2
|
Troubleshooting
Service manual
114
REYQ8~20+REMQ5U7Y1B
VRV IV+ Heat Recovery
ESIE18-15B – 2020.05
2.3.100 L4-01-02-03 – Inverter PCB A3P high fin temperature
Main error code
Sub error code
Unit
L4
01
Main
02
Sub 1
03
Sub 2
INFORMATION
Main, Sub 1 and Sub 2 indications are relevant in multiple outdoor unit
configurations. Main outdoor unit is the unit to which F1‑F2 IN transmission line is
connected. Main, Sub 1 and Sub 2 outdoor units can be identified by field setting
1‑00.
Trigger
Effect
Reset
Thermistor located inside
the power module of the
inverter PCB for
compressor detects a
temperature higher than
a certain value.
Unit will stop operating.
Manual reset via remote
controller.
Outdoor unit power reset.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
Prerequisite:
Stop the unit operation via the central controller.
1
Turn OFF the respective circuit breaker.
DANGER: RISK OF ELECTROCUTION
Confirm the rectifier voltage is below 10 V DC before proceeding, see
2
Check that the thermal interface grease is applied properly on the (PCB or
refrigerant piping) contact surface of the heat sink. Adjust if needed.
Possible cause:
Thermal interface grease NOT applied properly on the heat
sink.
3
Check if heat sink plate is correctly fixed with screws.
Possible cause:
Heat sink plate not correctly installed.
4
Check (by touching) if refrigerant is flowing through the radiant cooling
refrigerant circuit. The radiant cooling refrigerant circuit should be warm if
refrigerant is flowing. If no refrigerant flow, perform a check of the liquid
cooling expansion valve, see
244].
Possible cause:
No refrigerant flow through the radiant cooling refrigerant
circuit.
5
Perform a check of the liquid cooling expansion valve. See
244].
Possible cause:
Faulty liquid cooling expansion valve.
6
Check ambient temperature. Check if outdoor unit location temperature
differs drastically.