9 Relocation

Installation and operation manual

14

RXYLQ10~14T7Y1B*

VRV IV system air conditioner

4P543426-1B – 2020.10

8.2.6

Symptom: White mist comes out of a unit
(Indoor unit)

▪ When humidity is high during cooling operation. If the interior of an

indoor unit is extremely contaminated, the temperature distribution
inside  a  room  becomes  uneven.  It  is  necessary  to  clean  the
interior  of  the  indoor  unit.  Ask  your  dealer  for  details  on  cleaning
the unit. This operation requires a qualified service person.

▪ Immediately  after  the  cooling  operation  stops  and  if  the  room

temperature  and  humidity  are  low.  This  is  because  warm
refrigerant  gas  flows  back  into  the  indoor  unit  and  generates
steam.

8.2.7

Symptom: White mist comes out of a unit
(Indoor unit, outdoor unit)

When the system is changed over to heating operation after defrost
operation.  Moisture  generated  by  defrost  becomes  steam  and  is
exhausted.

8.2.8

Symptom: The user interface reads "U4"
or "U5" and stops, but then restarts after a
few minutes

This is because the user interface is intercepting noise from electric
appliances  other  than  the  air  conditioner.  The  noise  prevents
communication  between  the  units,  causing  them  to  stop.  Operation
automatically restarts when the noise ceases.

8.2.9

Symptom: Noise of air conditioners
(Indoor unit)

▪ A  "zeen"  sound  is  heard  immediately  after  the  power  supply  is

turned  on.  The  electronic  expansion  valve  inside  an  indoor  unit
starts  working  and  makes  the  noise.  Its  volume  will  reduce  in
about one minute.

▪ A  continuous  low  "shah"  sound  is  heard  when  the  system  is  in

cooling  operation  or  at  a  stop.  When  the  drain  pump  (optional
accessories) is in operation, this noise is heard.

▪ A  "pishi-pishi"  squeaking  sound  is  heard  when  the  system  stops

after heating operation. Expansion and contraction of plastic parts
caused by temperature change make this noise.

▪ A low "sah", "choro-choro" sound is heard while the indoor unit is

stopped.  When  another  indoor  unit  is  in  operation,  this  noise  is
heard. In order to prevent oil and refrigerant from remaining in the
system, a small amount of refrigerant is kept flowing.

8.2.10

Symptom: Noise of air conditioners
(Indoor unit, outdoor unit)

▪ A  continuous  low  hissing  sound  is  heard  when  the  system  is  in

cooling  or  defrost  operation.  This  is  the  sound  of  refrigerant  gas
flowing through both indoor and outdoor units.

▪ A  hissing  sound  which  is  heard  at  the  start  or  immediately  after

stopping  operation  or  defrost  operation.  This  is  the  noise  of
refrigerant caused by flow stop or flow change.

8.2.11

Symptom: Noise of air conditioners
(Outdoor unit)

When the tone of operating noise changes. This noise is caused by
the change of frequency.

8.2.12

Symptom: Dust comes out of the unit

When  the  unit  is  used  for  the  first  time  in  a  long  time.  This  is
because dust has gotten into the unit.

8.2.13

Symptom: The units can give off odours

The  unit  can  absorb  the  smell  of  rooms,  furniture,  cigarettes,  etc.,
and then emit it again.

8.2.14

Symptom: The outdoor unit fan does not
spin

During  operation.  The  speed  of  the  fan  is  controlled  in  order  to
optimise product operation.

8.2.15

Symptom: The display shows "88"

This  is  the  case  immediately  after  the  main  power  supply  switch  is
turned  on  and  means  that  the  user  interface  is  in  normal  condition.
This continues for 1 minute.

8.2.16

Symptom: The compressor in the outdoor
unit does not stop after a short heating
operation

This is to prevent refrigerant from remaining in the compressor. The
unit will stop after 5 to 10 minutes.

8.2.17

Symptom: The inside of an outdoor unit is
warm even when the unit has stopped

This is because the crankcase heater is warming the compressor so
that the compressor can start smoothly.

8.2.18

Symptom: Hot air can be felt when the
indoor unit is stopped

Several  different  indoor  units  are  being  run  on  the  same  system.
When another unit is running, some refrigerant will still flow through
the unit.

