16 Configuration
Installation and operation manual
18
FXMQ-A
VRV system air conditioner
3P701545-1 – 2022.07
▪ T1/T2 input setting
Setting: External static pressure
INFORMATION
▪ The fan speed of the indoor unit is preset to ensure the
standard external static pressure.
▪ To set a higher or lower external static pressure, reset
the initial setting with the user interface.
Settings for external static pressure can be achieved in 2 ways:
▪ Using the airflow automatic adjustment function
▪ Using the user interface
To set external static pressure by airflow automatic adjustment
function
NOTICE
▪ Do NOT adjust the dampers during the fan only
operation for airflow automatic adjustment.
▪ For the external static pressure higher than 100 Pa, do
NOT use airflow automatic adjustment function.
▪ If the ventilation paths have been changed, perform the
airflow automatic adjustment again.
▪ Test run MUST be done with a dry coil, run the unit for 2 hours
with fan only to dry the coil.
▪ Check if the power supply wiring, duct, air filter are properly
attached. If the closing damper is installed in the unit, make sure it
is open.
▪ If there is more than one air inlet and outlet, adjust the dampers so
that the airflow rate of each air inlet and outlet is conform with the
designed airflow rate.
1
Operate the unit in
fan only mode
prior to using the airflow
automatic adjustment function.
2
Stop
the air conditioning unit.
3
Set the value
number “—“ to 03 for
M
11(21) and
SW
7.
4
Start
the air conditioning unit.
Result:
The operation lamp lights up and the unit starts the fan
operation for airflow automatic adjustment.
5
After airflow automatic adjustment is finished (air conditioning
unit will stop) check if the value number “—“ is set to 02. If there
is no change, perform the setting again.
Setting content:
Then
(1)
M
SW
—
Airflow adjustment is OFF
11(21)
7
01
Completion of automatic airflow adjustment
02
Start of automatic airflow adjustment
03
To set external static pressure by the user interface
Check the indoor unit setting: the value number “—“ must be set to
01 for
M
11(21) and
SW
7.
1
Change the value number “—“ according to the external static
pressure of the duct to be connected as in table below.
M
SW
—
External static pressure (Pa)
(1)
13(23)
6
01
50
02
75
03
100
04
115
05
130
06
150
07
160
08
175
09
190
10
200
11
210
12
220
13
230
14
240
15
250
Setting: Air volume when thermostat control is OFF
This setting must correspond with the needs of the user. It
determines the fan speed of the indoor unit during thermostat OFF
condition.
1
If you have set the fan to operate, set the air volume speed:
If you want…
Then
(1)
M
SW
—
During thermostat
OFF at cooling
operation
LL
(2)
12 (22)
6
01
Setup volume
(2)
02
OFF
(a)
03
Monitoring 1
(2)
04
Monitoring 2
(2)
05
During thermostat
OFF at heating
operation
LL
(2)
12 (22)
3
01
Setup volume
(2)
02
OFF
(a)
03
Monitoring 1
(2)
04
Monitoring 2
(2)
05
(a)
Only use in combination with optional remote sensor or when
setting
M
10 (20),
SW
2, —
03 is used.
Setting: Time to clean air filter
This setting must correspond with the air contamination in the room.
It determines the interval at which
"Time to clean filter"
notification
is displayed on the user interface.
If you want an interval of…
(air contamination)
Then
(1)
M
SW
—
±2500 h (light)
10 (20)
0
01
±1250 h (heavy)
02
Notification ON
3
01
Notification OFF
02
(1)
Field settings are defined as follows:
•
M
: Mode number –
First number
: for group of units –
Number between brackets
: for individual unit
•
SW
: Setting number
• —: Value number
•
: Default
(2)
Fan speed:
•
LL
: Low fan speed (set during thermostat OFF)
•
L
: Low fan speed (set by the user interface)
•
Setup volume
: The fan speed corresponds to the speed the user has set (low, medium, high) using the fan speed button on the user
interface.
•
Monitoring 1, 2
: The fan is OFF, but runs for a short time every 6 minutes to detect the room temperature by
LL
(Monitoring 1) or by
L
(Monitoring 2).