for fastening to the wall Unit of measurement m...

Страница 7: ...propriate tightening torque Overtightening may damage the flare and cause leaks When connecting the flare nut coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turn...

Страница 8: ...ne A main switch or other means for disconnection having a contact separation in all poles must be incorporated in the fixed wiring in accordance with relevant local and national legislation Note that...

Страница 9: ...the terminals Keep wiring in neat order so that they do not obstruct other equipment such as popping open the control box cover Make sure the cover closes tight Incomplete connections could result in...

Страница 10: ...g rods or crossground with telephones Improper grounding could result in electric shock 1 Control box 2 Power supply wiring field supply 3 Remote controller wiring field supply 4 Transmission wiring f...

Страница 11: ...the wiring again MAINTENANCE Wire specification Sheathed vinyl cord or cable 2 wire Gauge 0 75 1 25 mm2 Length Max 100 m External terminal Contact that can ensure the minimum applicable load of 15 V D...

Страница 12: ...g the front as a leverage To install use the opposite method How to clean the drain strainer The drain strainer clears dirt out of the drain water and prevents the piping from clogging However if the...

Страница 13: ...d of other parts must be done in accordance with relevant local and national legislation WIRING DIAGRAM A1P PRINTED CIRCUIT BOARD C1 CAPACITOR M1F F1U FUSE B 5 A 250 V HAP LIGHT EMITTING DIODE SERVICE...