Outline of Control (Indoor Unit)
SiME332106E
74
Part 4 Functions and Control
8.5 Auto Draft Reducing Control (FXFSQ-AR only)
In the case where both this control is activated and auto airflow direction control (eco full
automatic control) is set, when human presence is detected, the airflow direction is
automatically set to horizontal (P0) to reduce discomfort by direct airflow.
This control works for each airflow outlet individually.
Note: This function is inoperative for the airflow outlet where an individual airflow direction is set.
8.6 Eco Full Automatic Control (FXFSQ-AR only)
This is a generic term for the setting where both fan speed and airflow direction are set to
"Auto". For detailed control contents, refer to
Automatic Airflow Rate Control
and
Airflow
Direction Control
.
P0
P1
P2
P3
P4
Indoor
u
nit
AIR
Flap position
(Horizontal
v
ie
w
)
P0 (horizontal)
When presence is detected
Absence continues for 5 mins
Airflow direction by auto airflow direction
Cooling: P0 or P1
Heating: P3 or P4
Содержание VRV RXYMQ-A Series
Страница 1: ...Service Manual RXYMQ A Series Heat Pump 50 60 Hz SiME332106E...
Страница 283: ...SiME332106E Check Part 6 Service Diagnosis 277 PCB and Circuit Diagram U V W L3B L2B L1B P1 P2 N32...
Страница 296: ...SiME332106E 290 Part 7 Appendix 1 Wiring Diagrams 291 1 1 Outdoor Unit 291 1 2 VRV Indoor Unit 293 Part 7 Appendix...
Страница 297: ...SiME332106E Wiring Diagrams Part 7 Appendix 291 1 Wiring Diagrams 1 1 Outdoor Unit RXYMQ4AVMK C 3D133942...
Страница 298: ...Wiring Diagrams SiME332106E 292 Part 7 Appendix RXYMQ4 5 6AYFK C 3D133944A...
Страница 303: ...SiME332106E Wiring Diagrams Part 7 Appendix 297 FXMQ40 50 63 80 100ARV1 3D127112 04 59...