9

Relocation

Contact  your  dealer  for  removing  and  reinstalling  the  total  unit.
Moving units requires technical expertise.

10

Disposal

This  unit  uses  hydrofluorocarbon.  Contact  your  dealer  when
discarding this unit.

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

Содержание VRV IV RXYLQ10T7Y1B Series

Страница 1: ...Installation and operation manual VRV IV system air conditioner English Installation and operation manual VRV IV system air conditioner RXMLQ8T7Y1B RXYLQ10T7Y1B RXYLQ12T7Y1B RXYLQ14T7Y1B...

Страница 2: ...18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Direktyvose su papildymais Direkt v s un to papildin jumos Smernice v plat...

Страница 3: ...astaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota T...

Страница 4: ...t fan does not spin 14 8 2 15 Symptom The display shows 88 14 8 2 16 Symptom The compressor in the outdoor unit does not stop after a short heating operation 14 8 2 17 Symptom The inside of an outdoor...

Страница 5: ...Outdoor unit installation and operation manual Installation and operation instructions Format Paper in the box of the outdoor unit Installer and user reference guide Preparation of the installation re...

Страница 6: ...ressure side Do NOT use taped wires stranded conductor wires extension cords or connections from a star system They can cause overheating electrical shock or fire Do NOT install a phase advancing capa...

Страница 7: ...y By ensuring this product is disposed of correctly you will help to prevent potential negative consequences for the environment and human health For more information contact your installer or local a...

Страница 8: ...ways have qualified service personnel confirm that the point of leakage has been repaired or corrected before resuming operation WARNING Stop operation and shut off the power if anything unusual occur...

Страница 9: ...and automatic operation Changeover cannot be made with a user interface whose display shows change over under centralised control refer to installation and operation manual of the user interface When...

Страница 10: ...Press the ON OFF button of the user interface Result The operation lamp lights up and the system starts operating 3 Press the air flow direction adjust button only for double flow multi flow corner ce...

Страница 11: ...o perform this work WARNING NEVER replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit to break down or cause a fire...

Страница 12: ...peration the system automatically restarts immediately after power is restored Check if no fuse has blown or breaker is activated Change the fuse or reset the breaker if necessary Malfunction Measure...

Страница 13: ...nsistency Auto address malfunction inconsistency 8 2 Symptoms that are NOT system malfunctions The following symptoms are NOT system malfunctions 8 2 1 Symptom The system does not operate The air cond...

Страница 14: ...s kept flowing 8 2 10 Symptom Noise of air conditioners Indoor unit outdoor unit A continuous low hissing sound is heard when the system is in cooling or defrost operation This is the sound of refrige...

Страница 15: ...2HP 14 16HP 18 20HP 2 0 1 5 1 5 1 2 1 5 1 1 0 7 1 0 0 5 0 5 0 3 0 5 0 0 0 1 0 0 5 0 5 0 5 0 5 0 0 0 Total indoor unit capacity when piping length 30m Total indoor unit capacity when piping length 30m...

Страница 16: ...lation in a commercial and light industrial environment NOTICE This is a class A product In a domestic environment this product may cause radio interference in which case the user may be required to t...

Страница 17: ...be increased depending on the installation place and condition 729 613 929 AB AA a mm Minimum foundation a Anchor point 4 HP AA AB 8 14 1076 1302 Fasten the unit in place using four foundation bolts...

Страница 18: ...eam capacity for D capacity index of unit 1 capacity index of unit 2 E Piping between refrigerant branch kit and indoor unit Pipe size for direct connection to indoor unit must be the same as the conn...

Страница 19: ...with the capacity of the outdoor unit example refnet joint a Outdoor unit capacity type HP 2 pipes 8 10 KHRQ22M29T9 12 22 KHRQ22M64T 24 42 KHRQ22M75T For refnet joints other than the first branch exam...

Страница 20: ...n b Front connection c Right side connection For side connections the knockout hole on the bottom plate should be removed c b a a Large knockout hole b Drill c Points for drilling NOTICE Precautions w...

Страница 21: ...wing guidelines into account Make sure to keep all stop valves open during operation The gas and liquid stop valves are factory closed Do NOT apply excessive force to the stop valve Doing so may break...

