7 Maintenance and service

Installation and operation manual

9

RXYTQ
VRV IV+ heat pump for high ambient temperatures
4P546223-1C – 2021.11

7

Maintenance and service

NOTICE

NEVER  inspect  or  service  the  unit  by  yourself.  Ask  a
qualified service person to perform this work.

WARNING

NEVER  replace  a  fuse  with  a  fuse  of  a  wrong  ampere
ratings  or  other  wires  when  a  fuse  blows  out.  Use  of  wire
or copper wire may cause the unit to break down or cause
a fire.

CAUTION

Do  NOT  insert  fingers,  rods  or  other  objects  into  the  air
inlet  or  outlet.  Do  NOT  remove  the  fan  guard.  When  the
fan is rotating at high speed, it will cause injury.

CAUTION

After  a  long  use,  check  the  unit  stand  and  fitting  for
damage. If damaged, the unit may fall and result in injury.

NOTICE

Do  NOT  wipe  the  controller  operation  panel  with  benzine,
thinner,  chemical  dust  cloth,  etc.  The  panel  may  get
discoloured  or  the  coating  peeled  off.  If  it  is  heavily  dirty,
soak  a  cloth  in  water-diluted  neutral  detergent,  squeeze  it
well  and  wipe  the  panel  clean.  Wipe  it  with  another  dry
cloth.

7.1

About the refrigerant

This  product  contains  fluorinated  greenhouse  gases.  Do  NOT  vent
gases into the atmosphere.

Refrigerant type: R410A

Global warming potential (GWP) value: 2087.5

NOTICE

Applicable  legislation  on 

fluorinated  greenhouse  gases

requires  that  the  refrigerant  charge  of  the  unit  is  indicated
both in weight and CO

2

 equivalent.

Formula  to  calculate  the  quantity  in  CO

2

  equivalent

tonnes:

  GWP  value  of  the  refrigerant  ×  total  refrigerant

charge [in kg] / 1000

Please contact your installer for more information.

WARNING

The refrigerant in the system is safe and normally does not
leak. If the refrigerant leaks in the room, contact with a fire
of  a  burner,  a  heater  or  a  cooker  may  result  in  a  harmful
gas.

Turn  off  any  combustible  heating  devices,  ventilate  the
room and contact the dealer where you purchased the unit.

Do  NOT  use  the  system  until  a  service  person  confirms
that the portion where the refrigerant leaks is repaired.

7.2

After-sales service and warranty

7.2.1

Warranty period

▪ This  product  includes  a  warranty  card  that  was  filled  in  by  the

dealer  at  the  time  of  installation.  The  completed  card  has  to  be
checked by the customer and stored carefully.

▪ If repairs to the product are necessary within the warranty period,

contact your dealer and keep the warranty card at hand.

7.2.2

Recommended maintenance and
inspection

Since  dust  collects  when  using  the  unit  for  several  years,
performance  of  the  unit  will  deteriorate  to  some  extent.  As  taking
apart and cleaning interiors of units requires technical expertise and
in  order  to  ensure  the  best  possible  maintenance  of  your  units,  we
recommend to enter into a maintenance and inspection contract on
top  of  normal  maintenance  activities.  Our  network  of  dealers  has
access  to  a  permanent  stock  of  essential  components  in  order  to
keep your unit in operation as long as possible. Contact your dealer
for more information.

When asking your dealer for an intervention, always state:

▪ The complete model name of the unit.

▪ The manufacturing number (stated on the nameplate of the unit).

▪ The installation date.

▪ The symptoms or malfunction, and details of the defect.

WARNING

▪ Do  NOT  modify,  disassemble,  remove,  reinstall  or

repair  the  unit  yourself  as  incorrect  dismantling  or
installation  may  cause  an  electrical  shock  or  fire.
Contact your dealer.

▪ In case of accidental refrigerant leaks, make sure there

are  no  naked  flames.  The  refrigerant  itself  is  entirely
safe,  non-toxic  and  non-combustible,  but  it  will
generate  toxic  gas  when  it  accidentally  leaks  into  a
room  where  combustion  air  from  fan  heaters,  gas
cookers,  etc.  is  present.  ALWAYS  have  qualified
service personnel confirm that the point of leakage has
been repaired or corrected before resuming operation.

8

Troubleshooting

If one of the following malfunctions occur, take the measures shown
below and contact your dealer.

WARNING

Stop  operation  and  shut  OFF  the  power  if  anything
unusual occurs (burning smells etc.).

Leaving  the  unit  running  under  such  circumstances  may
cause  breakage,  electrical  shock  or  fire.  Contact  your
dealer.

The system MUST be repaired by a qualified service person.

Malfunction

Measure

If a safety device such as a fuse, a
breaker or an earth leakage breaker
frequently actuates or the ON/OFF
switch does NOT properly work.

Turn OFF the main power
switch.

If water leaks from the unit.

Stop the operation.

The operation switch does NOT work
well.

Turn OFF the power
supply.

If the user interface display indicates the
unit number, the operation lamp flashes
and the malfunction code appears.

Notify your installer and
report the malfunction
code.

If  the  system  does  NOT  operate  properly  except  for  the  above
mentioned cases and none of the above mentioned malfunctions is
evident,  investigate  the  system  in  accordance  with  the  following
procedures.

Содержание VRV IV+ RXYTQ10U5/U7YF

Страница 1: ...tion manual VRV IV heat pump for high ambient temperatures English Installation and operation manual VRV IV heat pump for high ambient temperatures RXYTQ8U5 U7YF RXYTQ10U5 U7YF RXYTQ12U5 U7YF RXYTQ14U...

Страница 2: ...oor unit fan does not spin 12 8 2 15 Symptom The display shows 88 12 8 2 16 Symptom The compressor in the outdoor unit does not stop after a short heating operation 12 8 2 17 Symptom The inside of an...

Страница 3: ...rence data Detailed step by step instructions and background information for basic and advanced usage Format Digital files on http www daikineurope com support and manuals product information Latest r...

Страница 4: ...phase advancing capacitor will reduce performance and may cause accidents WARNING All wiring MUST be performed by an authorised electrician and MUST comply with the applicable legislation Make electri...

Страница 5: ...household waste If a chemical symbol is printed beneath the symbol this chemical symbol means that the battery contains a heavy metal above a certain concentration Possible chemical symbols are Pb le...

Страница 6: ...ge electrical shock or fire Contact your dealer WARNING The refrigerant in the system is safe and normally does not leak If the refrigerant leaks in the room contact with a fire of a burner a heater o...

Страница 7: ...cooled coil increases over time restricting the energy transfer to the outdoor unit s coil Heating capability decreases and the system needs to go into defrost operation to be able to remove frost fr...

Страница 8: ...details To stop 5 Press the ON OFF button on the user interface once again Result The operation lamp goes out and the system stops operating NOTICE Do not turn off power immediately after the unit st...

Страница 9: ...the warranty card at hand 7 2 2 Recommended maintenance and inspection Since dust collects when using the unit for several years performance of the unit will deteriorate to some extent As taking apart...

Страница 10: ...ction code reset the code by pushing the ON OFF button If not ask your installer for advice Main code Contents External protection device was activated EEPROM failure indoor Drain system malfunction i...

Страница 11: ...another indoor unit is in heating operation if the button is pressed 8 2 5 Symptom The fan direction does not correspond to the setting The fan direction does not correspond with the user interface d...

Страница 12: ...30 10 20 19 9 29 39 38 28 8 18 17 7 27 37 36 26 6 16 15 5 25 35 34 23 24 4 3 2 1 INSTALLATION MODELNAME No 12 13 14 50 49 48 47 46 45 60 59 58 57 56 64 63 62 61 11 22 21 33 32 31 44 43 42 41 55 54 53...

Страница 13: ...e outdoor unit is designed to work in heating mode at ambient temperatures from 20 C WB to 15 5 C WB and in cooling mode at ambient temperatures from 5 C DB to 52 C DB Unit weights Model Total net wei...

Страница 14: ...the grey marked area 729 613 929 AB AA a mm Minimum foundation a Anchor point 4 HP AA AB 8 766 992 10 16 1076 1302 Fasten the unit in place using four foundation bolts M12 It is best to screw in the...

Страница 15: ...D capacity index of unit 1 capacity index of unit 2 E Piping between refrigerant branch kit and indoor unit Pipe size for direct connection to indoor unit must be the same as the connection size of th...

Страница 16: ...ollowing table in accordance with the total capacity of all the indoor units connected below the refnet header Indoor unit capacity index 2 pipes 200 KHRQ22M29H 200 x 290 290 x 640 KHRQ22M64H a 640 KH...

Страница 17: ...r paint to prevent rusting When passing electrical wiring through the knockout holes wrap the wiring with protective tape to prevent damage 14 2 2 To connect the refrigerant piping to the outdoor unit...

Страница 18: ...en the 19 1 25 4 mm stop valve turn the hexagonal wrench until a torque between 27 and 33 N m is achieved Inadequate torque may cause leakage of refrigerant and breakage of the stop valve cap NOTICE P...

Страница 19: ...oil has dripped out before continuing with the connection of the field piping in case the recovery was not complete 14 3 Checking the refrigerant piping 14 3 1 About checking the refrigerant piping Re...

