Part 6 Service Diagnosis
337
Note(s)
Reference
6. Check
6.1 High Pressure Check
CHECK 1
Referring to the Fault Tree Analysis (FTA) shown below, probe the defective points.
CHECK 6
Refer to page 345.
Rise in high
pressure
Local
pressure
rise
High pipe
resistance
Stop valve closed
Bent or crashed pipe
Clogging of foreign
particles
Check to be sure the stop valve is open.
Conduct visual checks for pipe conditions.
Is there any temperature difference caused before
and after the filter or branch pipe?
In cooling
If the outdoor unit electronic
expansion valve is throttled:
(
1)
Defective outdoor
unit electronic
expansion valve
Defective valve coil
Defective valve body
Are the coil resistance and insulation normal?
A temperature difference in
excess of 10
C between the
inlet and the outlet is deemed
to be abnormal.
Defective
control
Defective high pressure sensor
Defective outdoor unit main PCB
Are the electrical characteristics normal?
Is the pressure value checked with the Service Checker
corresponding to the measurement of the pressure sensor?
Defective
high
pressure
control
In cooling
High suction
air
temperature
of the
condenser
High suction
air temperature
of outdoor unit
Short circuit
High outdoor air temperature
Is the suction air temperature less than 43
C?
Is the outdoor air temperature less than 43
C?
Degradation
in condensing
capacity
Dirty condenser
Mixing of non-condensable gas
Is the heat exchanger clogged? (In cooling)
Is air or else mixed in the refrigerant system?
Decreased
fan airflow
rate
Decreased
fan
output
Defective fan
motor
Can the fan motor be rotated with hands?
Are the motor coil resistance and
insulation normal?
If a spare PCB is mounted, is the capacity
setting properly made?
Defective outdoor
unit main PCB
(Including
capacity setting)
High air
passage
resistance
Dirty filter
Is the air filter clogged?
Obstacle
Is there any obstacle in the air passage?
Excessive refrigerant charging
Refer to
CHECK 6
1. In cooling, the normal state of the outdoor unit electronic expansion valve (main)
is fully open.
Содержание VRV S RXMQ10ARY1
Страница 1: ...Service Manual Cooling Only 50 60 Hz RXQ4 5ARV1 RXMQ6ARV1 RXMQ8 10 12ARY1 SiAF332111E...
Страница 349: ...SiAF332111E Check Part 6 Service Diagnosis 343 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 366: ...SiAF332111E 360 Part 7 Appendix 1 Wiring Diagrams 361 1 1 Outdoor Unit 361 1 2 VRV Indoor Unit 366 Part 7 Appendix...
Страница 369: ...SiAF332111E Wiring Diagrams Part 7 Appendix 363 RXMQ6ARV1 C 3D137051...
Страница 370: ...Wiring Diagrams SiAF332111E 364 Part 7 Appendix RXMQ8ARY1 C 3D137060...
Страница 371: ...SiAF332111E Wiring Diagrams Part 7 Appendix 365 RXMQ10 12ARY1 3D121610B...
Страница 375: ...SiAF332111E Wiring Diagrams Part 7 Appendix 369 FXMQ40 50 63 80 100ARV1 3D127112 04 59...
Страница 376: ...Wiring Diagrams SiAF332111E 370 Part 7 Appendix 1 2 4 Wall Mounted FXAQ20 25 32PVE FXAQ40 50 63PVER1 C 3D076498B...