Страница 22: ...410A tank siphon system e Vacuum pump f Liquid line stop valve g Gas line stop valve A Valve A B Valve B 3 Recover gas and oil from the spun piping by using a recovery unit CAUTION Do not vent gases i...

Страница 23: ...e a vacuum pump to evacuate the installation 14 3 3 Checking refrigerant piping Setup p p R410A N2 C b c e a g f d A B a Pressure reducing valve b Nitrogen c Weighing scales d Refrigerant R410A tank s...

Страница 24: ...power of some units is turned off the charging procedure cannot be finished properly NOTICE In case of a multiple outdoor system turn on the power of all outdoor units NOTICE Be sure to turn ON the po...

Страница 25: ...io Parameter B Parameter B 8 10 HP 12 14 HP 3 5 kg 3 8 kg Metric piping When using metric piping replace the weight factors in the formula by the ones from the following table Inch piping Metric pipin...

Страница 26: ...outdoor unit operation If Then The additional refrigerant amount is smaller than 10 kg Perform steps 2 3 The additional refrigerant charge is larger than 10 kg Perform steps 2 8 3 Pre charging can be...

Страница 27: ...ional refrigerant charging operation again 14 4 7 Checks after charging refrigerant Are all stop valves open Is the amount of refrigerant that has been added recorded on the refrigerant charge label N...

Страница 28: ...these limits it may result in communication error For non standard combinations Calculate the recommended fuse capacity Formula Calculate by adding the minimum circuit amps of each used unit according...

Страница 29: ...to the Q1 Q2 Out Multi terminals Connecting the wires to the F1 F2 terminals results in system malfunction The wiring for the other systems must be connected to the F1 F2 Out Out terminals of the PCB...

Страница 30: ...pump system it is required to give some input to the PCB of the unit This chapter will describe how manual input is possible by operating the push buttons DIP switches on the PCB and reading the feedb...

Страница 31: ...CE Make sure that all outside panels except for the service cover on the electrical component box are closed while working Close the lid of the electrical component box firmly before turning on the po...

Страница 32: ...1 1 Description 0 Unit is currently not operating under low noise restrictions 1 Unit is currently operating under low noise restrictions 1 2 Shows the status of power consumption limitation operatio...

Страница 33: ...door units and RA DX indoor units are used at the same time 2 83 Description 0 VRV DX indoor unit has mode selection right 1 default RA DX indoor unit has mode selection right setting 16 1 9 To connec...

Страница 34: ...ial Additional refrigerant charge The amount of refrigerant to be added to the unit shall be written on the included Added refrigerant plate and attached to the rear side of the front cover Installati...

Страница 35: ...n and confirm that the abnormality is properly corrected INFORMATION Refer to the installation manual of the indoor unit for detailed malfunction codes related to indoor units 18 Hand over to the user...

Страница 36: ...Check connection on PCB or actuator Discharge temperature sensor malfunction R21T open circuit A1P X29A Check connection on PCB or actuator Discharge temperature sensor malfunction R21T short circuit...

Страница 37: ...ase loss Check if power supply is within range Warning indication Leak detection or refrigerant amount check not performed system operation possible Execute autocharge function see manual unit not rea...

Страница 38: ...utomatic charging nearly finished Prepare for autocharge stopping Automatic charging finished Finish autocharge mode Leak detection function related Unit is not prepared to execute leak detection oper...

Страница 39: ...D Sides along the installation site with obstacles F Front side Suction side In case of an installation site where sides A B C D have obstacles the wall heights of sides A C have no impact on service...

Страница 40: ...ot mounted in switch box Wiring depending on model PCB 1 Refer to the installation or service manual on how to use BS1 BS3 push buttons and DS1 DS2 DIP switches 2 Do not operate the unit by short circ...

Страница 41: ...rminal strip X M A P Terminal strip on PCB X Y Connector Y E Electronic expansion valve Y S Solenoid valve Z C Noise filter ferrite core Z F Noise filter Optional Field supply 21 Disposal NOTICE Do NO...

Страница 42: ......

Страница 43: ......

Страница 44: ...4P543426 1B 2020 10 Copyright 2018 Daikin 4P543426 1 B 0000000 Verantwortung f r Energie und Umwelt...

Отзывы: