Outline of Control (Indoor Unit)
Part 4 Functions and Control
81
3.2.2 With Optional Infrared Presence/Floor Sensor
The thermostat ON/OFF condition is determined by the difference between the remote
controller set temperature and the detected temperature around people.
Normal operation
Cooling operation
Dry operation
When Tro ≤ 24.5°C
When Tro > 24.5°C
ΔT = Detected room temperature – Remote controller set temperature
Tro: Detected room temperature at the start of dry operation
Tr: Determined by the room temperature detected by the thermistor
Control range of temperature around people
When the floor temperature is very low, operation using the temperature around people may
cause the suction air temperature to operate outside of use range.
To avoid the above condition, a limit based on the suction air temperature is set for the use
range of the temperature around people.
Cooling operation
When the floor temperature is lower than suction air thermistor detection temperature
(R1T), R1T will be treated as the control target temperature for operation.
When the temperature around people is 15°C or lower, R1T will be treated as the control
temperature for operation.
3.3 Automatic Airflow Rate Control
The automatic airflow rate control (Five steps from H to L) is based on the difference between
control target temperature and set temperature.
1. LL airflow for FXFSQ-AR
Thermostat OFF
Normal operation
(Thermostat ON)
Δ
T ≤
–1.0°C
Δ
T ≥
+
1.0°C
Thermostat OFF
Dry operation
Tr
<
Tro – 1.0°C
Tr
>
Tro + 1.0°C
Thermostat OFF
Dry operation
Tr
<
Tro – 1.5°C
Tr
>
Tro + 0.5°C
Conditions
When airflow rate is set
Automatic airflow rate
Cooling
Thermostat ON
Set
The fan tap is determined
by the difference between control target
temperature and set temperature.
Thermostat OFF
Set (
1)
The fan keeps rotating at
the speed as just before
the thermostat off (
1)
Program dry
Thermostat ON
L
L
Thermostat OFF
OFF
OFF
Fan
Set
M
Stop
OFF
OFF
Содержание VRV S RXQ4/5ARV1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...