Страница 20: ...to the unit If not see also the flow chart earlier described in this chapter see 14 3 1 About checking the refrigerant piping 419 14 3 4 To perform a leak test The leak test must satisfy the specific...

Страница 21: ...is as normal see 16 1 4 To access mode 1 or 2 429 If a malfunction code is present see 19 1 Solving problems based on error codes 433 NOTICE Make sure all connected indoor units are recognised see 1 1...

Страница 22: ...outdoor unit to the farthest indoor unit b Total CR Total indoor unit capacity connection ratio c In case of a multi outdoor unit system add the sum of the individual outdoor unit charge factors Metr...

Страница 23: ...charging refrigerant Step 1 Calculate additional refrigerant charge amount R kg Refrigerant overcharge happened recover refrigerant to reach R Q Step 2 Open valves C and B to the liquid line Execute...

Страница 24: ...out outdoor unit operation If Then The additional refrigerant amount is smaller than 10 kg Perform steps 2 3 The additional refrigerant charge is larger than 10 kg Perform steps 2 8 3 Pre charging can...

Страница 25: ...y charge refrigerant INFORMATION The manual refrigerant charge operation will automatically stop within 30 minutes If charging is not completed after 30 minutes perform the additional refrigerant char...

Страница 26: ...esult by 1 1 and select the next higher recommended fuse capacity Example Combining the RXYTQ30 by using the RXYTQ8 RXYTQ10 and RXYTQ12 Minimum circuit ampacity of the RXYTQ8 16 1 A Minimum circuit am...

Страница 27: ...A1P d d e f b a c Q1 Q2 a Unit A master outdoor unit b Unit B slave outdoor unit c Unit C slave outdoor unit d Master slave transmission Q1 Q2 e Outdoor indoor transmission F1 F2 f Outdoor unit other...

Страница 28: ...lt should be removed Attach both cables to the power supply terminal as indicated below L1 L2 L2 N 15 8 To check the insulation resistance of the compressor NOTICE If after installation refrigerant ac...

Страница 29: ...a b c a Front plate b Main PCB with 3 7 segment displays and 3 push buttons c Electrical component box service cover Operate the switches and push buttons with an insulated stick such as a closed ball...

Страница 30: ...e required value is selected you can define the change of value by pushing BS3 1 time Press BS3 again to start operation according to the chosen value 16 1 7 Mode 1 Monitoring settings 1 0 Shows wheth...

Страница 31: ...described below 17 1 Precautions when commissioning CAUTION Do NOT perform the test operation while working on the indoor units When performing the test operation NOT ONLY the outdoor unit but the co...

Страница 32: ...ing communication check with indoor units Check of the stop valves opening Judgement of piping length Abnormalities on indoor units cannot be checked for each unit separately After the test operation...

Страница 33: ...nction code which is displayed on the outdoor unit will indicate a main malfunction code and a sub code The sub code indicates more detailed information about the malfunction code The malfunction code...

Страница 34: ...mperature sensor malfunction R8T open circuit A1P X19A Check connection on PCB or actuator Compressor casing temperature sensor malfunction R8T short circuit A1P X19A Check connection on PCB or actuat...

Страница 35: ...manual unit not ready for leak detection functionality Malfunction code System test run not yet executed system operation not possible Execute system test run Faulty wiring to Q1 Q2 or indoor outdoor...

Страница 36: ...Leak detection function related Unit is not prepared to execute leak detection operation Refer to requirements to be able to execute leak detection operation Indoor unit is out of temperature range fo...

Страница 37: ...600 mm h1 h2 1500 500 F mm d b ABCD Sides along the installation site with obstacles F Front side Suction side In case of an installation site where sides A B C D have obstacles the wall heights of s...

Страница 38: ...Y3S c Heat exchanger n Solenoid valve oil2 Y4S d Fan o 4 way valve main Y1S e Fan motor M1F M2F p 4 way valve sub Y5S f Accumulator q Electrical component box g Expansion valve main Y1E r Service port...

Страница 39: ...1 BS3 A1P Push button switch MODE SET RETURN C A3P Capacitor DS1 DS2 A1P DIP switch E1HC Crankcase heater E3H Drain pan heater option F1U F2U A1P Fuse T 3 15 A 250 V F3U Field fuse F101U A4P Fuse F401...

Страница 40: ...y R24 A4P A7P Resistor current sensor R300 A3P A6P Resistor current sensor R1T Thermistor air R3T Thermistor accumulator R4T Thermistor heat exchanger liquid pipe R5T Thermistor subcool liquid pipe R6...

Страница 41: ......

Страница 42: ......

Страница 43: ......

Страница 44: ...4P546223 1C 2021 11 Copyright 2018 Daikin 4P546223 1 C 0000000 Verantwortung f r Energie und Umwelt...

Отзывы: